Department of Commerce, Community, and Economic Development
Alaska Oil and Gas Conservation Commission
Loading...
HomeMy WebLinkAboutPBU FS 2 / BP Exploration
STATE OF ALASKA
AOGCC
GAS DISPOSITION FILES
YEAR: 2002
FACILITY: PBU FS 2
OPERATOR: BP EXPLORATION
(ALASKA) INC
Facility
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA EASTERN OPERATING AREA-PBU 01/2002
FLOW STATION 2
Disposition Volume MCF'
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 180
4. Flared or vented greater than 1 hour 0 ,/
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 19,696
6. Used for lease operations Fuel 829,023
Assist 8
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 848,907
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: CGF 403,551
11. Transferred to: CCP 21,336,631
Remarks:
I hereby ce¡¿,të1 therregOing iSr[Ue and correct to the best of my knowledge.
Signature: .. . 1.. A "'^~: 1. Title: SUPERVISOR
Form 1 0-422 (Revised 4/95)
'Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
MCF
2. Lease Use
MCF
3. Conserv. Purposes
MCF
Commissioner
Date
If)
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-2
GAS FLARING INCIDENT REPORT
JANUARY, 2002
Page 1
t
lunPlanned Events less than or equal to 1 hour
p1¥¡ra;........ '.' ························¡rfME:( ···································/V(;)L'uME:···············PE$Cftlf?'I1I(;)N/O!::iifNCJPENT/&:ß'AUSe
1/9/2002 1703-1804 77 Not required for unplanned events which
1/10/2002 1325-1327 3 are less than or equal to 1 hour
1/17/2002 1000-1002 2
1/17/2002 1006-1008 2
1/17/2002 1030-1032 1
1/21/2002 0743-0745 5
1/23/2002 1034-1037 30
1/23/2002 1040-1046 60
TOTAL
180
Iunplanned Events greater than 1 hour
DATE TfME . . VOLUME
DESCRIPTION OF INCIDENT&: CAUSE
See attachments
o
TOTAL
. ACTION TAKEN TO ELlMINATECAU$E ..'
Not required for unplanned events whil
are less than or equal to 1 hour
,
ACTION TAKEN TO ELIMINATE cAUSE
See attachments
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Met
See attachments
o
TOTAL
See attachments
Planned Events Exceeding 1 Hour OR Exceeding 5000 Met
See attachments
o
TOTAL
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour & not
exceeding 5,000 MCF
Planned Events> 1 hour and
exceeding 5,000 MCF
Pilot Purge
Assist
o
o
o
TOTAL FLARED VOLUME
See attachments
Facility
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s)
I BP EXPLORATION, ALASKA I EASTERN OPERATING AREA-PBU
FLOW STATION 2
Disposition Volume MCF'
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 728
4. Flared or vented greater than 1 hour 0
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 17,344
6. Used for lease operations Fuel 727,667
Assist 4
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 745,743
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: CGF 364,907
11. Transferred to: CCP 19,634,826
Remarks:
I hereby ceV,L3t t~ foregoiI true and correct to the best of my knowledge.
Signature: , . J . --^ '» Title: SUPERVISOR
Form 1 0-422 (Revised 4/95)
Month/Year of Disposition
I 02/2002
'Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
MCF
2. Lease Use
MCF
3. Conserv. Purposes
MCF
Commissioner
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-2
GAS FLARING INCIDENT REPORT
FEBRUARY, 2002
~Unplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
2/1/2002 1334-1401 270 Not required for unplanned events which
2/4/2002 1117-1129 120 are less than or equal to 1 hour
2/4/2002 1131-1138 70
2/4/2002 1140-1157 170
2/7/2002 0809-0815 30
2/7/2002 0831-0833 16
2/18/2002 1118-1121 10
2/18/2002 1150-1153 15
2/18/2002 1232-1233 5
2/18/2002 2238-2240 6
2/19/2002 1043-1045 4
2/19/2002 1046-1051 10
2/19/2002 1058-1059 2
TOTAL 728
Page 1
lunplanned Events greater than 1 hour
DATE TIME VOLUME
ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events whic
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
j
DESCRIPTION OF INCIDENT 8< CAUSE'
See attachments
o
TOTAL
,
~Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Met
DATE TIME VOLUM,E DESCRIPTION OF INCIDENT 8c CAUSE
See attachments
TOTAL 0
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
~Planned Events Exceeding 1 Hour OR Exceeding 5000 Met
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See attachments
TOTAL 0
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
o
o
o
18,076
~
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
Facility
FLOW STATION 2
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA EASTERN OPERATING AREA-PBU 03/2002
Disposition Volume MCF'
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 134
4. Flared or vented greater than 1 hour 0
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 19,284
6. Used for lease operations Fuel 822,488
Assist 152
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 842,058
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: CGF 402,900
11. Transferred to: CCP 20,966,498
Remarks:
I hereby ce(J that thTIoregoing li~ true and correct to the best of my knowledge.
Signature: . a . 1 j~.. ,. Title: SUPERVISOR
Form 10-422 (Revised 4/95)
'Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
MCF
2. Lease Use
MCF
3. Conserv. Purposes
MCF
Commissioner
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-2
GAS FLARING INCIDENT REPORT
MARCH, 2002
Page 1
Unplanned Events less than or equal to 1 hour
3/17/2002
3/17/2002
3/18/2002
3/20/2002
3/21/2002
1147-1203
2138-2142
0028-0035
1740-1755
1406-1414
21 Not required for unplanned events which
8 are less than or equal to 1 hour
40
50
15
TOTAL
134
I
Junplanned Events greater than 1 hour
DATE TIME 'VOLUME', DESCRIPTION OF INCIDENT & CAUSE
See attachments
TOTAL 0
~Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mct
DATE TIME VOLUME' DESCRIPTION OF INCIDENT & CAUSE '
See attachments
TOTAL 0
Not required for unplanned events whi,
are less than or equal to 1 hour
ACTIONTAIŒN TO ELIMINATE CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE , "
See attachments
I
Iplanned Events Exceeding 1 Hour OR Exceeding 5000 Met
DATE TIME' 'vOLUME 'DESCRIPTIONOFINCIDENT &: CAUSE
See attachments
TOTAL 0
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
I
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
134
o
o
o
TOTAL FLARED VOLUME
19,570
Facility
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA EASTERN OPERATING AREA-PBU 04/2002
FLOW STATION 2
Disposition Volume MCF*
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 1,045
4. Flared or vented greater than 1 hour 322
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 18,801
6. Used for lease operations Fuel 783,146
Assist 226
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 803,540
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: CGF 391,828
11. Transferred to: CCP 20,408,119
Remarks:
I hereby ce~t the f~9 is true and correct to the best of my knowledge.
Signature: Þ ""-- Title: 8UrCnVI800 ~. ~
Form 10-422 (Revisetf 4/95)
*Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
:3 z- -z.. MCF ~
2. Lease Use
MCF
3. Conserv. Purposes
MCF
~
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-2
GAS FLARING INCIDENT REPORT
April 2002
Page 1
tunPlanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
4/13/2002 0027-0034 15 Not required for unplanned events which
4/18/2002 0946-0958 120 are less than or equal to 1 hour
4/18/2002 1002-1009 70
4/18/2002 1013-1018 50
4/18/2002 1020-1220 200 Intermittent
4/23/2002 1727-1736 90
4/25/2002 1109-1133 240
4/26/2002 1805-1838 290
4/28/2002 1042-1059 170
TOTAL
1,245
IUnplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See attachments
TOTAL
o
Iplanned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mct
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See attachments
TOTAL
o
Iplanned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
4/26/2002 1315-1630 122 See attachments
'-f f l 8/,;). ao 2... .;400 I I
TOTAL ~ 3~Á..
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
o
~3~
TOTAL FLARED VOLUME
20,394
ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events whic
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
I
bp
REPORT NO: 02-0233
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS2 DATE: 18 Apr 2002
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 09:46 09:58 OHrs 12 Mins ~ 0 0 120 MSCF
2. Flare/Relief Valve 10:02 10:09 OHrs 7Mins ~ 0 0 70 MSCF
3. Flare/Relief Valve 10:13 10:18 OHrs 5Mins ~ 0 0 50 MSCF
4. F/are/Relief Valve 10:20 12:20 2Hrs OMins ~ 0 0 200 MSCF
TOTAL VOLUME 440 MSCF
First Determination of Cause:
1. Backed out by gas transit system.
2. As Above
3. Depressured B-train HP seperator to do maintenance on the level control valve, L 14V.
Action Taken to Stop Flaring:
1. Gas cuts made across the field by EOC. Cut wells 11-24, 3-24, and 11-18 at FS-2.
2. As above
3. Completed depressurization.
Tuesday, April 30, 2002
Page 1 of 1
bp
REPORT NO: 02-0260
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS2
DATE: 26 Apr 2002
SYSTEM
1. Flare/Relief Valve
TIME OF FLARING
Start Stop Duration
13:15 16:30 3 Hrs 15Mins
Black
Intermittent Smoke
Planned
o 0
~
VOLUME
122 MSCF
122 MSCF
TOTAL VOLUME
First Determination at Cause:
1. Depressured 11 D commonline to fix leaking thermowell.
Action Taken to Stop Flaring:
1. Completed depressure and performed maintenance. Calculations on file based upon start pressure
of 600psig/120f and ending 0 psig/120f.
Tuesday.ApnI30.2002
Page 1 of 1
Facility
FLOW STATION 2
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA EASTERN OPERATING AREA-PBU OS/2002
Disposition Volume MCF*
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 2,421
4. Flared or vented greater than 1 hour 378 /
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 20,288
6. Used for lease operations Fuel 701,666
Assist 440
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 725,193
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: CGF 341,045
11. Transferred to: CCP 18,881,494
Remarks:
I hereby cert~ thõ ~hX foregoing is ;rue and correct to the best of my knowledge.
Signature: . . ~ ~ "~A 1 Title: SUPERVISOR
Form 1 0-422 (Revised 4/95)
'Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
~78 MCF..::.Jl?L-
2. Lease Use
MCF
3. Conserv. Purposes
MCF
~~
Commiss~ner l
'C/1/ùr
Date
Note: All volumes must be corrected to pressure of 14.65
psia. and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT· FS-2
GAS FLARING INCIDENT REPORT
May 2002
Page 1
'unplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCFlIPTIONOFINCIDENT8cCAUSE
5/5/2002 1321-1337 160 Not required for unplanned events which
5/6/2002 1221-1308 470 are less than or equal to 1 hour
5/8/2002 1432-1446 19
5/11/2002 1758-1822 10
5/11/2002 2059-2118 10
5/11/2002 2136-2156 7
5/16/2002 0822-0827 35
5/16/2002 0846-0901 104
5/24/2002 0030-0115 420
5/24/2002 0300-0400 328
5/24/2002 1120-1133 328
5/24/2002 1300-1330 350
5/24/2002 1400-1440 170
TOTAL
2,411
~Unplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION ()F INCIDENT & CAUSE,
See attachments
TOTAL
o
~Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mct
DATE TIME VOLUME DI;SCRIPTIOtfOF INCIDENT& CAUSE ,
5/10/2002 2056-2111 10 See attachments
TOTAL
10
~Planned Events Exceeding 1 Hour OR Exceeding 5000 Mct
, DATE TIME VOLUME DESCRIPTION OF INCIDENT &, CAUSE
5/29/2002 1700-1920 378 See attachments
TOTAL
378
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
o
10
378
23,527
ACTI,ONTA.KENTO'.ELIMINATE.CA.USE
Not required for unplanned events which
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
ACTION TAKENTOELIMINATE,CAUSE '
See attachments
6/6/2002
1:00 PM
bp
REPORT NO: 02-0289
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS2
DATE: 10 May 2002
TIME OF FLARING
SYSTEM Start Stop Duration
1. Controlled Slowdow 20:56 21:11 OHrs 15Mins
Black
Intermittent Smoke
o 0
TOTAL VOLUME
~
First Determination ot Cause:
1. SLOWDOWN OF TC-1804 PRIOR TO A WATERWASH IN THE A.M.
Action Taken to Stop Flaring:
1. COMPLETED DEPRESSURING THE MACHINE ONLY
Tuesday, May 28, 2002
Planned
VOLUME
10 MSCF
10 MSCF
Page 1 of 1
bp
FACILITY: FS2
SYSTEM
1. Flare/Relief Valve
REPORT NO: 02-0338
BPXA FLARE REPORT
PRUDHOE BAY
DATE: 29 May 2002
TIME OF FLARING
Start Stop Duration
17:00 19:20 2 Hrs 20 Mins
Black
Intermittent Smoke
Planned
~ 0
~
TOTAL VOLUME
First Determination of Cause:
1. Depressure of A train gas train for vessel repair and State required recertification.
Action Taken to Stop Flaring:
1. Completed maintenance required for above.
Sunday, June 02, 2002
VOLUME
378 MSCF
378 MSCF
Page 1 of 1
FLOW STATION 2
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA EASTERN OPERATING AREA-PBU 06/2002
Facility
Disposition
Volume MCF'
'Indicate contribution of each pool to total.
1. Sold
o
Pool Name
Code
Percent
2. Reinjected
o
PRUDHOE
640150
100.00%
3. Flared or vented less than 1 hour.
1,707
o
5. Pilot and Purge
20,119
6. Used for lease operations
Fuel
Assist
664,915
17
7. Other
Lift Gas, Off Field
o
TOTAL items 1 - 7
686,758
1. Safety
MCF
8. NGL gas equivalent produced
o
2. Lease Use
MCF
9. Purchased gas
o
3. Conserv. Purposes
MCF
10. Transferred from: CGF
20,189
Commissioner
Date
11. Transferred to: CCP
18,458,613
Remarks:
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
I hereby ce
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT· FS-2
GAS FLARING INCIDENT REPORT
June 2002
Page 1
~Unplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
6/4/2002 2339-2356 150 Not required for unplanned events which
6/7/2002 2232-2235 10 are less than or equal to 1 hour
6/13/2002 1702-1719 111
6/13/2002 1722-1742 139
6/13/2002 2243-2255 83
6/14/2002 1136-1154 125
6/15/2002 1546-1559 83
6/25/2002 1311-1404 1 ,006
ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
TOTAL
1,707
~Unplanned Events greater than 1 hour
DATE TIME VOLUME
DESCRIPTION OF INCIDENT 8< CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
TOTAL
o
~Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Met
DATE TIME VOLUME DESCRIPTION OF INCIDENT 8< CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
TOTAL
o
Iplanned Events Exceeding 1 Hour OR Exceeding 5000 Met
DATE TIME VOLUME DESCRIPTION OF INCIDENT 8< CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
o
o
o
TOTAL FLARED VOLUME
7/9/2002
11:07 AM
21,843
Facility
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA EASTERN OPERATING AREA-PBU 07/2002
FLOW STATION 2
Disposition Volume MCF'
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 316
4. Flared or vented greater than 1 hour 0
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 19,837
6. Used for lease operations Fuel 733,865
Assist 12
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 754,030
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: CGF 175,251
11. Transferred to: CCP 18,489,443
Remarks:
I hereby ceo. that tltforegOing ~, true and correct to the best of my knowledge.
Signature: (} .J. .A '~11 Title: SUPERVISOR
Form 10-422 (Revised 4/95)
'Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
MCF
2. Lease Use
MCF
3. Conserv. Purposes
MCF
Commissioner
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-2
GAS FLARING INCIDENT REPORT
July 2002
Page 1
Unplanned Events less than or equal to 1 hour
7/2/2002
7/10/2002
7/11/2002
7/23/2002
7/23/2002
7/27/2002
1947-2002
1128-1131
0956-1008
2012-2015
2221-2227
0730-0800
104 Not required for unplanned events which
21 are less than or equal to 1 hour
83
13
25
70
Not required for unplanned events which
are less than or equal to 1 hour
TOTAL
316
See attachments
See attachments
TOTAL
o
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Met
See attachments
See attachments
TOTAL
o
Planned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
See attachments
See attachments
TOTAL
o
316
o
o
o
8/8/2002
2:16 PM
TOTAL FLARED VOLUME
20,165
Facility
FLOW STATION 2
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s)
BP EXPLORATION, ALASKA EASTERN OPERATING AREA-PBU
Disposition Volume MCF'
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 2,263
4. Flared or vented greater than 1 hour 0
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 19,308
6. Used for lease operations Fuel 745,494
Assist 35
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 767,100
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: CGF 335,740
11. Transferred to: CCP 20,523,841
Remarks:
I hereby certil?:5he tregOing is ~ue and correct to the best of my knowledge.
Signature: .. . ~ J ....... 'ß. Title: SUPERVISOR
Form 10-422 (Revised 4/95)
ear of Disposition
08/2002
'Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
MCF
2. Lease Use
MCF
3. Conserv. Purposes
MCF
Commissioner
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-2
GAS FLARING INCIDENT REPORT
August 2002
Page 1
~Unplanned Events less than or equal to 1 hour
."'/.];º~"!t!!;;...;. """""""';"';;:+"!tIMIË""""" , , """"':!tØ¡;;!iJ.MI;!,,;ºI;!~~j;{II1í!fIØI!J:Ø!?tl!!l~I~!!;l\tm:c~t~~~·++':,'',"
8/4/2002 0106-0412 550 Not required for unplanned events which
8/4/2002 0625-0634 90 are less than or equal to 1 hour
8/4/2002 1320-1354 70
8/4/2002 2323-2332 90
8/5/2002 2211-2224 41
8/10/2002 0550-0608 180
8/13/2002 0744-0752 80
8/18/2002 2014-2017 15
8/21/2002 1944-1953 90
8/22/2002 1155-1208 130
8/23/2002 1009-1059 330
8/25/2002 1225-1238 130
8/25/2002 1503-1551 440
8/30/2002 1526-1553 27
TOTAL 2,263
,',·ACTIi:)I\ITAKEIltT()E"'II\IItI\tATl;!þA!iJ.$E ;;" '
Not required for unplanned events which
are less than or equal to 1 hour
J
~Unplanned Events 9reater than 1 hour
DATE '," TIME , ' , , VClLUME DESCRIPTIClNOFINCI)I;NT~CAUSE,
See attachments
, "'ACTIONTAKI;N TOI;LIMINA'TE9AUSE
See attachments
"""" ,I
TOTAL
o
Iplanned Events Less Than or Equal 1 Hour AND Not Exeeedin!¡J 5000 Met
...., . DArE " ";' .';; TIME;;; "", VOLUME; ."DESCÐIPTlON OF]NCIDEtfrli Ç'A'USE. Y'; ....,,'.. ." ,; .'... ,.AÇTlONTAKEI!J);OElJMINA'!£!.,CA'ü!ilE;,..,','
See attachments See attachments
...-..,-....-......,....,""',.....,..,.."...
TOTAL
o
1~1~,~~ed~v~~~.~xcee~i~~1~~ur~~~x~ee~ing 500~ "Met, '..""', "'" ",,; "I
·',',"""·DATIi;.':TIME'" """ : ',¥ClLi.!MI;' "',º~ÇBIP'TION'QJS"'NÇI!;i!eNT';~cAUSI;"'" ·"'·,+'·';AÇIl()I!J;."I"~~eNim!I()yt;1J\IIIf\I~m!I~.~A'I;1$e·.;·'
See attachments See attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
o
o
o
21 ,606
9/11/2002
3:57 PM
Facility
FLOW STATION 2
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA EASTERN OPERATING AREA-PBU 09/2002
Disposition Volume MCF'
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 616
4. Flared or vented greater than 1 hour 2,327 V
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 18,945
6. Used for lease operations Fuel 714,075
Assist 9
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 735,972
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: CGF 349,482
11. Transferred to: CCP 18,570,872
Remarks:
I hereby cert~that th~e and correct to the best of my knowledge.
Signature: ..Q. -'-- Title: SUPERVISOR
Form 10-422 (Revised 4/95)
'Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
L( 'Jz 7 MCF (]Bte-
2. Lease Use
MCF
3. Conserv. Purposes
MCF
~~~/
( ~';Y(()J-
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-2
GAS FLARING INCIDENT REPORT
September 2002
Page 1
Unplanned Events less than or equal to 1 hour
9/7/2002
9/8/2002
9/17/2002
9/17/2002
9/20/2002
9/23/2002
9/29/2002
Not required for unplanned events which
are less than or equal to 1 hour
1607-1613
0539-0542
1525-1547
1659-1725
0117-0129
0401-0412
0925-0942
21 Not required for unplanned events which
10 are less than or equal to 1 hour
220
260
70
11
24
TOTAL
616
Unplanned Events greater than 1 hour
9/3/2002
9/3/2002
9/4/2002
9/4/2002
0441-0757
1945-2215
0237 -0411
1530-1920
681 See attachments
521
326
799
See attachments
TOTAL
2,327
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mef
See attachments
See attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
See attachments
See attachments
TOTAL
o
2,327
o
o
10/7/2002
1 :30 PM
TOTAL FLARED VOLUME
21,897
bp
REPORT NO: 02-0606
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS2
DATE: 03 Sep 2002
SYSTEM
1. Flare/Relief Valve
2. Flare/Relief Valve
TIME OF FLARING Black
Start Stop Duration Intermittent Smoke Planned VOLUME
04:41 07:57 3Hrs 16 Mins 0 0 0 681 MSCF
19:45 22:15 2 Hrs 30 Mins 0 0 0 521 MSCF
TOTAL VOLUME 1 ,202 MSCF
First Determination of Cause:
1. Spin cool 1804 for water wash and maintenance.
2. Spin cool 1803 for water wash and maintenance
Action Taken to Stop Flaring:
1. Completed cooldown.
Volume based upon 5mmscfd = 3472 per minute x 196 mins.
2. Completed cooling.
Volume based upon 5mmscfd = 3472 x 150 mins.
Wednesday, September 25, 2002
Page 1 of 1
bp
REPORT NO: 02-0611
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS2
DATE: 04 Sep 2002
SYSTEM
1. Flare/Relief Valve
2. Flare/Relief Valve
TIME OF FLARING Black
Start Stop Duration Intermittent Smoke Planned VOLUME
02:37 04:11 1 Hrs 34Mins D D D 326 MSCF
15:30 19:20 3 Hrs 50 Mins D D D 799 MSCF
TOTAL VOLUME 1,125 MSCF
First Determination of Cause:
1. SPIN COOLING TC-1803 TO PREP FOR MAINTENANCE
2. SPIN COOLING TC-1804 TO PREP FOR MAINTENANCE
Action Taken to Stop Flaring:
1. COMPLETED COOLING PERIOD
2. COMPLETED COOLING PERIOD
Wednesday, September 25,2002
Page 1 of 1
Facility
FLOW STATION 2
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA EASTERN OPERATING AREA-PBU 10/2002
Disposition Volume MCF'
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 354
4. Flared or vented greater than 1 hour 0
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 19,658
6. Used for lease operations Fuel 778,466
Assist 5
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 798,483
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: CGF 372,601
11. Transferred to: CCP 20,413,222
Remarks:
I hereby celL that t fOr~!g is true and correct to the best of my knowledge.
Signature: .0..Jvt ~ Title: SUPERVISOR
Form 10-422 (Revised 4/95)
'Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
MCF
2. Lease Use
MCF
3. Conserv. Purposes
MCF
Commissioner
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT· FS-2
GAS FLARING INCIDENT REPORT
October 2002
Page 1
Iunplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OFINCIDENT&; CAUSE
10/1/2002 1937 -1941 8 Not required for unplanned events which
10/19/2002 0805-0809 40 are less than or equal to 1 hour
10/24/2002 1122-1206 306
, ACTION T.AKENTOELlMINATECAUSE '
Not required for unplanned events which
are less than or equal to 1 hour
~
TOTAL
354
'Unplanned Events ~reater than 1 hour
, , DATE ' TIME ' . VOLUME DESCRIPTION OF INCIDENT &;CAUSE
See attachments
" ACTION TAKEN TO ELIMINATE CAUSE
See attachments
~
TOTAL
o
~Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Met
DATE ' TIME VOLUME DESCRIPTION OF INCIDENT 8< CAUSE,
See attachments
,ACTION TAKEN TO ELfMINA Te CAUSE
See attachments
TOTAL
o
~Planned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
, , DATE TIME ' , VOLUME DESCRIPTION OF INCIDENT 8c CAUSE,
See attachments
ACTIOþ, TAKEN TO ELIMINATE CAUSE
See attachments
I
TOTAL 0
Unplanned Events < 1 Hour 354
Unplanned Events> 1 Hour 0
Planned Events < 1 hour and not 0
exceeding 5,000 MCF
Planned Events> 1 hour or 0
exceeding 5,000 MCF
Pilot Purge
Assist 1117/2002
3:16 PM
TOTAL FLARED VOLUME 20,017
FLOW STATION 2
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA EASTERN OPERATING AREA-PBU 11/2002
Facility
Disposition
Volume MCF'
'Indicate contribution of each pool to total.
1. Sold
o
Pool Name
Code
Percent
2. Reinjected
o
PRUDHOE
640150
100.00%
3. Flared or vented less than 1 hour.
1,804
4. Flared or vented greater than 1 hour
(Supplemental report required - See 20 AAC 25.235)
837
5. Pilot and Purge
18,284
6. Used for lease operations
Fuel
Assist
722,011
44
7. Other
Lift Gas, Off Field
o
TOTAL items 1 - 7
742,980
1. Safety
837 MCF OS~
8. NGL gas equivalent produced
o
2. Lease Use
MCF
9. Purchased gas
o
3. Conserv. Purposes
MCF
10. Transferred from: CGF
334,732
-/
f,t1-/ù~
Date
11. Transferred to: CCP
19,383,708
I hereby cerJilr ~t th
Signature: k·l1.
Form 10-422 (Revised 4/95)
true and correct to the best of my knowledge.
Title: SUPERVISOR
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
Remarks:
SP EXPLORATION (ALASKA) INC.
PRUDHOE SAY UNIT· FS-2
GAS FLARING INCIDENT REPORT
November 2002
Page 1
~Unplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTlONiOFINCIOENT:&:CAuSE
11/6/2002 2238-2304 181 Not required for unplanned events which
11/11/2002 0552-0606 97 are less than or equal to 1 hour
11/15/2002 0733-0742 90
11/15/2002 2234-2245 110
11/16/2002 0635-0643 80
11/16/2002 1148-1218 300
11/16/2002 1455-1548 290
11/16/2002 2234-2245 110
11/17/2002 2339-2355 160
11/18/2002 0900-0927 195
11/21/2002 2102-2118 111
11/22/2002 11 00-11 08 80
TOTAL
1,804
~Unplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
11/3/2002 1422-1600 837 See attachments
TOTAL
837
~Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Met
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See attachments
TOTAL
o
'Planned Events Exceeding 1 Hour OR Exceeding 5000 Met
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See attachments
TOTAL 0
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour 837
Planned Events < 1 hour and not 0
exceeding 5.000 MCF
Planned Events> 1 hour or 0
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME 20.969
ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
12/9/2002
11:28AM
REPORT NO: 02-0763
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS2
DATE: 03 Nov 2002
SYSTEM
1. Flare/Relief Valve
TIME OF FLARING
Start Stop Duration
14:22 16:00 1 Hrs 38 Mins
Black
Intermittent Smoke
Planned
o 0
o
VOLUME
837 MSCF
837 MSCF
TOTAL VOLUME
First Determination ot Cause:
1. LEAKING GREASE FITTING AT DS3. DEPRESSURED 3C COMMONLlNE. BASED UPON 170
PSIG AT 150 deg 1.
Action Taken to Stop Flaring:
1. shutin after finishing flaring
Tuesday, November 26, 2002
Page 1 of 1
REPORT NO: 02-0809
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS3
DATE: 15 Nov 2002
SYSTEM
1. Flare/Relief Valve
TIME OF FLARING
Start Stop Duration
04:10 04:15 OHrs 5Mins
Slack
Intermittent Smoke
Planned
o 0
~
VOLUME
3 MSCF
3 MSCF
TOTAL VOLUME
First Determination ot Cause:
1. Normal stop of 1802 T/C due to completion of hours required for a 4000 hour inspection. 1801 T/C
was already on line.
Action Taken to Stop Flaring:
1. 1802 T/C completed depressuring and is in a SIB mode.
Tuesday,November26,2002
Page 1 of 1
Facility
FLOW STATION 2
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA EASTERN OPERATING AREA-PBU 12/2002
Disposition Volume MCF'
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 0
4. Flared or vented greater than 1 hour 600 ,./
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 18,655
6. Used for lease operations Fuel 830,644
Assist 8
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 849,907
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: CGF 378,253
11. Transferred to: CCP 21,512,689
Remarks:
I hereby certiV~õ ~~ foregoing 1-< true and correct to the best of my knowledge.
Signature: " À J AN\ l' Title: SUPERVISOR
Form 10-422 (Revised 4/95)
'Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety bOO MCF ::}ßR
2. Lease Use MCF
3. Conserv. Purposes MCF
~~.* d/tO/05
Commi ioner Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-2
GAS FLARING INCIDENT REPORT
December 2002
Page 1
JUnplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT 8< CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
TOTAL
o
IUnplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT 8< CAUSE
12/12/2012 0946-1117 600 See attachments
TOTAL
600
~Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT 8< CAUSE
See attachments
TOTAL
o
Iplanned Events Exceeding 1 Hour OR Exceeding 5000 Met
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
o
600
o
o
19,263
ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
1/10/2003
3:32 PM
FACILITY: FS2
SYSTEM
1. Flare/Relief Valve
REPORT NO: 02-0867
BPXA FLARE REPORT
PRUDHOE BAY
DATE: 12 Dee 2002
TIME OF FLARING
Start Stop Duration
09:46 11 :17 1 Hrs 31 Mins
Black
Intermittent Smoke
Planned
o 0
o
TOTAL VOLUME
First Determination ot Cause:
1. 16-1801 T/C shut down due to commpressor seal oil pump failure.
Action Taken to Stop Flaring:
1. Restarted 1801 T/C. Note, delay in start up was due to fuel gas control valve problems.
Thursday, December 26, 2002
VOLUME
600 MSCF
600 MSCF
Page 1 of 1