Please see test rpt SLB 1 CTU 10‐13‐22 Thanks ED Hooter WSM Dillon Plt Cell phone 318‐452‐8947 Your message is
ready to be sent with the following file or link attachments:
SLB 1 CTU 10‐13‐22
Note: To protect against computer viruses, e‐mail programs may prevent sending or receiving certain types of file
attachments. Check your e‐mail security settings to determine how attachments are handled.
________________________________
The information contained in this email message is confidential and may be legally privileged and is intended only for
the use of the individual or entity named above. If you are not an intended recipient or if you have received this
message in error, you are hereby notified that any dissemination, distribution, or copy of this email is strictly prohibited.
If you have received this email in error, please immediately notify us by return email or telephone if the sender's phone
number is listed above, then promptly and permanently delete this message.
While all reasonable care has been taken to avoid the transmission of viruses, it is the responsibility of the recipient to
ensure that the onward transmission, opening, or use of this message and any attachments will not adversely affect its
systems or data. No responsibility is accepted by the company in this regard and the recipient should carry out such
virus and other checks as it considers appropriate.
________________________________
S. Middle Ground Shoal Dillon 18
PTD 1940980
STATE OF ALASKA
OIL AND GAS CONSERVATION COMMISSION
*All BOPE reports are due to the agency within 5 days of testing*
Submit to:jim.regg@alaska.gov; AOGCC.Inspectors@alaska.gov; phoebe.brooks@alaska.gov
Rig Owner:Rig No.:1 DATE:10/13/22
Rig Rep.:Rig Email:
Operator:
Operator Rep.:Op. Rep Email:
Well Name:PTD #1940980 Sundry #322-540
Operation:Drilling:Workover:x Explor.:
Test:Initial:x Weekly:Bi-Weekly:Other:
Rams:250/4000 Annular:N/A Valves:250/4000 MASP:2860
MISC. INSPECTIONS:TEST DATA FLOOR SAFETY VALVES:
Test Result/Type Test Result Quantity Test Result
Housekeeping P Well Sign P Upper Kelly 0 NA
Permit On Location P Hazard Sec.NA Lower Kelly 0 NA
Standing Order Posted P Misc.NA Ball Type 0 NA
Test Fluid Water Inside BOP 0 NA
FSV Misc 0 NA
BOP STACK:Quantity Size/Type Test Result MUD SYSTEM:Visual Alarm
Stripper 1 1.75"P Trip Tank NA NA
Annular Preventer 0 NA NA Pit Level Indicators NA NA
#1 Rams 1 blind/shear P Flow Indicator NA NA
#2 Rams 1 pipe/slip P Meth Gas Detector NA NA
#3 Rams 0 NA NA H2S Gas Detector NA NA
#4 Rams 0 NA NA MS Misc 0 NA
#5 Rams 0 NA NA
#6 Rams 0 NA NA ACCUMULATOR SYSTEM:
Choke Ln. Valves 2 2"P Time/Pressure Test Result
HCR Valves 0 NA NA System Pressure (psi)2950 P
Kill Line Valves 2 2"P Pressure After Closure (psi)2150 P
Check Valve 1 2" 1502 P 200 psi Attained (sec)15 P
BOP Misc 2 EQ Ports P Full Pressure Attained (sec)65 P
Blind Switch Covers:All stations YES
CHOKE MANIFOLD:Bottle Precharge:1400 P
Quantity Test Result Nitgn. Bottles # & psi (Avg.):NA NA
No. Valves 5 P ACC Misc 0 NA
Manual Chokes 2 P
Hydraulic Chokes 0 NA Control System Response Time:Time (sec)Test Result
CH Misc 0 NA Annular Preventer 0 NA
#1 Rams 12 P
Coiled Tubing Only:#2 Rams 8 P
Inside Reel valves 1 P #3 Rams 0 NA
#4 Rams 0 NA
Test Results #5 Rams 0 NA
#6 Rams 0 NA
Number of Failures:0 Test Time:4.0 HCR Choke 0 NA
Repair or replacement of equipment will be made within NA days. HCR Kill 0 NA
Remarks:
AOGCC Inspection
24 hr Notice YES Date/Time 10/10/22 14:37PM
Waived By
Test Start Date/Time:10/13/2022 14:30
(date)(time)Witness
Test Finish Date/Time:10/13/2022 18:30
BOPE Test Report
Notify the AOGCC of repairs with written confirmation to: AOGCC.Inspectors@alaska.gov
Jim Regg
Schlumberger
A push / pull test was performed on Slip rams.
Karmen Karns
Hilcorp Alaska
Howard Hooter
S MGS Unit 18
Test Pressure (psi):
KKarns@slb.com
howard.hooter@hilcorp.com
Form 10-424 (Revised 08/2022)2022-1013_BOP_SLB1_SMGS_Dillon-18
jbr
J. Regg; 11/22/2022