Department of Commerce, Community, and Economic Development
Alaska Oil and Gas Conservation Commission
Loading...
HomeMy WebLinkAboutPBU GC 2 / BP Exploration
STATE OF ALASKA
AOGCC
GAS DISPOSITION FILES
YEAR: 2002
FACILITY: PBU GC 2
OPERATOR: BP EXPLORATION
(ALASKA) IN C
GATHERING CENTER 2
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
perator ield(s) Month/Year of Disposition
BP EXPLORATION, ALASKA WESTERN OPERATING AREA-PBU 01/2002
acUity
Disposition Volume MCF*
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 766
4. Flared or vented greater than 1 hour 0
(Supplemental report reauired - See 20 AAC 25.235)
5. Pilot and Purge 23,372
6. Used for lease operations Fuel 678,694
Assist 0
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 702,832
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 21,632,946
Remarks:
I hereby ce~at th~gOing is tX:::::d corQ to the best of my knowledge.
Signature: . .. n._ R.", D.Qritle: SUPERVISOR
Form 1 0-422 (Revì~ 4/95) v
*Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
MCF
2. Lease Use
MCF
3. Conserv. Purposes
MCF
Date
J';:7
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Reþort due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-2
GAS FLARING INCIDENT REPORT
JANUARY, 2002
Page 1
Iunplanned Events less than or equal to 1 hour
. DATE .... TIME · VOLUME DESCRIPTION OF INCIDENT & CAUSE
1/24/2002 1128-1221 552 Not required for unplanned events which
1/26/2002 0117-0121 33 are less than or equal to 1 hour
1/26/2002 0427 -0432 49
1/26/2002 0634-0646 83
1/26/2002 0735-0742 49
ACTION TÄKEN TOpEL.lMINATECAUSE
Not required for unplanned events which
are less than or equal to 1 hour
I
TOTAL
766
IUnplanned Events greater than 1 hour
DATE· .. TIME . VOLUME
DESCRIPTION OF INCIDENT & CAUSE .
See Attachments
o
. ACTION TAKEN TO ELlMINATISCAUSE
See Attachments
I
TOTAL
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mct
See Attachments
o
See Attachments
TOTAL
Planned Events Exceeding 1 Hour OR Exceeding 5000 Mct
See Attachments
o
See Attachments
TOTAL
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour & not
exceeding 5,000 MCF
Planned Events> 1 hour and
exceeding 5,000 MCF
Pilot Purge
Assist
766
o
o
o
TOTAL FLARED VOLUME
Facility
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA WESTERN OPERATING AREA-PBU 0212002
GATHERING CENTER 2
Disposition Volume MCF*
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 3,022
4. Flared or vented greater than 1 hour 0
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 20,723
6. Used for lease operations Fuel 619,335
Assist 0
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 643,080
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 20,726,792
Remarks:
I hereby cert()t~ðthìtregOing iSIÖ~e and correct to the best of my knowledge.
Signature: .. ..Á.......A Â Title: SUPERVISOR
Form 10-422 (Revised 4/95)
*Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
MCF
2. Lease Use
MCF
3. Conserv. Purposes
MCF
Commissioner
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-2
GAS FLARING INCIDENT REPORT
FEBRUARY, 2002
Page 1
'unplanned Events less than or equal to 1 hour
.. DATE.·.·.·· ···TIME· P VOLUME ....... DESCRIPTION OF INCIDENT & CAUSE·
2/1/2002 1335-1345 417 Not required for unplanned events which
2/4/2002 1115-1157 2,167 are less than or equal to 1 hour
2/4/2002 2113-2132 396
2/19/2002 0140-0144 42
ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
~
TOTAL
3,022
IUnplanned Events greater than 1 hour
··.DATI!: . ... . TIME . ... VOLUMEDESCRIP.TIONOFUlCIDENT ~CAUSE . ......
See Attachments
TOTAL 0
~CTIONTAKi5N T(,l1;LlMtNATE CAUSE .........
See Attachments
I
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mct
See Attachments
o
See Attachments
TOTAL
'planned Events Exceeding 1 Hour OR Exceeding 5000 Mct .....1
. ...DATE .... . .... TIME .... .... . VOLUME . Di5SCRIPTIONOFINCIDENT& CAUSE .... . ... ACTION TAKEtIrOELlMItIATE CAU~I!:
See Attachments See Attachments
TOTAL 0
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
o
o
o
23,745
Facility
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA WESTERN OPERATING AREA-PBU 03/2002
GATHERING CENTER 2
Disposition Volume MCF"
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 6,948
/
4. Flared or vented greater than 1 hour 10,694
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 24,179
6. Used for lease operations Fuel 669,517
Assist 0
7. Other Lift Gas, Off Field 0
TOTAL items 1 . 7 711,338 /
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 22,193,068
Remarks:
I herebY::~ð atæe fOregOi~ is true and correct to the best of my knowledge.
Signature: . . 1 A 1\ '"'* ' I J Title: SUPERVISOR
Form 10-422 (Revised 4/95)
"Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
1(:) &FJt.f MCF IIJGA
2. Lease Use
MCF
3. Conserv. Purposes
MCF
<l1~ /0 ð-
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-2
GAS FLARING INCIDENT REPORT
MARCH, 2002
IUnplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
0301-02 1707-1719 58 Not required for unplanned events which
3/1/2002 1729-1755 181 are less than or equal to 1 hour
3/7/2002 2118-2150 375
3/14/2002 2334-2359 5,417
3/15/2002 0206-0227 146
3/16/2002 0937-0947 49
3/16/2002 2115-2118 15
3/17/2002 0322-0331 63
3/18/2002 1206-1226 56
3/21/2002 1633-1645 42
3/21/2002 2009-2017 56
3/22/2002 1621-1625 14
3/22/2002 2058-2105 49
3/22/2002 2314-2329 260
3/24/2002 0947-0951 167
Page 1
TOTAL
6,948
lunplanned Events greater than 1 hour
DATE TIME
3/15/2002 0000-0117
VOLUME DESCRIPTION OF INCIDENT & CAUSE
10,694 See Attachments
Intermittent
10,694
TOTAL
ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
Iplanned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mct
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See Attachments
TOTAL 0
Iplanned Events Exceeding 1 Hour OR Exceeding 5000 Mct
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See Attachments
TOTAL 0
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5.000 MCF
Planned Events> 1 hour or
exceeding 5.000 MCF
Pilot Purge
Assist
TOTAL
6.948
10.694
o
o
TOTAL FLARED VOLUME
41,821
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
REPORT NO: 02-0144
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: GC2
DATE: 15 Mar 2002
SYSTEM
1. Flare/Relief Valve
2. Flare/Relief Valve
TIME OF FLARING Black
Start Stop Duration Intermittent Smoke Planned VOLUME
00:00 01:17 1 Hrs 17 Mins 0 0 0 10,694 MSCF
02:06 02:27 OHrs 21 Mins 0 0 0 146 MSCF
TOTAL VOLUME 10,840 MSCF
First Determination ot Cause:
1. lPS compressor K-7000 shut down because of control/instrumentation failure associated with the
seal oil differential pressure switch.
2. lPS compressor K-7000 shut down because of control/instrumentation failure associated with the
seal oil differential pressure switch.
Action Taken to Stop Flaring:
1. WOA reduced production rates and shut-in lP wells equaling 266mmscfd. Wells were shut-in or
choked back starting at 00:00 hours.
2. WOA reduced production rates and shut-in lP wells equaling 10 mmscfd. Wells were shut-in or
choked back starting at 02:06 hours.
Thursday, March 28, 2002
Page 1 of 1
GPB Flaring incident
Subject: GPB Flaring incident
Date: Mon, 18 Mar 200215:43:14 -0600
From: "Bolkovatz, Mike J" <BolkovMJ@BP.com>
To: "'Steve McMains (E-mail)...<steve_mcmains@admin.state.ak.us>
CC: "Fiedler, Anne M" <FiedleAM@BP.com>, "Benson, Gary A" <BensonGA@BP.com>,
"Pfeiffer, Jim A" <PfeiffJA@BP.com>,
"GPB, Environ Advisor East" <GPBEnvironAdvisorEast@BP.com>
> To:
>
>
>
> From:
>
> This note is to inform you of a flaring incident which occurred on March
> 15, 2002. At midnight, GC2 started flaring
> because LPS compressor K-7000 shutdown due to an instrumentation failure
> associated with the seal oil differential
pressure switch. 266 MM/D gas was immediately shutin to reduce the
slugcatcher pressure below its flare limit. The
flare valve did not reseat for 1 hr and 17 minutes, and a total of
10,694 MSCF was flared.
> Please don't hesitate to call me with any questions.
>
>
>
>
>
Steve McMains, AOGCC
steve mcmains@admin.state.ak.us
907-793-1241, fax 907-276-7542
Michael Bolkovatz, GPB Prod Optim Team Leader, 907-659-5566
Michael Bolkovatz
GPB Production Optimization TL
659-5566
1 of 1
3/18/02 12:47 PM
Facility
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA WESTERN OPERATING AREA-PBU 04/2002
GATHERING CENTER 2
Form 10-422 (Revised 4/95)
"Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
~ 33 MCF -...J.ßI'Z--
Disposition Volume MCF*
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 2,135 /'
4. Flared or vented greater than 1 hour 833 ./
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 22,685
6. Used for lease operations Fuel 521,777
Assist 0
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 547,430 /
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 17,419,930
Remarks:
I hereby certC!.hñ the tregOing is tr and correct to the best of my knowledge.
Signature:. .Á . A .^. h Title: SUPERVISOR
2. Lease Use
MCF
3. Conserv. Purposes
MCF
(~~. t;,L.-A/Gi'
Commissi~er 0
(P!iO 10 ;r
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-2
GAS FLARING INCIDENT REPORT
April 2002
Page 1
~Unplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT &. CAUSE
4/8/2002 1114-1122 250 Not required for unplanned events which
4/11/2002 1500-1505 69 are less than or equal to 1 hour
4/13/2002 0432-0450 625
4/13/2002 0734-0833 1,024
4/26/2002 1546-1551 56
TOTAL
2,024
~Unplanned Events greater than 1 hour
DATE TIME
4/8/2002 2136-2336
VOLUME DESCRIPTION OF INCIDENT &. CAUSE
833 See Attachments
Intermittent
833
TOTAL
~Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mct
DATE TIME VOLUME DESCRIPTION OF INCIDENT &. CAUSE
4/2/2002 1225-1442 111 See Attachments
ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
TOTAL
111
IPlanned Events Exceeding 1 Hour OR Exceeding 5000 Mct
DATE TIME VOLUME DESCRIPTION OF INCIDENT &. CAUSE
See Attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
833
111
o
TOTAL FLARED VOLUME
25,653
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
bp
FACILITY: GC2
SYSTEM
1. Flare/Relief Valve
REPORT NO: 02-0191
BPXA FLARE REPORT
PRUDHOE BAY
DATE: 02 Apr 2002
TIME OF FLARING
Start Stop Duration
12:25 14:42 0 Hrs 16Mins
Black
Intermittent Smoke
~ 0
Planned
TOTAL VOLUME
~
First Determination of Cause:
1. LPS compressor K-7000 shut down for exhaust stack repair
Action Taken to Stop Flaring:
1. All LP wells to GC-2 cut back to minimum
Tuesday,ApriI30,2002
VOLUME
111 MSCF
111 MSCF
Page 1 of 1
REPORT NO: 02-0213
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: GC2
DATE: 08 Apr 2002
SYSTEM
1. Flare/Relief Valve
2. Flare/Relief Valve
TIME OF FLARING Black
Start Stop Duration Intermittent Smoke Planned VOLUME
11:14 11:22 OHrs 8Mins D D D 250 MSCF
21:36 23:36 2Hrs OMins ~ D D 833 MSCF
TOTAL VOLUME 1,083 MSCF
First Determination of Cause:
1. High ambient temperature swings resulted in flaring and required cuts in production. Ambient
temperature increased by 7°F.
2. LPS compressor K-7001 shut down due to a problem associated with seal oil leakage.
Action Taken to Stop Flaring:
1. WOA reduced production rates and shut-in 6 wells equaling 25 mmscfd. Wells were shut-in or
choked back starting at 1115 hours.
2. WOA stopped bringing production rates up until wells unloaded and flaring was ceased.
3 intermittent incidents.
2136 to 2148
2149 to 2204
2312 to 2336 all about the same rate.
Tuesday, April 30, 2002
Page 1 of 1
Facility
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s)
BP EXPLORATION, ALASKA WESTERN OPERATING AREA-PBU
GATHERING CENTER 2
Disposition Volume MCF"
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 2,479
4. Flared or vented greater than 1 hour 0
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 22,325
6. Used for lease operations Fuel 621,002
Assist 0
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 645,806
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 19,996,337
Remarks:
I hereby certi~t~Qtheloregoing i~drue and correct to the best of my knowledge.
Signature: . ..A. .A .. A""'. 1. I Title: SUPERVISOR
Form 10-422 (Revised 4/95)
ear of Disposition
OS/2002
"Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 1 00.00%
1. Safety
MCF
2. Lease Use
MCF
3. Conserv. Purposes
MCF
Commissioner
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BA V UNIT - GC-2
GAS FLARING INCIDENT REPORT
May 2002
Page 1
Unplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
5/9/2002 0245-0306 292 Not required for unplanned events which
5/12/2002 0312-0334 139 are less than or equal to 1 hour
5/12/2002 0358-0408 69
5/16/2002 0422-0447 260
5/24/2002 1436-1441 56
5/24/2002 1519·1528 106
5/24/2002 1657·1702 52
5/24/2002 1730-1832 285 Intermittent - 41 minutes
5/29/2002 1741-1826 938
5/31/2002 0015-0102 83
5/31/2002 0705·0807 199 Intermittent· 26 minutes
TOTAL
2,479
'Unplanned Events greater than 1 hour
DATE TIME VOLUME
DESCRIPTION OF INCIDENT & CAUSE
See Attachments
Intermittent
o
TOTAL
ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
Planned Events Less Than or Equal 1 Hour AND Not Exceedln 5000 Mct
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See Attachments
TOTAL
o
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
Planned Events Exceedln 1 Hour OR Exeeedin 5000 Met
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See Attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
TOTAL
2,479
o
o
o
24,804
6/6/2002
1:03 PM
Facility
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA WESTERN OPERATING AREA-PBU 06/2002
GATHERING CENTER 2
Disposition Volume MCF"
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 1,152
4. Flared or vented greater than 1 hour 0
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 20,295
6. Used for lease operations Fuel 601,944
Assist 0
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 623,391
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 19,726,877
Remarks:
I hereby certify that Re fOregOin1iS true and correct to the best of my knowledge.
Signature: 0·0. ..Á. A A .J\.L J, Title: SUPERVISOR
Form 10-422 (RevIsed 4/95)
"Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
MCF
2. Lease Use
MCF
3. Conserv. Purposes
MCF
Commissioner
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-2
GAS FLARING INCIDENT REPORT
June 2002
Page 1
¡unplanned Events less than or equal to 1 hour
[)~II: . TIME···· . "QLUM.EPIË$¢RIP"'I()I\I()FIN¢IPf:I\I,"~¢At.J$lËi
6/1/2002 0722-0727 31 Not required for unplanned events which
6/4/2002 1056-1246 258 are less than or equal to 1 hour
6/15/2002 1 036-1126 400
6/20/2002 0339-0344 35
6/23/2002 0833-0841 78
6/24/2002 0755-0802 68
6/25/2002 0338·0404 126
6/25/2002 1527-1543 156
TOTAL
1,152
¡unPlanned Events greater than 1 hour
.·DATE TIME VOLUME
DESCRIPTION OF INCIDENT & CAUSE·
See Attachments
Intermittent
o
TOTAL
ACTIONTAI<EN TQ .ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSE· .
See Attachments
¡Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mct
. . DATE TIME VOLUME.· DESCRIPTION OF INCIDENT & CAUSE
See Attachments
TOTAL
o
Iplanned Events Exceeding 1 Hour OR Exceeding 5000 Mct
. DATE .. TIME . . VOLUME . DESCRIPTION OF INCIDENT & CAUSE
See Attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
1,152
o
o
o
21,447
ACTION TAKEN TO ELIMINATE CAUSE.
See Attachments
. . ACTION TAKEN TO ELIMINATE CAUSE .
See Attachments
7/9/2002
10:50 AM
Facility
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s)
BP EXPLORATION, ALASKA WESTERN OPERATING AREA-PBU
GATHERING CENTER 2
Disposition Volume MCF"
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 258
4. Flared or vented greater than 1 hour 0
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 19,345
6. Used for lease operations Fuel 551,082
Assist 0
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 570,685
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 20,368,137
Remarks:
I hereby ce~ t}~ tr fOregOin~oS true and correct to the best of my knowledge.
Signature:. 1.J..... 0 J Title: SUPERVISOR
Form 10-422 (Revised 4/95)
Month/Year of Disposition
07/2002
"Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
MCF
2. Lease Use
MCF
3. Conserv. Purposes
MCF
Commissioner
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE SAY UNIT· GC·2
GAS FLARING INCIDENT REPORT
July 2002
Page 1
Unplanned Events less than or equal to 1 hour
7/4/2002
7/26/2002
7/26/2002
1556-1600
0646-0655
2149-2201
28 Not required for unplanned events which
63 are less than or equal to 1 hour
167
Not required for unplanned events which
are less than or equal to 1 hour
TOTAL
258
See Attachments
Intermittent
o
See Attachments
TOTAL
Planned Events Less Than or Equal 1 Hour AND Not Exceedin
See Attachments
See Attachments
TOTAL
o
Planned Events Exceeding 1 Hour OR Exceedin
See Attachments
See Attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
258
o
o
o
19,603
8/12/2002
2:43 PM
Facility
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s)
BP EXPLORATION, ALASKA WESTERN OPERATING AREA-PBU
GATHERING CENTER 2
Disposition
Volume MCF"
1. Sold
2. Reinjected
o
o
3. Flared or vented less than 1 hour.
3,595
4. Flared or vented greater than 1 hour
(Su lemental report required - See 20 AAC 25.235)
5. Pilot and Purge
6. Used for lease operations
7. Other
8. NGL gas equivalent produced
9. Purchased gas
10. Transferred from:
11. Transferred to: CCP
Remarks:
394
20,391
Fuel
Assist
590,132
o
Lift Gas, Off Field
o
TOTAL items 1 - 7
614,512
o
o
o
20,731,435
I hereby cert'
Signature:
Form 10-422 (Revised 4/95)
Title: SUPERVISOR
"Indicate contribution of each pool to total.
Pool Name
Code
Percent
PRUDHOE
640150
100.00%
1. Safety
.3t4» MCF ~
2. Lease Use
MCF
3. Conserv. Purposes
MCF
~.~
\/2(,,/0 :>-
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUOHOE BAY UNIT - GC-2
GAS FLARING INCIOENT REPORT
August 2002
Page 1
ual to 1 hour
8/3/2002
8/5/2002
8/6/2002
8/7/2002
8/8/2002
r&/9/2002
U8/10/2OO2
8/10/2002
8/10/2002
8/14/2002
8/16/2002
8/16/2002
8/19/2002
8/20/2002
8/20/2002
8/27/2002
8/30/2002
8/31/2002
8/31/2002
181 Not events which
69 are less than or equal to 1 hour
125
33
63
140
50r
270
150
260
106
229
139
84
700
347
250
52
156
191
Not for events
are less than or equal to 1 hour
1034-1054
2314-2332
0915-0919
0243-0252
0136-0156
-:z358:2400
0001-0033
0202-0224
0458-0537
1638-1655
0157-0219
1737-1757
1427-1438
1356-1432
1742-1832
0927-0948
1135-1140
1012-1021
1235-1246
¡"Sl.~ß''c~.j- "~,~~-\O
ck.\er-;'~I\t ~F ~ ~ I
<:;I~ ~'€t t:-: j'Ç 5." ~ì..;~,.kv
Iøi:' ir'\C(..u.;leg r.{ç (- 1412- ~
Úß12-
TOTAL
3,595
IUnplanned Events greater than 1 hour
'".O)\Te· '·TI",e ',V9lUME ·1>ej;C/JfPTJØN'Of"lNeJO~&ç:AUSe·
8/15/2002 0433-0544 394 See Attachments
Intermittent
TOTAL 394
·ÄÇTlON TAtœ.f:I TpeWMIItATj;'Ci\,USE; ."".
See Attachments
IPlanned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Met
, '·DATE . TIME .. u 'u:VQlUMS·, P!~RIPT!()Jj};~!"!I!I:CII,),I!t"'FIiR~US¡:¡" /'CA,CTIOIITAKEIITI)'ELJMINATECAUSE':uU
See Attachments See Attachments
TOTAL
o
¡Planned Events Exceeding 1 Hour OR Exceedin~ 5000 Met
, DATE ·u .,. uTIME..' "VOlUM! DI!SCRII'fION:OF'INCI¡¡!NHi:CAUSI;,u
See Attachments
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
.,. /!..CTlON'TA~EN TOEl;lMINATJi;CAtJS!., .
See Attachments
I
TOTAL
o
394
o
o
24,380
9/1112002
3:01 PM
REPORT NO: 02-0554
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: GC2
DATE: 15 Aug 2002
SYSTEM
1. Flare/Relief Valve
TIME OF FLARING
Start Stop Duration
04:33 05:44 1 Hrs 11 Mins
Black
Intermittent Smoke
Planned
o 0
o
VOLUME
394 MSCF
394 MSCF
TOTAL VOLUME
First Determination of Cause:
1. High gas transit line pressure, ambient air temperature 48 degrees, too much gas for current
ambient air temperature.
Action Taken to Stop Flaring:
1. WOA reduced production rates and shut-in 6 wells equaling 100 mmscfd. Wells were shut-in or
choked back starting at 04:34 hours.
EOA shut-in 100 mmscfd at 05:31 hrs.
VVednesday, August 21, 2002
Page 1 of 1
OPB Flaring Incident
Subject: GPB Flaring Incident
Date: Fri, 16 Aug 2002 21 :41 :30 -0500
From: "GPB, Prod Opt TL" <GPBProdOptTL@BP.com>
To: 'steve _ mcmains@admin.state.ak.us'
CC: "Fiedler, Anne M" <Fied1eAM@BP.com>, "Benson, Gary A" <BensonGA@BP.com>,
"Pfeiffer, Jim A" <PfeiffJA@BP.com>,
"GPB, Environ Advisor West" <GPBEnvironAdvisorWest@BP.com>
>
>
>
>
>
> Leader, 907-659-4472
>
>
>
>
>
>
>
>
>
>
>
>
>
>
>
>
To:
Steve McMains, AOGCC
steve mcmains@admin.state.ak.us
907-793-1241, fax 907-276-7542
From:
Michael Bolkovatz, GPB Prod Optim Team
This note is to inform you of an extended flaring
incident at GC2.
On August 15, starting at 04:33, the ambient
temperature starting increasing at a higher than normal rate. This caused
a higher than allowable gas transit line pressure and GC2 flare valve
opened. Wells totaling 100 MSCFPD were immediately SI on the WOA, and an
additional 100 MMSCFPD was SI on the EOA at 05:31 when the flare valve did
not reseat. This was enough rate cut/pressure decrease to reseat the flare
valve at GC2 at 05:44. A total of 394 MSCF was flared over this 1 hr, 11
min period.
If you require additional information, please don't
hesitate to call me.
Michael Bolkovatz
GPB Production Optimization TL
659-5566, 659-4472
1 of 1
8/19/20027:26 AM
GATHERING CENTER 2
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA WESTERN OPERATING AREA-PBU 09/2002
Facility
Disposition
Volume MCF"
"Indicate contribution of each pool to total.
1. Sold
o
Pool Name
Code
Percent
2. Reinjected
o
PRUDHOE
640150
100.00%
3. Flared or vented less than 1 hour.
3,047
4. Flared or vented greater than 1 hour
(Supplemental report required - See 20 AAC 25.235)
o
5. Pilot and Purge
18,202
6. Used for lease operations
Fuel
Assist
353,710
o
7. Other
Lift Gas, Off Field
o
TOTAL items 1 - 7
374,959
1. Safety
MCF
8. NGL gas equivalent produced
o
2. Lease Use
MCF
9. Purchased gas
o
3. Conserv. Purposes
MCF
10. Transferred from:
o
Commissioner
Date
11. Transferred to: CCP
11 ,304,169
I hereby certi?í that t
Signature: 1<.. I
Form 10-422 (Revised 4/9 )
foregoing is true and correct to the best of my knowledge.
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
Remarks:
Title: SUPERVISOR
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT· GC-2
GAS FLARING INCIDENT REPORT
September 2002
Page 1
IUnplanned Events less than or equal to 1 hour
DATE TIM¡ VoLUME DESC¡:UPTIONOF INCIDEN'J1 8< CAUsE
9/2/2002 1241·1250 63 Not required for unplanned events which
9/4/2002 0917-0933 111 are less than or equal to 1 hour
9/4/2002 0939-0954 94
9/4/2002 1500-1556 417
9/4/2002 1619-1640 146
9/5/2002 0250-0306 111
9/5/2002 1 028-1 044 133
9/5/2002 1245-1258 90
9/5/2002 1341-1416 243
9/512002 1930-1935 17
9/5/2002 2233·2240 24
9/6/2002 0000-0019 264
9/6/2002 1307-1326 198
9/7/2002 0545-061 0 521
9/7/2002 1128-1134 63
9/7/2002 11 49-1204 156
9/10/2002 0835-0856 292
9/12/2002 1016-1031 104
TOTAL
3,047
IUn¡>lanned Events greater than 1 hour
DATE TIME VOLUME
ACTION TAKEN TO· ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
DESCRIPTION OF INCIDENT 8< CAUSE
See Attachments
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
TOTAL
o
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
IPlanned Events Less Than or Equal 1 Hour AND Not ExeeedinQ 5000 Met
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See Attachments
TOTAL
o
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
¡Planned Events Exeeedin\l1 Hour OR Exeeedin~ 5000 Met
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See Attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5.000 MCF
Planned Events> 1 hour or
exceeding 5.000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
o
o
o
21,249
10/412002
2:31 PM
GATHERING CENTER 2
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA WESTERN OPERATING AREA-PBU 10/2002
Facility
Disposition
Volume MCF"
"Indicate contribution of each pool to total.
1. Sold
o
Pool Name
Code
Percent
2. Reinjected
o
PRUDHOE
640150
100.00%
3. Flared or vented less than 1 hour.
1,087
4. Flared or vented greater than 1 hour
(Supplemental report required - See 20 AAC 25.235)
5,165
5. Pilot and Purge
24,124
6. Used for lease operations
Fuel
Assist
629,336
o
7. Other
Lift Gas, Off Field
o
TOTAL items 1 - 7
659,712
1. Safety
5;16S MCF .y~_
8. NGL gas equivalent produced
o
2. Lease Use
MCF
9. Purchased gas
o
3. Conserv. Purposes
MCF
10. Transferred from:
o
~~ tD..J.,,¡: !fi,t"
CommisGoner
\~L ?> \ 0 .)-
Date
11. Transferred to: CCP
19,666,777
I ~erebY cerpty V\at
Signature: K U,
Form 10-422 (Revised 4/95)
is true and correct to the best of my knowledge.
Title: SUPERVISOR
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
Remarks:
BP EXPLORATION (ALASKA) INC.
PRUDHOE SAY UNIT - GC-2
GAS FLARING INCIDENT REPORT
October 2002
lunplanned Events less than or equal to 1 hour
DATE TIME VOLuME DESCRIPTIONOFINCIDENrllrCAUSE
10/1/2002 1842-1847 35 Not required for unplanned events which
10/1/2002 2217-2222 17 are less than or equal to 1 hour
10/2/2002 0458-0502 28
10/6/2002 2141-2150 88
10/7/2002 0504-0528 267
10/7/2002 2133-2145 125
10/7/2002 2158-2208 125
10/8/2002 0417-0424 58
10/9/2002 0142-0152 69
10/23/2002 1307-1316 94
10/30/2002 2319-2332 181
Page 1
TOTAL
1,087
lunplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
10/3/2002 0740-0847 5,165 See Attachments
TOTAL
5,165
Iplanned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mct
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See Attachments
TOTAL
o
Iplanned Events Exceeding 1 Hour OR Exceeding 5000 Mct
DATE TIME VOLUME DESCRIPTlONOflNCIOENT & CAUSE
See Attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
TOTAL
1,087
5,165
o
o
30,376
ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
11/13/2002
2:16PM
REPORT NO: 02-0694
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: GC2
DATE: 03 Oct 2002
SYSTEM
1. Flare/Relief Valve
TIME OF FLARING
Start Stop Duration
0140 0&41 1 Hrs 7Mins
Black
Intermittent Smoke
o 0
Planned VOLUME
o 5,165 MSCF
TOTAL VOLUME 5,165 MSCF
First Determination of Cause:
1. K-7000 LPS compressor sid.
Action Taken to Stop Flaring:
1. Choked all LP wells that could be choked back remotly.
Friday, October 25, 2002
Page 1 of 1
Facility
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
perator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA WESTERN OPERATING AREA-PBU 11/2002
GATHERING CENTER 2
Disposition Volume MCF"
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 6,030
4. Flared or vented greater than 1 hour 0
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 26,483
6. Used for lease operations Fuel 582,500
Assist 0
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 615,013
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 19,058,340
Remarks:
I hereby cert~.thðte tregOing isp~e and correct to the best of my knowledge.
Signature: . , .J A../7\ h Title: SUPERVISOR
Form 10-422 (Revised 4/95)
"Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
MCF
2. Lease Use
MCF
3. Conserv. Purposes
MCF
Commissioner
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-2
GAS FLARING INCIDENT REPORT
November 2002
Page 1
lunPlanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION .OFHNCIDENT&CAUSE
11/1/2002 1935-1955 486 Not required for unplanned events which
11/6/2002 1439-1517 3,958 are less than or equal to 1 hour
11/6/2002 2129-2136 15
11/7/2002 1548-1615 206
11/9/2002 1610-1700 417
11/10/2002 0240-0248 78
11/10/2002 0344-0356 117
11/16/2002 1157-1214 177
11/17/2002 0815-0843 311
11/24/2002 1449-1455 63
11/24/2002 1639-1704 174 Intermittent
11/25/2002 1755-1759 28
TOTAL 6,030
ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
lunplanned Events greater than 1 hour
DATE TIME VOLUME
DESCRIPTION OF INCIDENT & CAUSE
See Attachments
TOTAL
o
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
IPlanned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mct
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See Attachments
TOTAL
o
~Planned Events Exceeding 1 Hour OR Exceeding 5000 Mct
DATE TIME VOLUME DESCRIPTION OF INCIDENT.,. CAUSE
See Attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
o
o
o
32,513
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
12/9/2002
11:10AM
Facility
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA WESTERN OPERATING AREA-PBU 12/2002
GATHERING CENTER 2
Disposition Volume MCF"
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 1,612
4. Flared or vented greater than 1 hour 2,813 /'
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 24,877
6. Used for lease operations Fuel 676,525
Assist 0
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 705,827
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 21,107,311
Remarks:
I hereby ceU~athe fOregO~g is true and correct to the best of my knowledge.
Signature: J . ..... a.. Title: SUPERVISOR
Form 10-422 (Revised 4/95)
"Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
:; ß 13 MCF <YiJ2-
2. Lease Use
MCF
3. Conserv. Purposes
MCF
d/¡ð!o3
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-2
GAS FLARING INCIDENT REPORT
December 2002
Page 1
lunplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTJON OFJNCIDENT& CAUSE
12/7/2002 2306-2311 35 Not required for unplanned events which
12/8/2002 0246-0253 97 are less than or equal to 1 hour
12/15/2002 2341-2400 1,319
12/23/2002 1442-1448 42
12/24/2002 0454-0502 28
12/24/2002 1817·1834 56
1225-02 2223-2228 35
TOTAL
1,612
IUnplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
12/16/2002 0000-0121 2,813 See Attachments
TOTAL
2,813
Iplanned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mct
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See Attachments
TOTAL
o
Iplanned Events Exceeding 1 Hour OR Exceeding 5000 Mct
DATE TIME VOLUME DESCRIPTIONOFfNCIDENT & CAUSE
See Attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL
1,612
2,813
o
o
TOTAL FLARED VOLUME
29,302
ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
1/10/2003
3:18 PM
REPORT NO: 02-0875
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: GC2
DATE: 16 Dee 2002
SYSTEM
1. Flare/Relief Valve
TIME OF FLARING
Start Stop Duration
00:00 01 :21 1 Hrs 21 Mins
Black
Intermittent Smoke
D D
Planned VOLUME
D 2,813 MSCF
TOTAL VOLUME 2,813 MSCF
First Determination of Cause:
1. LPS compressor K-7000 shut down because of control/instrumentation failure associated with a
faulty power supply.
Action Taken to Stop Flaring:
1. WOA reduced production rates and shut-in 34 wells equaling 250mmscfd. Wells were shut-in or
choked back starting at 23:42 hours.(12/15)
Thursday, December 26, 2002