BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - CENTRAL GAS FACILITY
GAS FLARING INCIDENT REPORT
January 2016
Unplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
1/21/2016 0930-0940 43 Not required for unplanned events <= 1 hr Not required for unplanned events <= 1 hr
1/21/2016 1355-1405 43
1/27/2016 0315-0346 255
TOTAL 341
l
See attachments
TOTAL 0
AL ION TAKEN TO I
See attachments
1/12/2016 1415-1425
--- •• --^—
387 See attachments
AuwN IAKeN IU ELIMINATE CAUSE
1/31/2016 0350-0400
430
See attachments
TOTAL
817
Planned Events Exceeding -1 Hour OR > 5,000 mcf
DATE TIME
VOLUME DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
See attachments
TOTAL
0
TOTAL
Unplanned Events < 1 Hour
341
Unplanned Events > 1 Hour
0
Planned Events < 1 hour and not
817
exceeding 5,000 MCF
Planned Events> 1 hour or
0
exceeding 5,000 MCF
Pilot Purge
22,289
Assist
41,498
TOTAL FLARED VOLUME
64,945
Page 2
2/12/2016
2:27 PM
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000008
2. Facility Name
PBU CGF B
3. Field
PBU - EOA
4. Operator
BP
5. MonthNear of Disposition
I February -2016
Disposition
Volume MCF
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
6. Sold
1,463,570
Pool Name Pool Code Percent
7. Reinjected
4,784,788
PRUDHOE 640150 100.00%
8. Flared or vented 1 hour or less
1,647
9. Flared or vented more than 1 hour (see instr.)
0
10. Pilot and Purge
21,055
11. Assist Gas
37,906
12. Fuel gas used in lease operations.
2,685,370
13. Other (see instructions)
Q
Official Use Only
Authorization >7 hr:
Safety
MCF
14. TOTAL VOLUME (ITEMS 6-12)
8,994,336
Lease Use
MCF
15. NGL Gas Equivalent
1,463,570
Conservation
MCF
16. Purchased gas
Waste:
MCF
17. Transferred from: FSI, FS2, FS3, GC1, GC2 & GC3
215,251,704
18. Transferred to: (Express as a negative #) FSI, FS2, FS3, CCP & GPMA
-206,257,369
Commissioner Date
19. Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 1,877,510 mscf
I hereby certify that the foregoing is true and correct to the best of my knovAedge.
Note: All volumes must be corrected
Signature Title Mana er Production Taxes and Royalties Alaska t0 pressure of 14.65 psia and t0 a
temperature of 60o F. Authority 20
Printed Name Diane Colley Phone (907) 564-5775 Date AAC25.235.
Form 10-422 Rev. 512009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT- CENTRAL GAS FACILITY
GAS FLARING INCIDENT REPORT
February 2016
junplanneo Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
2/5/2016 1738-1745 430 Not required for unplanned events <= 1 hr Not required for unplanned events <= 1 hr
2/24/2016 0524-0534 387
2/26/2016 1644-1712 400
TOTAL 1,217
See attachments
See attachments
TOTAL 0
Planned Events Less Than or Equal 1 Hour AND <= 5,000 mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
2/24/2016 0524-0534 430 See attachments See attachments
TOTAL 430
Planned Events Exceeding 1 Hour OR > 5,000 mcf
TOTAL
Unplanned Events < 1 Hour
Unplanned Events > 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events > 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
A
TOTAL
1,217
0
430
0
21,055
37,906
60,608
See attachments
See attachments
Page 3
3/11/2016
3:27 PM
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000008
2. Facility Name
PBU TGF B
3. Field
PBU - EOA
4. Operator
BP
5. MonthNear of Disposition
I March -2016
Disposition
Volume MCF
20. Forproduction from multiple pools, list contribution of each pool as a percent of
Total Volume,
6. Sold
1,501,945
Pool Name Pool Code Percent
7. Reinjected
5,062,200
PRUDHOE 640150 100.00%
8. Flared or vented 1 hour or less
10,430
9. Flared or vented more than 1 hour (see Irish.)
135,998
10. Pilot and Purge
23,308
11. Assist Gas
47,113
12. Fuel gas used in lease operations.
3,090,384
13. Other (see instructions)
Official Use Onlyctions)
Authorization >7 hr:
Safety
22 qqQ
MCF
14. TOTAL VOLUME (ITEMS 6-12)
9,871,378
Lease Use
MCF
15. NGL Gas Equivalent
1,501,945
Conservation
MCF
16. Purchased gas
0
Waste:
MCF
17. Transferred from: FS1, FS2, FS3, GC1, GC2 & GC3
233,061,469
Commissioner Date
18. Transferred to: (Express as a negative #) FS1, FS2, FS3, CCP & GPMA
-223,190,091
19. Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 1,606,580 mscf
I hereby certify that the foregoing is true and correct to the best of my knowledge.
Note: All volumes must be corrected
Signature Title Mana er Production Taxes and Ro allies Alaska to pressure of 14.65 psia and to a
temperature of 60o F. Authority 20
Printed Name Diane Colley Phone (907) 564-5775 Date `j �� 6 AAC25.235.
t/TL
5/¢/!j�
Form 10-422 Rev. 5/1009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - CENTRAL GAS FACILITY
GAS FLARING INCIDENT REPORT Page 2
March 2016
Unplanned events less than or equal to 1 hour
DATE
TIME
VOLUME DESCRIPTION OF INCIDENT &CAUSE ACTION TAKEN TO ELIMINATE CAUSE
3/11/2016
1411-1427
2,000 Not required for unplanned events <= 1 hr Not required for unplanned events <=1 hr
3/14/2016
0830-0930
8,000
3/27/2016
1400-1415
43
3/30/2016
1257-1310
387
Assist
TOTAL
10,430
unplanned events greater than 1 hour
GATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN 70 ELIMINATE CAUSE
3/11/2016 1411-1545 88,000 See attachments See attachments
3/12/2016 0001-1428 30,796
3/30/2016 1257-1501 17,202
TOTAL 135,998
Planned events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
See attachments See attachments
TOTAL 0
See attachments See attachments
TOTAL 0
4/14/2016
1:52 PM
TOTAL
Unplanned Events < 1 Hour
10,430
Unplanned Events > 1 Hour
135,998
Planned Events < 1 hour and not
0
exceeding 5,000 MCF
Planned Events> 1 hour or
0
exceeding 5,000 MCF
Pilot Purge
23,308
Assist
47,113
TOTAL FLARED VOLUME
216,849
4/14/2016
1:52 PM
Link, Liz M (DOA)
From: AK, OPS PCC EOC TL <AKOPSPCCEOCTL@bp.com>
Sent: Wednesday, April 06, 2016 4:34 PM
To: AOGCC Reporting (DOA sponsored)
Cc: Loepp, Victoria T (DOA); Benson, Gary A; Arthur, Gregory; AK, OPS CCP CGF OSM;
Fortenberry, Christopher; AK, OPS GC3&PCC OSM; AK, HSSEE Env Adv Central; Glover,
Robin; AK, OPS CGF OTL; Kain, Rachel B
Subject: Gas flaring event at CGF
To: AOGCC Reporting
Aogcc.reporting (c alaska.gov
CC: Victoria Leopp, AOGCC
victoria. loepi)q alasks.goy
From: David Spall, GPB Production Optimization Team Leader
A flaring event occurred at CGF starting at 03/30/2016 12:57 and stopping at 03/30/2016 15:01 with a volum o 17202
(MSCF). The event lasted for 124 minutes and was due to T\C 1805 MI 1 Shutdown on control problem/ recyc i er
660. Residue gas flare meter 664. The event stopped when we repaired and restarted MI Compressor T/C 1805.
Thanks,
David Spall
PCC/EOC Production Optimization Team Lead (Alt Jennifer Blake)
Office 907-659-4472
Cell 219-689-4036
David.spall@bp.com
Link, Liz M (DOA)
From:
AK, OPS PCC EOC TL <AKOPSPCCEOCTL@bp.com>
Sent:
Monday, March 21, 2016 3:16 PM
To:
AOGCC Reporting (DOA sponsored)
Cc:
Loepp, Victoria T (DOA); Benson, Gary A; Arthur, Gregory; AK, OPS CCP CGF OSM;
Fortenberry, Christopher; AK, OPS GC3&PCC OSM; AK, HSSEE Env Adv Central; Glover,
Robin; AK, OPS CGF OTL; Kain, Rachel B
Subject:
Gas flaring event at CGF
To: AOGCC Reporting CC: Victoria Leepp, AOGCC
Aogcc.reportingC&alaska.gov victoria.loepp(a alaska.gov
From: Jennifer Blake, GPB Production Optimization Team Leader
A flaring event occurred at CGF starting at 03/14/2016 08:30 and stopping at 03/14/2016 09:30 with a volume o 8000
(MSCF). The event had a volume greater than 5000 (MSCF) and was due to purging and warming the HP -6 flare le
to relight the pilot and return to it service. The event stopped when the pilot was relit and the flare valve was closed.
Thanks,
Jennifer Blake
PCC/EOC Production Optimization Team Lead (alt David Spall)
Office (907) 659-4472
Cell (907) 830-6204
lennifer.blakeC@bp.com
Link, Liz M (DOA)
From:
AK, OPS PCC EOC TL <AKOPSPCCEOCTL@bp.com>
Sent:
Sunday, March 13, 20167:59 PM
To:
AOGCC Reporting (DOA sponsored)
Cc:
Loepp, Victoria T (DOA); Benson, Gary A; Arthur, Gregory; AK, OPS CCP CGF OSM;
Fortenberry, Christopher; AK, OPS GC3&PCC OSM; AK, HSSEE Env Adv Central; Glover,
Robin; AK, OPS CGF OTL; Kain, Rachel B
Subject:
Gas flaring event at CGF
To: AOGCC Reporting
Aogcc.reporting()alaska.gov
CC: Victoria Leopp, AOGCC
victoria. Ioepp(o)alaska.gov
From: David Spall, rastedfor
ction Optimization Team Leader
A flaring event occustarting at 03/11/2016 14:11 and stopping at 03/11/201 15:45 with a volume of 90000
(MSCF). The event minutes and was due to Power loss caused plant blow own. Residue gas flare meter
664. The event stope Plant de -pressured.
A flaring event occurred at CGF starting at 03/1112016 14:11 and stopping at 03/12/2016 14:28 with a volume of 30796
(MSCF). The event lasted for 867 minutes and was due to Plant shutdown due to power loss. stabilizer flaring meter 660.
The event stopped when the plant was started.
Thanks,
David Spall
PCC/EOC Production Optimization Team Lead (Alt Jennifer Blake)
Office 907-659-4472
Cell 219-689-4036
David.spall@bp.com
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000008
2. FaaCy Name
PB CGF B
3. Field
PBU - EOA
4. Operator
BP
5. MonthNear of Disposition
Aril -2016
Disposition
Volume MCF
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
6. Sold
1,000,976
Pool Name Pool Code Percent
7. Reinjected
3,708,240
PRUDHOE 640150 100.00%
8. Flared or vented l hour or less
163,592
9. Flared or vented more than 1 hour (see inso.)
313,559
10. Pilot and Purge
23,090
11. Assist Gas
56,501
12. Fuel gas used in lease operations.
2,401, 568
13. Other (see instructions)
U
Official Use Only
Authorization >7 hr:
Safety
d
MCF I/r
14. TOTAL VOLUME (ITEMS 6.12)
7,667,526
Lease Use
MCF
15. NGL Gas Equivalent
1,000,976
Conservation
MCF
16. Purchased gas
0
Waste:
MCF
17. Transferred from: FS1. FS2, FS3, GC1, GC2 & GC3
187,641,391
_2 —
14
Commissioner Date
18. Transferred to: (Express as a negative #) FS1, FS2, FS3, CCP & GPMA
-179,973,867
19. Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 1,190,838 tract
I hereby certify that the foregoing istrue and correct to the best of my knowledge.
Note: All volumes must be corrected
Signature_ �(l��; u[ ��6d! Title Manager Production Taxes and Ro alties Alaska to pressure of 14.65 psi8 and to a
/� temperature of 60o F. Authority 20
Printed Name Diane Colley Phone (907) 564-5775 Date f AAC25.235.
Form 10-422 Rev. 512009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT- CENTRAL GAS FACILITY
GAS FLARING INCIDENT REPORT
April 2016
Unplanned events less than or equal to 1 hour
DATE
TIME
VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
4/9/2016
1450-1502
497 Not required for unplanned events <= 1 hr Not required for unplanned events <= 1 hr
4/14/2016
1959-2008
111
4/19/2016
1122-1136
400
4/24/2016
0635-0645
400
4/24/2016
0635-0645
195
4/24/2016
0635-0645
387
4/24/2016
0635-0645
400
4/24/2016
0635-0645
400
4/24/2016
0635-0639
375
4/24/2016
0635-0645
400
4/24/2016
0635-0650
130
4/24/2016
0635-0650
130
4/24/2016
0640-0658
60
4/24/2016
0641-0700
93,000
4/25/2016
0058-0110
195
4/25/2016
0058-0110
430
4/25/2016
0058-0115
255
4/25/2016
0058-0110
430
4/25/2016
0109-0154
150
4/26/2016
1705-1715
400
4/26/2016
1705-1715
430
4/26/2016
1705-1715
400
4/26/2016
1705-1715
430
4/26/2016
1715-1735
62,000
TOTAL
162,005
nrvm vULOME DESCRIPTION OF IN
4/11/2016 1721-2247 56 See attachments
4/25/2016 0105-0230 232,000
4/28-30/16 1000-1159 81,503
TOTAL 313,559
See attachments
Page 4
5/16/2016
3:44 PM
events less than or
4/17/2016
0034-0055
4/18/2016
0103-0115
4/20/2016
0026-0044
4/22/2016
1650-1700
exceeding 5,000 MCF
TOTAL
to 1 hour
events ereater than 1 hour
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - CENTRAL GAS FACILITY
GAS FLARING INCIDENT REPORT
April 2016
400 See attachments
400
400
387
1,587
DESCRIPTION OF IN
See attachments
TOTAL 0
[4711114
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
Page 5
5/16/2016
3:44 PM
TOTAL
Unplanned Events < 1 Hour
162,005
Unplanned Events > 1 Hour
313,559
Planned Events < 1 hour and not
1,587
exceeding 5,000 MCF
Planned Events > 1 hour or
0
exceeding 5,000 MCF
Pilot Purge
23,090
Assist
56,501
TOTAL FLARED VOLUME
556,742
[4711114
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
Page 5
5/16/2016
3:44 PM
Link, Liz M (DOA)
From:
AK, OPS PCC EOC TL <AKOPSPCCEOCTL@bp.com>
Sent:
Tuesday, April 12, 2016 6:19 AM
To:
AOGCC Reporting (DOA sponsored)
Cc:
Loepp, Victoria T (DOA); Benson, Gary A; Arthur, Gregory; AK, OPS CCP CGF OSM;
Fortenberry, Christopher; AK, OPS GC3&PCC OSM; AK, HSSEE Env Adv Central; Glover,
Robin; AK, OPS CGF OTL; Kain, Rachel B
Subject:
Gas flaring event at CGF
To: AOGCC Reporting
Aogcc.reportinq(o)alaska.gov
CC: Victoria Leopp, AOGCC
victoria. loepp(a?alaska. qov
From: David Spall, GPB Production Optimization Team Leader
A flaring event occurred at CGF starting at 04/11/2016 17:21 and stopping at 04/11/2016 22:47 with a volume of 56
(MSCF). The event lasted for 326 minutes and was due to Changes in the plant while returning LTS 1 to operation after a
derime caused the MI overhead to swell up and bump flare. Volume recorded on Meter 660. The event stopped when
Ops responded to lower the Stabilizer overhead pressure and stop flaring..
Thanks,
David Spall
PCC/EOC Production Optimization Team Lead (Alt Jennifer Blake)
Office 907-659-4472
Cell 219-689-4036
David.spall@bp.com
Link, Liz M (DOA)
From: AK, OPS PCC EOC TL <AKOPSPCCEOCTL@bp.com>
Sent: Sunday, May 15, 2016 12:27 PM
To: AOGCC Reporting (DOA sponsored)
Cc: Loepp, Victoria T (DOA); Benson, Gary A; Arthur, Gregory; AK, OPS CCP CGF OSM;
Fortenberry, Christopher, AK, OPS GC3&PCC OSM; AK, HSSEE Env Adv Central; Glover,
Robin; AK, OPS CGF OTL; Kain, Rachel B
Subject: Gas flaring event at CGF
To: AOGCC Reporting CC: Victoria Leopp, AOGCC
Aogcc.reportinq(a)alaska.gov victoria.loepp(d2alaska.gov
From: Jennifer Blake, GPB Production Optimization Team Leader
A flaring event occurred at CGF starting at 04/28/2016 10:00 and stopping at 04/29/2016 24:00 with a volume of 17000
(MSCF). The event lasted for 840 minutes and was due to starting up the plant's process and awaiting M/I Compressor
availability. The event was ongoing until the MI compressor started on 5/1/2016.
A flaring event occurred at CGF starting at 04/29/2016 00:00 and stopping at 04/30/2016 24:00 with a volume of 21500
(MSCF). The event lasted for 1440 minutes and was due to starting up the plant's process and awaiting M/I Compressor
availability. The event was ongoing until the MI compressor started on 5/1/2016.
A flaring event occurred at CGF starting at 04/30/2016 00:00 and stopping at 05/01/2016 24:00 with a volume of 36600
(MSCF). The event lasted for 1440 minutes and was due to starting up the plant's process and awaiting M/I Compressor
availability. The event stopped when the MI Compressor started up on 5/1/2016.
Thank you,
Jennifer Blake
PCC/EOC Production Optimization Team Lead (alt David Spall)
Office (907) 659-4472
Cell (907) 830-6204
Jennifer.blake@bp.com
a
Link, Liz M (DOA)
From: AK, OPS PCC EOC TL <AKOPSPCCEOCTL@bp.com>
Sent: Thursday, May 05, 2016 10:25 AM
To: AOGCC Reporting (DOA sponsored)
Cc: Loepp, Victoria T (DOA); Benson, Gary A; Arthur, Gregory; AK, OPS CCP CGF OSM;
Fortenberry, Christopher; AK, OPS GC3&PCC OSM; AK, HSSEE Env Adv Central; Glover,
Robin; AK, OPS CGF OTL; Kain, Rachel B
Subject: Gas flaring event at CGF
To: AOGCC Reporting
AoQcc. reporti ng(c)alaska.gov
CC: Victoria Leopp, AOGCC
victoria. loepp()alaska. clov
From: David Spall, GPB Production Optimization Team Leader
A flaring event occurred at CGF starting at 04/24/2016 06:41 and stopping at 04/24/2016 07:00 with a volume of 93000
(MSCF). The event lasted for 19 minutes and was due to Residue gas to CCP P203 opened during the field wide power
failure due to high pressure venting down the gas transit line to normal pressure. Meter 664. The event stopped when
Gas transit line pressure dropped to normal pressure and P 203 flare valve closed.
A flaring event occurred at CGF starting at 04/25/2016 01:05 and stopping at 04/25/2016 02:30 with a volume of 23200
(MSCF). The event lasted for 85 minutes and was due to P 203 Residue gas to flare opened up during the second field
wide power failure venting down the gas transit lines due to high pressure. Meter 664. The event stopped when P203
closed when the gas transit line pressure dropped to normal pressure.
A flaring event occurred at CGF starting at 04/26/2016 17:15 and stopping at 04/26/2016 17:35 with a volume of 62000
(MSCF). The event lasted for 20 minutes and was due to Another power failure: P 203 Residue gas to flare opened to
relieve gas transit line over pressure. Meter 664. The event stopped when Gas transit line pressure came down to normal
pressure and P203 closed
A flaring event occurred at CGF starting at 04/30/2016 18:28 and stopping at 04/30/2016 23:59 with a volume of 6403
(MSCF). The event lasted for 331 minutes and was due to Plant start up after power loss. The event stopped when Flare
valve closed
Thanks,
David Spall
PCC/EOC Production Optimization Team Lead (Alt Jennifer Blake)
Office 907-659-4472
Cell 219-689-4036
David.spall@bp.com
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000008
2. Facility Name
PBU CGF B
3. Field
PBU - EOA
4. Operator
BP
5. MonthNear of Disposition
May -2016
Disposition
Volume MCF
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
6. Sold
1,321.382
Pool Name Pool Code Percent
7. Reinjected
5,277,293
PRUDHOE 640150 100.00%
8. Flared or vented 1 hour or less
65,476
9. Flared or vented more than 1 hour (see instr.)
36,186
10. Pilot and Purge
24,550
11, Assist Gas
53,276
12. Fuel gas used in lease operations.
2,783,720
13. Other (see instructions)
Q
Official Use Only
Authorization >1 hr:
Safety
� � (8
MCF
14. TOTAL VOLUME (ITEMS 6.12)
9,561,883
Lease Use
MCF
15. NGL Gas Equivalent
1,321,382
Conservation
MCF
16. Purchased gas
Q
Waste:
MCF
17. Transferred from: FS1, FS2, FS3, GC1, GC2 & GC3
212,023,416
7-2z
18. Transferred to: (Express as a negative #) FS1, FS2, FS3, CCP & GPMA
-202,461,531
mmissioner Date
19. Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 318,141 mscf
I hereby certify that the foregoing is true and correct to the best of my knowledge.
Note: All volumes must be corrected
Signature Title Manager Production Taxes and Ro alties Alaska to pressure Of 14.65 psia and to a
/1 / temperature of 60o F. Authority 20
Printed Name Diane ColleyPhone (907) 564-5775 Date /.k / r AAC25.235.
Y T t --
-?-/f8 /l�—
Form 10-422 Rev. 512009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - CENTRAL GAS FACILITY
GAS FLARING INCIDENT REPORT
May 2016
junplanned events less than or equal to 1 hour
5/DATE 2011-2016EVOLUME 38 Notrequired OF IN IIDENT & "E hr ACTION
TAKEN TO ELIMINATE CAUSE
Af N TAIL
unplanned events <= 1 t required for unplanned events <= 1 hr
5/21/2016 1004-1027 400
TOTAL 438
5/1/2016 0000-2400
36,186 See attachments
See attachments
TOTAL
36,186
Planned events less than or equal to 1 hour
DATE - TIME
VOLUME DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
5/2/2016 1150-1153
38 See attachments
See attachments
5/13/2016 2143-2231
65,000
TOTAL
65,038
Planned events greater than 1 hour
DATE TIME
VOLUME DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
See attachments
TOTAL
0
TOTAL
Unplanned Events < 1 Hour
438
Unplanned Events> 1 Hour
36,186
Planned Events < 1 hour and not
65,038
exceeding 5,000 MCF
Planned Events > 1 hour or
0
exceeding 5,000 MCF
Pilot Purge
24,550
Assist
53,276
TOTAL FLARED VOLUME
179,488
Page 3
6/15/2016
2:44 PM
Link, Liz M (DOA)
From:
AK, OPS PCC EOC TL <AKOPSPCCEOCTL@bp.com>
Sent:
Wednesday, May 18, 2016 9:28 AM
To:
AOGCC Reporting (DOA sponsored)
Cc:
Loepp, Victoria T (DOA); Benson, Gary A; Arthur, Gregory; AK, OPS CCP CGF OSM;
Fortenberry, Christopher; AK, OPS GC3&PCC OSM; AK, HSSEE Env Adv Central; Glover,
Robin; AK, OPS CGF OTL; Kain, Rachel B
Subject:
Gas flaring event at CGF
To: AOGCC Reporting CC: Victoria Leopp, AOGCC
Aogcc. reoortingCaoalaska. qov victoria. loeppoalaska. qov
From: Jennifer Blake, GPB Production Optimization Team Leader
A flaring event occurred at CGF starting at 05/01/2016 00:00 and stopping at 05/02/2016 with a volume of 36186 (MSCF).
The event lasted for 1440 minutes and was due to starting up the plant's process and awaiting M/I Compressor
availability. The event stopped when the MI Compressor started up on 5/1/2016. The flaring event was intermittent.
A flaring event occurred at CGF starting at 05/13/2016 21:43 and stopping at 05/13/2016 22:31 with a volume of 65000
(MSCF) and was due to testing flare staging valve operation. The event stopped when flare testing was completed,
01 P2031C closed and flare valves closed.
Thank you,
Jennifer Blake
PCC/EOC Production Optimization Team Lead (alt David Spall)
Office (907) 659-4472
Cell (907) 830-6204
Jennifer.blake@bp.com
Link, Liz M (DOA)
From:
AK, OPS PCC EOC TL <AKOPSPCCEOCTL@bp.com>
Sent:
Thursday, June 09, 2016 11:03 AM
To:
AOGCC Reporting (DOA sponsored)
Cc:
Loepp, Victoria T (DOA); Benson, Gary A; Arthur, Gregory; AK, OPS CCP CGF OSM;
Fortenberry, Christopher; AK, OPS GC3&PCC OSM; AK, HSSEE Env Adv Central; Glover,
Robin; AK, OPS CGF OTL; Buckbee, Rachel A
Subject:
Flaring event at CGF
To: AOGCC Reporting CC: Victoria Leopp, AOGCC
Aogcc.reporting(a)alaska.gov victoria.loeppna alaska.gov
From: Jennifer Blake, GPB Production Optimization Team Leader
A flaring event occurred at CGF starting at 06/07/2016 14:40 and stopping at 06/07/2016 17:08 with a volume of 20276
(MSCF). The event lasted for 148 minutes and was due to Turbine compressor 1805 shutdown due to a problem
associated with the P-217SV closed limit switch. The event stopped when equipment was restarted.
Thanks,
Jennifer Blake
PCC/EOC Production Optimization Team Lead (alt David Spall)
Office (907) 659-4472
Cell (907) 830-6204
Jennifer.blake@bp.com
Flare Start Date 05/01/2016
Flare End Date 05/31/2016
CGF Flare Report Total Volume (MSCF) 101662
Report
Numbs System Date Start Time Stop Time Duration Intsmlittent Black Smoke Planned Reported By Volume
16-164 Flare Relief 05/01/2016 12:00:00 am 12:00:00 am 1440 min Yes No
Determination Cause Plant Process coming online. Awaiting M/I Compressor start-up
Action Taken M/I Compressor started upon 5/1/16.
16-149 Flare Relief 05/02/2016 11:50:00 am 11:5300 am 3 min No No
Determination Cause T\C 1855 planned maintenance for vibration study of compressor recycle valve F85AV
Action Taken Completed troubleshooting, reloaded 1855 T/C, and stabilized facility process and operation.
No BP1\BOLDJT 36186
Daily Volume (MSCF) 36186
Yes BPI\VINZANRA 38
Daily Volume (MSCF) 38
16-160 Flare Relief 05/13/2016 9:43:00 pm 10:31:00 pm 48 min No No Yes BP1ZRAMBL 65000
Determination Cause Extended Baring event occurred while checking Flare staging valve operation.
Action Taken Flare testing complete. O1 P2031C closed and flare valves closed.
Daily Volume (MSCF) 65000
Total Volume (MSCF) 101662
Generated 06/07/2016 4:33:28PM Page 3 of 9
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number2.
0290000008
Facility Name
PBU CGF B
3. Field
PBU - EOA
4. Operator
BP
5. Month/Year of Disposition
June -2016
Disposition
Volume MCF
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
6. Sold
1,109,876
Pool Name PoolCode Percent
7. Reinjected
4,559,088
PRUDHOE 640150 100.00%
8. Flared or vented 1 hour or less
2,422
9. Flared or vented more than 1 hour (see Instr.)
64,531
10. Pilot and Purge
23,521
11. Assist Gas
60,116
12. Fuel gas used in lease operations.
2,235,653
13. Other (see instructions)
p
Official Use Only
Authorization>1 M:
Safety
/� 2/
[o
MCF
14. TOTAL VOLUME (ITEMS 6.12)
6,055,207
Lease Use
MCF
15. NGL Gas Equivalent
1,109,876
Conservation
MCF
16. Purchased gas
U
Waste:
MCF
IT Transferred from: FSI, FS2, FS3, GCT, GC2 & GC3
180,975,568
7"Lt' 7 /
18. Transferred to: (Express as a negative #) FST, FS2, FS3, CCP & GPMA
-172,920,360
If Corfirnissioner Datte
19. Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 881,446 mscf
I hereby certify that the foregoing is true and correct to the best of my knowledge.
Note: All volumes must be corrected
Signatu ay` Title Manager Production Taxes and Ro alties Alaska to pressure of 14.65 psis and to a
I temperature of 60o F. Authority 20
Diane Cole P
Printed Name hone (907) 564-5775 Dale AAC25.235.
Form 10-422 Rev. 5/2009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - CENTRAL GAS FACILITY
GAS FLARING INCIDENT REPORT
June 2016
6/4/2016
1633-1713
53 Not required for unplanned events <= 1 hr
6/4/2016
1700-1715
387
6/9/2016
1440-1450
387
6/10/2016
1245-1255
400
6/26/2016
0251-0317
190
6/26/2016
0327-0338
190
6/26/2016
1121-1159
195
190
TOTAL
1,802
Not required for unplanned events <= 1 hr
6/7/2016
1440-1708
20,276 See attachments See attachments
6/26/2016
0216-0507
229
6/29/2016
0122-1229
42,026
TOTAL
62,531
Planned events less than or equal to 1 hour
DATE
TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
6/15/2016
2330-2359
430 See attachments See attachments
6/29/2016
1615-1635
190
TOTAL
620
6/19-20/2016 1612-2359
TOTAL
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
2,000 See attachments
2,000
TOTAL
1,802
62,531
620
2,000
23,521
60,116
150,590
See attachments
Page 3
7/18/2016
3.41 PM
Flare Start Date 06/01/2016
Flare End Date 0 613 0/2 01 6
CGF Flare Report
Total Volume (MSCF) 66953
Report
Numbe System Date Start Time Stop Time Duration Intermittent Black Smoke Planned Reported By Volume
16-190 Controlled Blowdown 06/07/2016 2:40:00 pm 5:08:00 pm 148 min No No
Determination Cause T\C 1805 shutdown due to a problem associated with P-217SV closed limit switch
Action Taken Equipment was restarted at 16:48
No BP1\BUCHR8 20276
Daily Volume (MSCF) 20276
Determination Cause Plant shut down for TAPS outage
Action Taken Flare valve closed
Generated 07/06/2016 1:44:03PM Page 3 of 11
16-200 Controlled Blowdown 06/15/2016 11:30:00 pm 11:59:00 pm 29 min No
No Yes BP1\GONDEO
430
Determination Cause
TC 1886 shutdown for planned maintenance
Action Taken
1886 TIC depressurization completed.
Daily Volume (MSCF)
430
16-211 Other
06/19/2016 4:12:00 pm 11:59:00 pm 467 min No
Yes Yes BP1\BOLDJT
1300
Determination Cause
Blowing down INDIA MI Line starting at 275 psig to LP Flare header. Black smoke was at the BPD from LP Flare blowcase dumps due to
JIT. Black Smoke Tr@ction item report number is IR -5278637
Action Taken
Continuous Baring for support of INCA line lifts and repair work on MI system.
Daily Volume (MSCF)
1300
16-212 Other
06/20/2016 12:00:00 am 11:59:00 pm 1439 min No
No Yes BP1\BOLDJT
700
Determination Cause
Flaring WOA MI line to LP Bare in support of WOA Ml line lifts and otherwork.
Updated meter 618 to reflect the volume
Action Taken
Blocked in flare when pressure was at an acceptable low.
Daily Volume (MSCF)
700
16-218 Flare Relief 06/26/2016 2:16:00 am 5:07:00 am 171 min No
No No BP1\CONNK7
229
Determination Cause Plant shut down for TAPS outage
Action Taken Flare valve closed
Generated 07/06/2016 1:44:03PM Page 3 of 11
Flare Start Data 06/01/2016
Flare End Date 06/30/2016
Flare valves closed
16-226 Controlled Blowdown 06/29/2016 1:22:00 am 12:29:00 pm 667 min No No No BPI\CONNK7 42026
Determination Cause starting plant up after TAPS outage
Action Taken Stated off-line T/C, and stabilized facility process and operation
16-226 Controlled Blowdown 06/29/2016 4:15:00 pm 4:35:00 pm 20 min No No Yes BPI\OKINELKJ 190
Determination Cause S/D 1883 Tandem 1 (Type'A').
Action Taken 1883 de -pressured to 40 psig.
Daily Volume (MSCF) 42216
Total Volume (MSCF) 66953
Generated 07/06/2016 1:44:03PM Page 4 of 11
Link, Liz M (DOA)
From: AK, OPS PCC EOC TL <AKOPSPCCEOCTL@bp.com>
Sent: Thursday, June 23, 2016 4:59 PM
To: AOGCC Reporting (DOA sponsored)
Cc: Loepp, Victoria T (DOA); Benson, Gary A; Arthur, Gregory; AK, OPS CCP CGF OSM;
Fortenberry, Christopher, AK, OPS GC3&PCC OSM; AK, HSSEE Env Adv Central; Glover,
Robin; AK, OPS CGF OTL, Buckbee, Rachel A
Subject: Flaring event at CGF
To: AOGCC Reporting CC: Victoria Leopp, AOGCC
Aoocc.reportinona alaska.gov victoria.loepp(d-)alaska.gov
From: Jennifer Blake, GPB Production Optimization Team Leader
A flaring event occurred at CGF starting at 06/20/2016 00:00 and stopping at 06/20/2016 23:59 with a volume of 700
(MSCF). The event lasted for 1439 minutes and was due to depressurization of the WOA MI line to support planned line
lifts and other work on the WOA MI system. The event stopped when depressurization of the WOA MI Line was
completed.
Thanks,
Jennifer Blake
PCC/EOC Production Optimization Team Lead (alt David Spall)
Office (907) 659-4472
Cell (907) 830-6204
Jennifer.blake@bp.com
Link, Liz M (DOA)
From: AK, OPS PCC EOC TL <AKOPSPCCEOCTL@bp.com>
Sent: Thursday, July 07, 2016 2:48 PM
To: AOGCC Reporting (DOA sponsored)
Cc: Loepp, Victoria T (DOA); Benson, Gary A; Arthur, Gregory; AK, OPS CCP CGF OSM;
Fortenberry, Christopher; AK, HSSEE Env Adv Central; Glover, Robin; AK, OPS CGF OTL;
Buckbee, Rachel A
Subject: Flaring events at CGF
To: AOGCC Reporting CC: Victoria Leopp, AOGCC
Aogcc.reporting(cDalaska.gov victoria.loepp(d)alaska.gov
From: Jennifer Blake, GPB Production Optimization Team Leader
A flaring event occurred at CGF starting at 06/19/2016 16:12 with a volume of 1300 (MSCF) for the day of 6/19. The event
was due to depressurization of the WOA MI tine to support planned line lifts and other work on the WOA MI system. The
event continued into 6/20. The flare report for 6/20 was submitted separately on 6/23/16.
A flaring event occurred at CGF starting at 06/25/2016 00:37 and stopping at 06/25/2016 05:07 with a volume of 229
(MSCF). The event lasted for 270 minutes and was due to high pressure in the stabilizer overhead caused by a plant
upset while taking off-line for the TAPs planned shutdown. The event stopped when the stabilizer vent to flare closed.
A flaring event occurred at CGF starting at 06/29/2016 01:22 and stopping at 06/29/2016 12:29 with a volume of 42026
(MSCF). The event lasted for 667 minutes and was due to starting the plant up after the TAPS outage. The event stopped
when CGF started the off-line T/C and stabilized the facility process and operation.
Thanks,
Jennifer Blake
EOC Production Optimization Team Lead
Office (907) 564-5926
Cell (907) 830-6204
Jennifer.blake@bp.com
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000008
2. Facility Name
PBU CGF B
3. Field
PBU - EOA
4. Operator
BP
5. MonthNear of Disposition
I July -2016
Disposition
Volume MCF
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
6. sold
1,185,149
Pool Name Pool Code Percent
7. Reinjected
4,002,711
PRUDHOE 640150 100.00%
8. Flared or vented 1 hour or less
0
9. Flared or vented more than 1 hour (see instr.)
0
10. Pilot and Purge
24,063
11. Assist Gas
50,604
12. Fuel gas used in lease operations.
2,518,852
13. Other (see instructions)
0
Official Use Only
Authorization >t hr:
Safety
MCF
14. TOTAL VOLUME (ITEMS 6-12)
7,761,379
Lease Use
MCF
15. NGL Gas Equivalent
1,185,149
Conservation
MCF
16. Purchased gas
0
Waste:
MCF
17. Transferred from: FST, FS2, FS3, GC1, GC2 & GC3
193,574,712
18. Transferred to: (Express as a negative #) FSI, FS2, FS3, CCP & GPMA
-185,793,332
Commissioner Date
19. Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 1,585,276 mscf
I hereby certify that the foregoing is true and correct to the best of my knowledge.
�` Note: All volumes must be corrected
%J
Signature a `� Q&4 Title Mana er Production Taxes and Ro alties Alaska to pressure of 14.65 psis and to a
(. temperature of 60o F. Authority 20
Printed Name Diane ColleyPhone (907) 564-5775 Date s / I� AAC25.235.
Form 10-422 Rev. 512009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - CENTRAL GAS FACILITY
GAS FLARING INCIDENT REPORT
July 2016
YihAli
Not required for unplanned events <= 1 hr Not required for unplanned events <= 1 hr
TOTAL 0
Unplanned events ereaterthan i hour
See attachments See attachments
TOTAL 0
Planned events less than or equal to 1 hour
See attachments See attachments
TOTAL 0
Planned events ereater than 1 hour
TOTAL
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events > 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
VOLUME DESCRIPTION OF IN
See attachments
0
TOTAL
0
0
0
0
24,063
50,604
74,667
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
Page 2
8/11/2016
9'.46 AM
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000008
2. Facility Name
PBU CGF B
3. Field
PBU - EOA
4. Operator
BP
5. Month ear of Disposition
August -2016
Disposition
volume MCF
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
6. Sold
1,186,706
Pool Name Pool Code Percent
7. Reinjected
4,052,825
PRUDHOE 640150 100.00%
8. Flared or vented 1 hour or less
0
9. Flared or vented more than 1 hour (see insV.)
1,467
10. Pilot and Purge
23,974
11. Assist Gas
51,666
12. Fuel gas used in lease operations.
2,521,205
13. Other (see instructions)
0
Official Use Only
Authorization hr.
Safety
MCF VTL
l0 t0
14. TOTAL VOLUME (ITEMS 6-12)
7,837,843
Lease Use
MCF
15. NGL Gas Equivalent
1,186,706
Conservation
MCF
16. Purchased gas
Waste:
MCF
17. Transferred from: FS1, FS2, FS3, GC1, GC2 & GC3
204,737,892
>� /0, 12
Commissioner Date
18. Transferred to: (Express as a negative #) FS1, FS2, FS3, CCP & GPMA
-196,900,048
19. Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 943,464 mscf
I hereby certify that the foregoing is true and correct to the best of my knowledge.
Q/ Maq, All volumes must be corrected
Signature 11 =�L Title Manager Production Taxes and Ro alties Alaska t0 pressure Of 14.65 psia and t0 a
temperature of 60o F. Authority 20
Printed Name Diane Colley Phone (907) 564-5775 Date AAC25.235.
[G
Form 10-422 Rev. 5/2009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT- CENTRAL GAS FACILITY
GAS FLARING INCIDENT REPORT
August 2016
Unplanned events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events <= 1 hr Not required for unplanned events <= 1 hr
TOTAL
CAUSE
See attachments See attachments
TOTAL 0
Planned events less than or equal to 1 hour
DESCRIPTION OF INCIDENT & CAUSE
See attachments
See attachments
L911MA
TOTAL
0
Planned events greater than 1 hour
DATE TIME
VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
8/19-23/16 1300-2400
1,467 See attachments See attachments
TOTAL
1,467
TOTAL
Unplanned Events < 1 Hour
0
Unplanned Events> 1 Hour
0
Planned Events < 1 hour and not
0
exceeding 5,000 MCF
Planned Events > 1 hour or
1,467
exceeding 5,000 MCF
Pilot Purge
23,974
Assist
51,666
TOTAL FLARED VOLUME
77,107
Page 2
9/12/2016
9:44 AM
Flare Start Date 08/01/2016
Flare End Date 08/31/2016
CGF Flare Report Total Volume (MSCF) 1467
Report
Numbs System Date Start Time Stop Time
Duration Intermittent Black Smoke
Planned Reported By
Volume
16-261 Flare Relief 08/19/2016 1:00:00 pm 12:00:00 am
660 min No No
Yes BP1\CRAMBL
183
Determination Cause PT Mao Ml Line depressured for maintenance.
Action Taken ongoing
Daily Volume (MSCF)
183
16-262 Flare Relief 08/20/2016 12:00:00 am 12:00:00 am
1440 min No No
Yes BPI\CRAMBL
367
Determination Cause PT Mac MI Line depressured for maintenance.
Action Taken ongoing
Daily Volume (MSCF)
367
16-263 Flare Relief 08/21/2016 12:00:00 am 12:00:00 am
1440 min No No
Yes BP1\CRAMBL
367
Determination Cause PT Mac MI Line depressured for maintenance.
Action Taken ongoing
Daily Volume (MSCF)
367
16-264 Flare Relief 08/22/2016 12:00:00 am 12:00:00 am
1440 min No No
Yes BP1\CRAMBL
367
Determination Cause PT Mac MI Line depressured for maintenance.
Action Taken ongoing
Daily Volume (MSCF)
367
16-265 Flare Relief 08/23/2016 12:00:00 am 12:00:00 am
1440 min No No
Yes BP1\DENNSO
183
Determination Cause PT mac line depressured for maintenance
Action Taken Line is depressured
Daily Volume (MSCF)
183
Total Volume (MSCF) 1467
Generated 09/01/2016 3:47:14PM Page 2 of 9
Link, Liz M (DOA)
From: AKOpsProdEOCTL <AKOPSPCCEOCTL@bp.com>
Sent: Monday, August 29, 2016 12:01 PM
To: AOGCC Reporting (DOA sponsored)
Cc: Loepp, Victoria T (DOA); Benson, Gary A; Arthur, Gregory; AK, OPS CCP CGF OSM;
Hanus, John M.; AK, HSSEE Env Adv Central; Glover, Robin; AK, OPS CGF OTL; Buckbee,
Rachel A
Subject: Flaring events at CGF
To: AOGCC Reporting CC: Victoria Leopp, AOGCC
Aogcc.reporting(a,)alaska.gov victoria.loepp(a)alaska.gov
From: Jennifer Blake, GPB Production Optimization Team Leader
A flaring event occurred at CGF starting at 08/19/2016 13:00 and continuing to 08/20/2016 00:00 with a volume of 183
(MSCF). The event lasted for 660 minutes and was due to depressurizing the MI line between CGF and GPMA for
planned maintenance. The event continued into 8/20/2016.
A flaring event occurred at CGF starting at 08/20/2016 00:00 and continuing to 08/21/2016 with a volume of 367 (MSCF).
The event lasted for 1440 minutes and was due to depressurizing the MI line between CGF and GPMA for planned
maintenance. The event continued into 8/21/2016.
Aflaring event occurred at CGF starting at 08/21/2016 00:00 and continuing to 08/22/2016 with a volume of 367 (MSCF).
The event lasted for 1440 minutes and was due to depressurizing the MI line between CGF and GPMA for planned
maintenance. The event continued into 8/22/2016.
A flaring event occurred at CGF starting at 08/22/2016 00:00 and continuing to 08/23/2016 with a volume of 367 (MSCF).
The event lasted for 1440 minutes and was due to depressurizing the MI line between CGF and GPMA for planned
maintenance. The event continued into 8/23/2016.
A flaring event occurred at CGF starting at 08/23/2016 00:00 and stopping at 08/24/2016 with a volume of 183 (MSCF).
The event lasted for 1440 minutes and and was due to depressurizing the MI line between CGF and GPMA for planned
maintenance. The event stopped when depressurization was complete.
Thanks,
Jennifer Blake
EOC Production Optimization Team Lead
Office (907) 564-5926
Cell (907) 830-6204
Jennifer.blake@bp.com
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000008
2. Facility Name
PBU CGF B
3. Field
PBU - EOA
4. Operator
BP
5. Month/Vear of Disposition
September -2016
Disposition
Volume MCF
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
6. Sold
1,259,872
Pool Name PoolCode Percent
7. Reinjected
5,142,526
PRUDHOE 640150 100.00%
8. Flared or vented 1 hour or less
0
9. Flared or vented more than 1 hour (see instr.)
0
10. Pilot and Purge
23,160
11, Assist Gas
48,782
12. Fuel gas used in lease operations.
2,600,068
13. Other (see instructions)
0
Official Use Only
Authorization >1 he
Safety
MCF
14. TOTAL VOLUME (ITEMS 6-12)
9,074,408
Lease Use
MCF
15. NGL Gas Equivalent
1,259,872
Conservation
MCF
16. Purchased gas
0
Waste:
MCF
17. Transferred from: FS1, FS2, FS3, GC1, GC2 & GC3
201,260,529
Commissioner Dale
18. Transferred to: (Express as a negative #) FS1, FS2, FS3, CCP & GPMA
-192,186,117
19. Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 275,715 mscf
I hereby certify the he foregoing is true and correct to the best of my knowledge
tV61 I Note: All volumes must be corrected
Signature . Title Mana er Production Taxes and Ro alties Alaska to pressure of 14.65 psis and to a
temperature of 60o F. Authority 20
Printed Name Diane Colley Phone (907) 564-5775 Date / l L AAC25.235.
Form 10-422 Rev. 5/2009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT- CENTRAL GAS FACILITY
GAS FLARING INCIDENT REPORT
September 2016
events less than or equal to 1
I Wit VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events <= 1 hr Not required for unplanned events <= 1 hr
TOTAL 0
Unplanned events greater than 1 hour
nv�t vULUMt DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
See attachments See attachments
TOTAL 0
Planned events less than or equal to i hour
TOTAL
TOTAL
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
See attachments
i
See attachments
0
TOTAL
0
0
0
0
23,160
48,782
71,942
See attachments
See attachments
Page 2
10/14/2016
1:31 PM
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000008
2. Facility Name
PBU CGF B
3. Field
PBU - EOA
4. Operator
BP
5. Month/Year of Disposition
1 October -2016
Disposition
Volume MCF
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
6. Sold
1,428,845
Pool Name Pool Code Percent
7. Reinjected
5,729,481
PRUDHOE 640150 100.00%
8. Flared or vented 1 hour or less
1,727
9. Flared or vented more than 1 hour (see instr.)
13,566
10. Pilot and Purge
24,667
11. Assist Gas
54,009
12. Fuel gas used in lease operations.
2,845,846
13. Other (see instructions)
O
Use Only
AuthorizationOfficial
>1 hr:
Safety
.J
MCF
14. TOTAL VOLUME (ITEMS 6.12)
10,098,141
Lease Use
MCF
15. NGL Gas Equivalent
1,428,845
Conservation
MCF
16. Purchased gas
0
Waste:
MCF
17. Transferred from: FSI, FS2, FS3, GC1, GC2 & GC3
214,344,821
n
^� 21-14-17 — / 4 —1
Commissioner ( Date
18. Transferred to: (Express as a negative #) FST, FS2, FS3, CCP & GPMA
-204,246,680
19. Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 9271456 mscf
1 hereby certify that the foregoing is true and correct to the best of my knowledge.
� Note: All volumes must be corrected
Signature ���/// sss��� lll�wx'vriL Title Manager Production Taxes an Ro alties Alaska to pressure of 14.65 psia and to a
Oki
temperature of 60o F. Authority 20
Printed Name Diane ColleyPhone (907) 564-5775 Date AAC25.235.
Form 10-422 Rev. 5/2009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - CENTRAL GAS FACILITY
GAS FLARING INCIDENT REPORT
October 2016
uA1 c
11ME
VOLUME DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
10/16/2016
0541-0602
387 Not required for unplanned events <= 1 hr
Not required for unplanned events <= 1 hr
1930-2002
TOTAL
387
0541-0602
510
TOTAL
Unplanned events greater than 1 hour
DATE
TIME
VOLUME DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
10/15/2016
2230-2359
72 See attachments
See attachments
10/15/2016
2230-2359
12,664
TOTAL
12,736
Llannecl events less than or equal to 1 hour
DATE
TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
10/8/2016
0030-0100
400 See attachments See attachments
10/10/2016
1930-2002
430
10/16/2016
0541-0602
510
TOTAL
1,340
10/6/2016
10/11/2016
0030-0323
2044-2400
TOTAL
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events > 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
430 See attachments
400
830
TOTAL
387
12,736
1,340
830
24,667
54,009
93,969
See attachments
Page 1
11/18/2016
11:10 AM
Flare Start Date 10/01/2016
Flare End Date 10/31/2016
Total Volume (MSCF) 15293
Generated 11/02/2016 4:05:39PM Page 5 of 12
CGF Flare Report
Total Volume (MSCF)
15293
Report
Numbs System
Date StartTime Stop Time Duration Intermittent
Black Smoke
Planned Reported By
Volume
16-342 Flare Relief 10/06/2016 12:30:00 am 3:23:00 am 173 min Yes
No
Yes BP1\CLUBBBW
430
Determination Cause
Tandem 3 taken down for fuel valve work and Waterwash
Action Taken
T/C 1885 depressured
Daily Volume (MSCF)
430
16-350 Controlled Blowdown 10/08/2016 12:30:00 am 1:00:00 am 30 min No
No
Yes BP1\BUCHR8
400
Determination Cause
T\C 1886 shutdown for planned maintenance "Type A" S/D
Action Taken
1886 T/C depressurization completed.
Daily Volume (MSCF)
400
16-349 Controlled slowdown 10/10/2016 7:30:00 pm 8:02:00 pm 32 min No
No
Yes BP1\CLUBBBW
430
Determination Cause
T\C 1883 depmssured for water wash
Action Taken
1883 T/C depressudution completed.
Daily Volume (MSCF)
430
16-355 Controlled Blowtlown 10/11/2016 8:44:00 pm 12:00:00 am 196 min No
No
Yes BP1\CLUBBBW
400
Determination Cause
T\C 1884 depressured for water wash
Action Taken
1884 T/C depressurization completed.
Daily Volume (MSCF)
400
16-365 Controlled Blowdown 10/16/2016 10:30:00 pm 11:59:00 pm 89 min No
No
No BP1\DENNSO
72
Determination Cause
T\C 1855 shutdown due to controNnstmmen ation failure associated with 1855 (coolstop volume
72ni
Action Taken
1855 TIC 000lstop not a complete blowdown.
16-365 Controlled Blowdown 10/15/2016 10:30:00 pm 11:59:00 pm 89 min No
No
No BP1\CRAMBL
12664
Determination Cause
T/C 1855 s/d (meter 660 stab overheads)
Action Taken
Flare valve closed.
Daily Volume (MSCF)
12736
16-378 Controlled slowdown 10/20/2016 24000 am 3:00:00 am 20 min No
No
Yes BP1\GONDEO
510
Determination Cause
T/C 1801 and 1802 S/D for planned maintenance and water wash.
Action Taken
1801 and 1802 T/C depressurized and shut down.
Daily Volume (MSCF)
510
Total Volume (MSCF) 15293
Generated 11/02/2016 4:05:39PM Page 5 of 12
Link, Liz M (DOA)
From: AKOpsProcIEOCTL <AKOPSPCCEOCTL@bp.com>
Sent: Tuesday, October 11, 2016 11:06 AM
To: AOGCC Reporting (DOA sponsored)
Cc: Loepp, Victoria T (DOA); Benson, Gary A; Arthur, Gregory; AK, OPS CCP CGF OSM;
Hanus, John M.; AK, HSSEE Env Adv Central; Glover, Robin; AK, OPS CGF OTL; Buckbee,
Rachel A; Schinagl, Werner
Subject: Flaring events at CGF
To: AOGCC Reporting CC: Victoria Leopp, AOGCC
Aoacc.reportingAalaska.aov victoria.loepp(&alaska.gov
From: Jennifer Blake, GPB Production Optimization Team Leader
A flaring event occurred at CGF starting at 10/06/2016 00:30 and stopping at 10/06/2016 03:23 with a volume of 430
(MSCF). The event lasted for 173 minutes and was due shutting down tandem 3 for planned fuel valve work and water
wash. The events stopped when Tandem 3 depressurization was completed.
Thanks,
Jennifer Blake
EOC Production Optimization Team Lead
Office (907) 564-5926
Cell (907) 830-6204
Jennifer.blake(c@bp.com
Link, Liz M (DOA)
From: AKOpsProdEOCTL <AKOPSPCCEOCTL@bp.com>
Sent: Wednesday, November 09, 2016 4:15 PM
To: AOGCC Reporting (DOA sponsored)
Cc: Loepp, Victoria T (DOA); Benson, Gary A; Arthur, Gregory; AK, OPS CCP CGF OSM;
Hanus, John M.; AK, HSSEE Env Adv Central; Glover, Robin; AK, OPS CGF OTL; Buckbee,
Rachel A; Schinagl, Werner
Subject: Flaring events at CGF
To: AOGCC Reporting CC: Victoria Leopp, AOGCC
Aogcc.reportingna alaska.gov victoria.loeppna alaska.gov
From: Jennifer Blake, GPB Production Optimization Team Leader
A flaring event occurred at CGF starting at 10111/2016 20:44 and stopping at 10/12/2016 with a volume of 400 (MSCF).
The event lasted for 196 minutes and was due to depressurizing T/C 1884 for water wash. The events stopped when
depressurization was completed.
A flaring event occurred at CGF starting at 10/15/2016 22:30 and stopping at 10/15/2016 23:59 with a volume of 328
(MSCF). The event lasted for 89 minutes and was due to T/C 1855 shutdown due to control/instrumentation failure. The
events stopped when 1855 cool stop was complete.
A flaring event occurred at CGF starting at 10/15/2016 22:30 and stopping at 10/15/2016 23:59 with a volume of 12664
(MSCF). The event lasted for 89 minutes and was due to flaring off the stabilizers while T/C 1855 was shutdown. The
event stopped when the compressor was restarted and the flare valve was closed.
Thanks,
Jennifer Blake
EOC Production Optimization Team Lead
Office (907) 564-5926
Cell (907) 830-6204
Jennifer.blake@bp.com
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCFD GAR n1RpnR1T1nti
1. Facility Number
0290000008
2. Faciliry Name
PBU CGF B
3. Field
PBU - EOA
4. Operator . . •5.
BP
Month/Year of Disposition
November -2016
Disposition
Volume MCF
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
6. Sold
1,568,456
Pool Name Pool Code Percent
7. Reinjected
6,140,374
PRUDHOE 640150 100.00%
8. Flared or vented 1 hour or less
1,200
9. Flared or vented more than 1 hour (see instr.)
0
10. Pilot and Purge
24,288
11, Assist Gas
47,738
12. Fuel gas used in lease operations.
3,053,055
13. Other (see instructions)
0
Official Use Only
Authorization >1 hr:
Safety
MCF
14. TOTAL VOLUME (ITEMS 6-12)
10,835,111
Lease Use
MCF
15. NGL Gas Equivalent
1,568,456
Conservation
MCF
16. Purchased gas
0
Waste:
MCF
17. Transferred from: FSI, FS2, FS3, GC1, GC2 & GC3
234,088,853
18. Transferred to: (Express as a negative #) FS1, FS2, FS3, CCP & GPMA
-223,253,744
Commissioner Date
19. Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 905,452 mscf
hereby certify that the foregoing is true and correct to the best of my knowledge.
�fC4�� �� Note: All volumes must be corrected
Signature Title Manager Production Taxes and Ro aloes Alaska to pressure of 14.65 psia and to a
U temperature of 60o F. Authority 20
Printed Name Diane Colley Phone (907) 564-5775 DAAC25.235,
Form 10-422 Rev. 512009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT- CENTRAL GAS FACILITY
GAS FLARING INCIDENT REPORT
November 2016
LUnplanned events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
11/4/2016 1631-1641 400 Not required for unplanned events <= 1 hr Not required for unplanned events <= 1 hr
11/5/2016 1630-1635 400
11/7/2016 0922-0932 400
TOTAL 1,200
Unplanned events greater than 1 hour
DESCRIPTION OF IN
See attachments
TOTAL 0
Planned events less than or equal to 1 hour
See attachments
TOTAL 0
See attachments
TOTAL 0
ACTION TAKEN TO I
See attachments
See attachments
See attachments
Page 3
12/15/2016
12.31 PM
TOTAL
Unplanned Events < 1 Hour
1,200
Unplanned Events> 1 Hour
0
Planned Events < 1 hour and not
0
exceeding 5,000 MCF
Planned Events > 1 hour or
0
exceeding 5,000 MCF
Pilot Purge
24,288
Assist
47,738
TOTAL FLARED VOLUME
73,226
ACTION TAKEN TO I
See attachments
See attachments
See attachments
Page 3
12/15/2016
12.31 PM
Flare Start Date 11/01/2016
Flare End Date 11130/2016
CCP Flare Report Total Volume (MSCF) 3101
Report
Numbe System Date Start Time Stop Time
Duration Intermittent
Black Smoke Planned Reported By
Volume
16-390 Controlled Blowdown 11/01/2016 9:08:00 am 9:13:00 am
5 min No
No Yes BPMASSIETS
408
Determination Cause T/C 1878 de -pressured for air piping repair
Action Taken TIC 1878 de -pressurization complete
16-390 Controlled Blowdown 11/01/2016 11:58:00 am 12:03:00 pm
5 min No
No Yes BPIU ASSIETS
109
Determination Cause TIC 1878 de -pressured from spin cooling
Action Taken TIC 1878 de -pressurization complete
Daily Volume (MSCF)
517
16-402 Controlled Blowdown 11/05/2016 4:15:00am 4:30:00 am
15 min No
No Yes BP1\GAMBHO
987
Determination Cause Flared through P37 to crosslight pilots.
Action Taken Closed P37.
Daily Volume (MSCF)
987
16-405 Controlled Blowdown 11/06/2016 1:18:00 am 1:33:00 am
15 min No
No Yes BP1\GAMBHO
681
Determination Cause Opened P37 to cross light Flare pilots.
Action Taken Closed P37.
16-405 Controlled Blowdovrn 11/06/2016 2:00:00 pm 2:05:00 pm
5 min No
No Yes BP7\TOWNER
141
Determination Cause 1803 TIC shutdown and depressured to zero PSI for valve repair.
Action Taken 1803 T/C stopped depressuring at zero PSI.
Dairy Volume (MSCF)
822
16414 Flare Relief 11/12/2016 10:25:00 pm 10:30:00 pm 5 min No No Yes BP1\BRAUJW 200
Determination Cause Depressured FFGU Inlet Cap Gas Separators from 1500 psi to 1000 psi for planned maintenance.
Action Taken Depressurization complete
16-414 Flare Relief 11/12/2016 10:30:00 pm 10:40:00 pm 10 min No No Yes BPt\BAKERWF 106
Determination Cause FFGU Flash drum depressured for planned maintenance
Action Taken Valve closed, depressurization completed.
Daily Volume (MSCF) 306
16-415 Flare Relief 11/13/2016 3:25:00 am 3:35:00 am 10 min No No Yes BP1\BAKERWF 27
Determination Cause FFGU Flash drum depressured to"0" psi for planned maintenance
Action Taken Closed Flare valve, depressurization comoleted.
16439 Flare Relief 11/25/2016 12:20:00 am 12:25:00 am 5 min No No
Determination Cause TIC 1803 shut down for maintenance
Action Taken T/C 1803 de -pressurization complete
Generated 12/15/2016 2:11:57PM
Daily Volume (MSCF) 27
Yes BPI\MASSIETS 141
Page 1 of 12
Flare Start Date 11/01/2016
Flare End Date 11/30/2016
Daily Volume (MSCF) 141
Total Volume (MSCF) 3101
Generated 12/15/2016 2:11:57PM Page 2 of 12
Link, Liz M (DOA)
From: AKOpsProdEOCTL <AKOPSPCCEOCTL@bp.com>
Sent: Tuesday, November 29, 2016 1:34 PM
To: 'aogcc.reporting@alaska.gov'
Cc: Loepp, Victoria T (DOA); Benson, Gary A; Arthur, Gregory; Schinagl, Werner; Fortenberry,
Christopher; AK, HSSEE Env Adv East; AK, OPS GPMA Facility OTL; Glover, Robin;
Buckbee, Rachel A; AK, OPS GPMA OSM; Bessler, Mark
Subject: Flaring Event at LPC
To: AOGCC Reporting CC: Victoria Loepp, AOGCC
aoqcc. reporting (ala laska. gov
From: Jennifer Blake, GPB Production Optimization Team Leader
A flaring event occurred at LPC starting at 11/21/2016 16:02 and stopping at 11/21/2016 16:59 with a volume of 5167
(MSCF). The event lasted for 57 minutes and was due to compressor 1807 shutting down because of
control/instrumentation failure. The event stopped when field production was cut and the compressor was restarted.
Thanks,
Jennifer Blake
EOC Production Optimization Team Lead
Office (907) 564-5926
Cell (907) 830-6204
lennifer.blake@bp.com
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000008
2. Facility Name
PBU CGF B
3. Field
PBU - EOA
4. Operator
BP
5. M mthNear of Disposition
December -2016
Disposition
Volume MCF
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume .
6. Sold
1,645,424
Pool Name Pool Code Percent
7. Reinjected
6,892,004
PRUDHOE 640150 100.00%
8. Flared or vented l hour or less
21,864
9. Flared or vented more than 1 hour (see instr.)
126,101
10. Pilot and Purge
25,461
11. Assist Gas
49,945
12. Fuel gas used in lease operations.
3,110,658
13. Other (see instructions)
0
Official Use Only
Authorization >1 hr:
Safety
12 j b
MCF
14. TOTAL VOLUME (ITEMS fi-12)
11,871,457
Lease Use
M
15. NGL Gas Equivalent
1,645,424
Conservation
MCF
16. Purchased gas
0
Waste:
MCF
17. Transferred from: FS1, FS2, FS3, GC1, GC2 & GC3
242,450,924
3 I ,�
Commissioner Date
18. Transferred to: (Express as a negative #) FS1, FS2, FS3, CCP & GPMA
-230,579,469
19, Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 1,052,001 mscf
I hereby certify that the foregoing is true and correct to the best of my knowledge.
///��� Note: All volumes must be corrected
Signature t[.ti Title Manager Production Taxes and Rqyalties Alaska to pressure of 14.65 psia and to a
I ) temperature of 60o F. Authority 20
Printed Name Diane Colley Phone (907) 564-5775 Date 1 /` / AAC25.235.
1A
Form 10-422 Rev. 5/2009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT- CENTRAL GAS FACILITY
GAS FLARING INCIDENT REPORT
December 2016
unplanned events less than or equal to 1 hour
DATE
TIME
VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
12/4/2016
1010-1110
10,447 Not required for unplanned events <= 1 hr Not required for unplanned events <= 1 hr
12/4/2016
1010-1014
387
12/5/2016
2007-2011
387
12/8/2016
0245-0300
430
12/8/2016
2340-2355
430
12/25/2016
0030-0034
387
12/26/2016
0047-0057
387
12/26/2016
0754-0804
387
12/28/2016
0416-0503
7,717
12/28/2016
0416-0419
328
190
TOTAL
21,287
12/25/2016
a Lnwt
0030-0425 34,605 See attachments
ACTION TAKEN TO ELIMINATE CAUSE
12/26/2016
0047-0259
23,662
See attachments
12/26/2016
0754-1058
33,949
12/29/2016
0945-1230
33,885
TOTAL
126,101
Planned events less than or equal to 1 hour
DATE
TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
12/6/2016
0328-0338
387 See attachments
See attachments
12/23/2016
0033-0044
190
TOTAL
577
•�� vvwrvit UtSCRIPTION OF IN
See attachments
TOTAL 0
See attachments
Page 2
1/12/2017
2:11 PM
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - CENTRAL GAS FACILITY
GAS FLARING INCIDENT REPORT
December 2016
Page 3
1/12/2017
2:11 PM
TOTAL
Unplanned Events < 1 Hour
21,287
Unplanned Events> 1 Hour
126,101
Planned Events < 1 hour and not
577
exceeding 5,000 MCF
Planned Events > 1 hour or
0
exceeding 5,000 MCF
Pilot Purge
25,461
Assist
49,945
TOTAL FLARED VOLUME
223,371
Page 3
1/12/2017
2:11 PM
Link, Liz M (DOA)
From: AKOpsProdEOCTL <AKOPSPCCEOCTL@bp.com>
Sent: Wednesday, January 04, 2017 12:00 PM
To: AOGCC Reporting (DOA sponsored)
Cc: Loepp, Victoria T (DOA); Benson, Gary A; Arthur, Gregory; AK, OPS CCP CGF OSM;
Hanus, John M.; AK, HSSEE Env Adv Central; Glover, Robin; AK, OPS CGF OTL; Buckbee,
Rachel A; Schinagl, Werner
Subject: Flaring events at CGF
To: AOGCC Reporting CC: Victoria Leopp, AOGCC
Aogcc.reoorting(a)alaskagov victoria.loepp(a)alaska.gov
From: Jennifer Blake, GPB Production Optimization Team Leader
A flaring event occurred at CGF starting at 12/04/2016 10:10 and stopping at 12/04/2016 11:10 with a volume of 10447
(MSCF), The event had a volume greater than 5000 (MSCF) and was due to a tandem compressor (T/C) 1885 shutdown
from a spurious seal oil differential pressure switch problem. The event stopped when the T/C was restarted.
A flaring event occurred at CGF starting at 12125/2016 00:30 and stopping at 12/25/2016 04:25 with a volume of 34605
(MSCF). The event lasted for 235 minutes and was due to a shutdown and subsequent blowdown of the 1805 Miscible
Injection (MI) Compressor for unplanned maintenance. The event stopped when the operations/maintenance technician
troubleshooting was completed and the MI Compressor was restarted.
A flaring event occurred at CGF starting at 12/26/2016 00:47 and stopping at 12/26/2016 02:59 with a volume of 23662
(MSCF). The event lasted for 132 minutes and was due to a tandem compressor (T/C) 1885 shutdown from a gas control
valve issue. The event stopped when the T/C was restarted.
A flaring event occurred at CGF starting at 12/26/2016 07:54 and stopping at 12/26/2016 10:58 with a volume of 33949
(MSCF). The event lasted for 184 minutes and was due to a tandem compressor (T/C) 1885 shutdown from a gas control
valve issue. The event stopped when the T/C was restarted.
A flaring event occurred at CGF starting at 12/28/2016 04:16 and stopping at 12/28/2016 05:03 with a volume of 7717
(MSCF). The event had a volume greater than 5000 (MSCF) and was due to an MI Compressor 1805 shutdown due to
controls/instrumentation failure. The event stopped when the MI compressor was restarted.
A flaring event occurred at CGF starting at 12/29/2016 09:45 and stopping at 12/29/2016 12:30 with a volume of 33885
(MSCF). The event lasted for 165 minutes and was due to a tandem compressor (T/C) 1885 shutdown from an
instrumentation problem. The event stopped when the T/C was restarted.
Thanks,
Jennifer Blake
EOC Production Optimization Team Lead
Office (907) 564-5926
Cell(907)830-6204
Jennifer.blake@bp.com
Flare Start Date 12/01/2016
Flare End Date 12/31/2016
CGF Flare Report
Total Volume (MSCF) 147965
Report
Numbs System Date StartTime Stop Time Duration Intermittent Black Smoke Planned Reported By Volume
16452 Flare Relief 12/06/2016 3:28:00 am 3:38:00 am 10 min No
Determination Cause Planned shut down for MI
Action Taken 1855 shut down complete
No Yes BPI\DENNSO 387
Daily Volume (MSCF) 387
16-472 Flare Relief 12/23/2016 12:33:00 am 12:44:00 am 11 min No No Yes BP1\CRAMBL 190
Determination Cause TC 1883 S.D. for planned maintenance, Normal stop given. meter 618
Action Taken 1883 TIC depressurization completed.
Daily Volume (MSCF) 190
16-476 Flare Relief 12/25/2016 12:30:00 am 4:25:00 am 235 min No No No BPMRAMBL 34605
Determination Cause Extended flaring event occurred while awaiting operator/maintenance evaluation of 1805 MI #1 S.D. This is forthe stabilizer overhead
volume.
Action Taken Completed troubleshooting, loaded 1855 T/C, and stabilized facility process and operation.
16-477 Flare Relief 12/26/2016 12:47:00 am 2:59:00 am 132 min No No No BP1\OKINELKJ 23662
Determination Cause T/C 1855 s/d due togas control valve issues.
Action Taken Started 1855 and loaded.
Generated 01/05/2017 1:53:26PM Page 2 of 10
Flare Start Date 1210112016
Flare End Date 12/31/2016
16-477 Flare Relief 12/26/2016 7:54:00 am 10:58:00 am 184 min No
Determination Cause T/C 1855 s/d due to gas control valve issues ?
Action Taken Started 1855 and loaded.
No No BP110KINELKJ 33949
Daily Volume (MSCF) 58385
17-9 Flare Relief 12/29/2016 9:45:00 am 12:30:00 pm 165 min No No No
Determination Cause TIC 1855 shut down due to instrumentation problem. Facility went to flare with the Stabilizer Overhead gas.
Action Taken Facility re -started T/C 1855,
BP1\BUCHR8 33885
Daily Volume (MSCF) 33885
Total Volume (MSCF) 147965
Generated 01/05/2017 1:53:26PM Page 3 of 10