BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - CENTRAL GAS FACILITY
GAS FLARING AND VENTING INCIDENT REPORT
January 2018
1/8/2018
1837-1840
387 Not required for events <= 1 hr
1/8/2018
2314-2320
328
1/22/2018
0009-0034
387
1/22/2018
0141-0153
387
exceeding 5,000 MCF
TOTAL
1,489
planned events greater than 1 hour
exceeding 5,000 MCF
DATE
TIME
VOLUME DESCRIPTION OF INCIDENT & CAUSE
1/8-9/2018
1837-0112
52,960 See attachments
1/22/2018
0009-0153
626
TOTAL
53,586
fined events less than or equal to 1 hour
DATE
TIME
VOLUME DESCRIPTION OF INCIDENT & CAUSE
1/5/2018
0610-0615
400 Not required for events <= 1 hr
1/13/2018
1710-1747
400
1/14/2018
0203-0238
430
TOTAL
1,230
1/30/2018 2217-2347
387 See attachments
TOTAL
387
TOTAL
Unplanned Events < 1 Hour
1,489
Unplanned Events> 1 Hour
53,586
Planned Events < 1 hour and not
1,230
exceeding 5,000 MCF
Planned Events > 1 hour or
387
exceeding 5,000 MCF
Pilot Purge
24,455
Assist
54,411
TOTAL FLARED VOLUME
135,558
Not required for events <= 1 hr
See attachments
ALTION TAKEN TO ELIMINATE CAUSI
Not required for events <= 1 hr
See attachments
Page 3
2/13/2018
10:42 AM
Flare Start Date 01/01/2018
Flare End Date 01/31/2018
CGF Flare Report
Total Volume (MSCF) 56692
Report
Numbe System Date Start Time Stop Time Duration Intermittent Black Smoke Planned Reported By Volume
Action Taken
18-7 Controlled Blowdown 01/08/2018 6:37:00 pm 12:00:00 am 323 min Yes No No BPI\GONDEO 47323
Determination Cause Stabilizer overhead pressure relief as a result of nC 1805 shutdown due to controNnstrumentation failure associated with 86SESD and
TIC 1855 later S/D due to control/instrumentation issue associated with P49S
Action Taken MI production was cut to lower gas production until 1855 TIC restarted.
18-26 Controlled Blowdown 01/09/2018 12:00:00 am 1:12:00 am 72 min Yes No No BP1\GONDEO 5637
Determination Cause Stabilizer overhead pressure relief as a result of T\C 1805 shutdown due to controNnstrumentation failure associated with 86SESD and
T/C 1855 later S/D due to control/instrumentation issue associated with P49S
Action Taken MI production was cut to lower gas production until 1855 T/C restarted.
18-17 Controlled Blowdown 01/22/2018 12:09:00 am 15300 am 104 min Yes No No BPI GONDEO 626
Determination Cause Stabilizer overhead pressure relief resulting from T\C 1805 shutdown due to control\instrumentation failure associated with backup PLC
Action Taken T/C 1855 was running in parallel to 1805 so the load was transferred fully to 1855 and Flaring ceased.
18-23 Controlled Blowdown 01/30/2018 10:17:00 pm 11:47:00 pm 90 min No No Yes BP7\CONNK7 387
Determination Cause 1855 shut down for planned maintenance
Action Taken flaring complete
Generated 02/02/2018 9:52:54AM Page 3 of 8
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number2.
0290000008
Facility Name
PBU CGF B
3. Field
PBU - EOA
4. Operator
BP
5. MonthNear of Disposition
I February -2018
Disposition
Volume MCF
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
6. Sold
1,509,154
Pool Name Pool Code Percent
7. Reinjected
6,313,873
PRUDHOE 640150 100.00%
8. Flared or vented 1 hour or less
525
9. Flared or vented more than 1 hour (see inslr.)
0
10. Pilot and Purge
22,026
11. Assist Gas
46,869
12. Fuel gas used in lease operations.
2,887 713
13. Other (see instructions)
0
Official Use Only
Authorization>1 hr:
Safety
MCF
14. TOTAL VOLUME (ITEMS 6.12)
10,780,160
Lease Use
MCF
15. NGL Gas Equivalent
1,509,154
Conservation
MCF
16. Purchased gas
0MCF
Waste:
17. Transferred from: FS1, FS2, FS3, GC1, GC2 & GC3
213,627,275
18. Transferred to: (Express as a negative # FSI, FS2, FS3, CCP & GPMA
( p 9 )
-202,847,114
Commissioner Date
19. Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 1,826,466 mscf
I hereby certify that the foregoing is true and correct to the best of my knowledge.
Note: All volumes must be corrected
Signature Title Manager Production Taxes and Royalties Alaska to pressure of 14.65 psis and to a
Printed Name Diane Colley Phone (907) 564-5775 Date temperature of 60o F. Authority 20
AAC25 235,
Form 10422 Rev. 5/2009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - CENTRAL GAS FACILITY
GAS FLARING AND VENTING INCIDENT REPORT
February 2018
- - --- ---- ALI 1UN IAKIN TO ELIMINATE CAUSE
2/25/2018 0606-0650 525 Not required for events <= 1 hr Not required for events <= 1 hr
TOTAL 525
Unplanned events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
See attachments See attachments
TOTAL 0
Planned events less than or equal to 1 hour
Not required for events <=1 hr
TOTAL 0
UtSCRIPTION OF IN
See attachments
TOTAL 0
Not required for events <= 1 hr
See attachments
Page 2
3/12/2018
10:49 AM
TOTAL
Unplanned Events < 1 Hour
525
Unplanned Events> 1 Hour
0
Planned Events < 1 hour and not
0
exceeding 5,000 MCF
Planned Events> 1 hour or
0
exceeding 5,000 MCF
Pilot Purge
22,026
Assist
46,869
TOTAL FLARED VOLUME
69,420
Not required for events <= 1 hr
See attachments
Page 2
3/12/2018
10:49 AM
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DIRPOSiTIMI
1. Facility Number
0290000008
2. Facility Name
PBU CGF B
3. Field
PBU - EOA
4. Operator •
BP
5. Monthlyear of Disposition
I March -2018
Disposition
Volume MCF
20. FOrproduchon from multiple pools, list contribution of each pool as a percent of
Total Volume.
6. Sold
1,707,963
Pool Name Pool Code Percent
7. Reinjected
7,365,675
PRUDHOE 640150 100.00%
8. Flared or vented 1 hour or less
787
9. Flared or vented more than 1 hour (see instr.)
0
10. Pilot and Purge
24,544
11. Assist Gas
51,092
12. Fuel gas used in lease operations.
3,291,269
13. Other (see instructions)
p
Official Use OnlyAuthorization
>1 hr:
Safety
MCF
14. TOTAL VOLUME (ITEMS 6.12)
12,441,330
Lease Use
MCF
15. NGL Gas Equivalent
1,707,963
Conservation
MCF
16. Purchased gas
0
Waste:
MCF
17. Transferred from: FS1, FS2, FS3, GCT, GC2 & GC3
237,317,654
Commissioner Date
18. Transferred to: (Express as a negative #) FS1, FS2, FS3, CCP & GPMA
-224,876,323
19. Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 2,340,602 mscf
I hereby certify that the foregoing is true and correct to the best of my knowledge.
//�g/�[/�p Note: All volumes must be corrected
Signature S/lt,V! tXC(!.t,� TiOe Manacer Production Taxes and Royalties Alaska to pressure Of 14.65 psis and to a
/ �j temperature of 60o F. Authority 20
Printed Name Diane ColleyPhone (907) 564-5775 Dale b
Form 10-422 Rev. 512009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT- CENTRAL GAS FACILITY
GAS FLARING AND VENTING INCIDENT REPORT
March 2018
DATE TIME VOLUME
DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
3/17/2018 0622-0642
400 Not required for events <= 1 hr
Not required for events <= 1 hr
TOTAL
400
Unplanned events greater than 1 hour
DATE TIME VOLUME
DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
See attachments
TOTAL
0
Planned events less than or equal to 1 hour
DATE TIME VOLUME
DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
3/14/2018 1223-1300
387 Not required for events <= 1 hr
Not required for events <= 1 hr
TOTAL
387
TOTAL
Unplanned Events < 1 Hour
Unplanned Events > 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
VOLUME DESCRIPTION OF INCIDENT &
See attachments
0
TOTAL
400
0
387
0
24,544
51,092
76,423
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
Page 3
4/10/2018
3:25 PM
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000008
2. Facility Name
PBU CGF B
3. Field
PBU - EOA
4. Operator
BP
5. MonthNear of Disposition
Aril -2018
Disposition
Volume MCF
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
s. sold
1,595,166
Pool Name Pool Code Percent
7. Reinjected
7,509,309
PRUDHOE 640150 100.00%
8. Flared or vented 1 hour or less
1,758
9. Flared or vented more than 1 hour (see instr.)
0
10. Pilot and Purge
23,564
11. Assist Gas
54,170
12. Fuel gas used in lease operations.
3,151,895
13. Other (see instructions)
U
Official Use Only
Authorization >t hr
Safety
MCF
14. TOTAL VOLUME (ITEMS 6.12)
12,335,862
Lease Use
MCF
15. NGL Gas Equivalent
1,595,166
Conservation
MCF
16. Purchased gas
UMCF
Waste:
17. Transferred from: FS1, FS2, FS3, GCI, GC2 8 GC3
225,327,238
Commissioner Date
18. Transferred to: (Express as a negative #) FSI, FS2, FS3, CCP 8 GPMA
-212,991,377
19. Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 1,716,252 mscf
I hereby certify that the the f�g is true and correct to the best of my knowledge.
Note: All volumes must be corrected
Signature Title Manager Production Taxes and Royalties Alaska t0 pressure of 14.65 psis and to a
/ temperature of 60o F. Authority 20
Printed Name Diane ColleyPhone (907) 564-5775 Date o
Form 10-422 Rev. 512009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - CENTRAL GAS FACILITY
GAS FLARING AND VENTING INCIDENT REPORT
April 2018
Unplanned events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
4/9/2018 2214-2234 387 Not required for events <= 1 hr Not required for events <= 1 hr
4/9/2018 2215-2228 594
4/10/2018 0038-0058 387
TOTAL 1,368
Unplanned events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
See attachments See attachments
TOTAL 0
Planned events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
4/11/2018 0112-0132 19S Not required for events <= 1 hr Not required for events <= 1 hr
4/11/2018 0112-0132 195
TOTAL 390
I Imt VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO I
See attachments See attachments
TOTAL 0
Page 4
5/9/2018
4:35 PM
TOTAL
Unplanned Events < 1 Hour
1,368
Unplanned Events> 1 Hour
0
Planned Events < 1 hour and not
390
exceeding 5,000 MCF
Planned Events> 1 hour or
0
exceeding 5,000 MCF
Pilot Purge
23,564
Assist
54,170
TOTAL FLARED VOLUME
79,492
Page 4
5/9/2018
4:35 PM
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000008
2. Facility Name
PBU CGF B
3. Field
PBU - EOA
4. Operator
BP
5. MonthNear of Disposition
I May -2018
Disposition
Volume MCF
20. Forproduction from multiple pools, list contribution of each pool as a percent of
Total Volume.
6. Sold
1,568,180
Pool Name Pool Code Percent
7. Reinjected
5,677,667
PRUDHOE 640150 100.00%
8. Flared or vented 1 hour or less
2,170
9. Flared or vented more than 1 hour (see instr.)
78,258
10. Pilot and Purge
24,072
11. Assist Gas
67,127
12. Fuel gas used in lease operations.
2,968,427
13. Other (see instructions)
0
Official Use Onty
Authorization >7 hr.
S
7 (i /y
7 4
MCF
14. TOTAL VOLUME (ITEMS 6-12)
10,385,901
Lease Use
MCF
15. NGL Gas Equivalent
1,568,180
Conservation
MCF
16. Purchased gas
0
Waste:
MCF
17. Transferred from: FS1, FS2, FS3, GC1, GC2 & GC3
224,147,664
P z /
18. Transferred to: (Express as a negative #) FSI, FS2, FS3, CCP & GPMA
-213,761,763
Commissioner Date
19. Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 1,996,784 mscf
the
I hereby certify that foregoing oregoing is true=>rrect of my k owledge.
Note: All volumes must be corrected
SignatuIQ Title Mana er Production Taxes an Ro allies Alaska to pressure Of 14.65 psia and t0 a
J I C temperature of 60o F. Authority 20
Printed Name Diane Colley Phone (907) 564-5775 Date ' 7 % g
Form 10-422 Rev. 512009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - CENTRAL GAS FACILITY
GAS FLARING AND VENTING INCIDENT REPORT Page 2
May 2018
RAIL TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSI
5/17/2018 0218-0233 328 Not required for events <= 1 hr Not required for events <= 1 hr
5/31/2018 2120-2215 22
TOTAL 350
unplanned events greater than 1 hour
TOTAL
Unplanned Events < 1 Hour
DATE
TIME
VOLUME DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
5/12/2018
2042-2400
1,318 See attachments
See attachments
5/13/2018
0835-1723
61,975
Pilot Purge
5/17/2018
0219-0403
14,965
TOTAL FLARED VOLUME
171,627
TOTAL
78,258
Planned events less than or equal to 1 hour
DATE
TIME
VOLUME DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
5/4/2018
0250-0330
400 Not required for events <= 1 hr
Not required for events <= 1 hr
5/5/2018
0014-0054
400
5/6/2018
0829-0839
190
5/6/2018
1241-1255
430
5/11/2018
0213-0223
400
TOTAL
1,820
TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO 1
See attachments See attachments
TOTAL 0
6/11/2018
3:16 PM
TOTAL
Unplanned Events < 1 Hour
350
Unplanned Events> 1 Hour
78,258
Planned Events < 1 hour and not
1,820
exceeding 5,000 MCF
Planned Events > 1 hour or
0
exceeding 5,000 MCF
Pilot Purge
24,072
Assist
67,127
TOTAL FLARED VOLUME
171,627
6/11/2018
3:16 PM
FlareStartDate 05/01/2018
Flare End Date 05/31/2018
CGF Flare Report Total Volume (MSCF) 80428
Report
Numbs System Date StartTime Stop Time Duration Intermittent Black Smoke Planned Reported By Volume
18-153 Flare Relief 05/12/2018 8:42:00 pm 12:00:00 am 198 min Yes No No BPI\VINZANRA 1318
Determination Cause An external leak of F20AV, MI line to WOA, forced us to Bare while we isolate the leak.
Action Taken Reduced MI make
18-152 Flare Relief 05/13/2018 8:35:00 am 5:23:00 pm 528 min Yes No No BP11VTNZANRA 61975
Determination Cause TIC 1805 shutdown due to controNnstrumentation failureassociated with blow case level control problems.
Action Taken Bypassed the plant, reduced MI make and Baring was permitted to continue while operations personnel attempted to restart the
18-130 Flare Relief 05/17/2018 2:19:00 am 4:03:00 am 104 min No No No BPI\BOLDJT 14965
Determination Cause Stabilizer overhead flaring in response to unintended SID of T/C 1805
Action Taken Flare valve closed
Generated 06/06/2018 3:01:31 PM Page 2 of 7
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
RECLNE
NOV 14 2018
AOGCC
1. Facility Number
0290000008
2. Facility Name
PBU CGF B
3. Field
PBU - EOA
4. Operator
BP
5. i of t /Year of Disposition
October -2018
Disposition
Volume MCF
20. Forproduction from multiple pools, list contribution of each pool as a percent of
Total Volume.
6. Sold
1,585,621
Pool Name Pool Code Percent
7. Reinjected
6,571,314
PRUDHOE 640150 100.003/.--
00.00%8.
8.Flared or vented 1 hour or less
3,876
9. Flared or vented more than 1 hour (see instr.)
0
10. Pilot and Purge
15,810
11. Assist Gas
3,889
12. Fuel gas used in lease operations.
2,933,638
13. Other (see instructions)
0
Official Use Only
Authorization>1 hr:
Safety
MCF
14. TOTAL VOLUME (ITEMS 6-12)
11,114,148
Lease Use
MCF
15. NGL Gas Equivalent
1,585,621
Conservation
MCF
16. Purchased gas
0
Waste:
MCF
17. Transferred from: FS1, FS2, FS3, GC1, GC2 & GC3
212,560,956
Commissioner Date
18. Transferred to: (Express as a negative # FS1, FS2, FS3, CCP & GPMA
( p 9 )
-201,446,809
19. Remarks: Block 6: Gas equivalent of NGLs; Block 18: Includes MI Gas to Pt. McIntyre = 1,895,589 mscf
I hereby certify thaAa foregoing is true and correct to the best of my knowledge.
d1�a Note: All volumes must be corrected
Signature Title Manager Production Taxes and Royalties Alaska to pressure Of 14.65 psia and to a
J di ry temperature of 60o F. Authority 20
Printed Name Diane Colley Phone (907) 564-5775 Date d
Form 10-422 Rev. 512009 INSTRUCTIONS ON REVERSE SIDE Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - CENTRAL GAS FACILITY
GAS FLARING AND VENTING INCIDENT REPORT
October 2018
DATE
TIME
VOLUME
DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
10/6/2018
1322-1337
190
Not required for events <= 1 hr
Not required for events <= 1 hr
10/9/2018
1102-1117
387
10/16/2018 0248-0253
10/21/2018
1246-1248
27
712
23,575
10/26/2018 0550-0615
TOTAL
604
TOTAL
3,272
Planned events greater than 1 hour
Unplanned events greater than 1 hour
VOLUME DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
DATE
TIME
VOLUME
DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
See attachments
TOTAL
0
planned events less than or equal to 1 hour
--
DATE TIME
VOLUME DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
10/2/2018 0148-0153
400 Not required for events <= 1 hr
Not required for events <= 1 hr
10/3/2018 1515-1520
400
Planned Events> 1 hour or
10/5/2018 0359-0405
400
10/16/2018 0248-0253
850
Assist
10/16/2018 1457-1503
712
23,575
10/26/2018 0550-0615
510
TOTAL
3,272
Planned events greater than 1 hour
DATE TIME
VOLUME DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
See attachments
TOTAL 0
Page 3
11/13/2018
1121 AM
TOTAL
Unplanned Events < 1 Hour
604
Unplanned Events> 1 Hour
0
Planned Events < 1 hour and not
3,272
exceeding 5,000 MCF
Planned Events> 1 hour or
0
exceeding 5,000 MCF
Pilot Purge
15,810
Assist
3,889
TOTAL FLARED VOLUME
23,575
Page 3
11/13/2018
1121 AM