Disposition Volume MCF*
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 0
4. Flared or vented greater than 1 hour 0
(Supplemental report required - See 20 MC 25.235)
5. Pilot and Purge 26,349
6. Used for lease operations Fuel 760,601
Assist 8,440
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 795,390
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: CGF 300,947
11. Transferred to: CCP 82,039,946
Remarks:
I hereby ce(¿thfihe tegOing iS1~e and correct to the best of my knowledge.
Signature: ~ . ...L1.- 11. Title: SUPERVISOR
Form 10-422 (Revised 4/95)
*Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
MCF
2. Lease Use
MCF
3. Conserv. Purposes
MCF
Commissioner
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
~
f
Page 1
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-1
GAS FLARING INCIDENT REPORT
January 2004
lunplanned Events less than or egual to 1 hour
DATE TIME VOLUME.. DESCRIPTION OF INCIDENT & CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
TOTAL
. . ..ACTlQN TAKEN TO EUMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
o
Unplanned Events greater than 1 hour
TOTAL
See attachments
See attachments
o
See attachments
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mct
TOTAL
See attachments
o
Planned Events Exceedin 1 Hour OR Exceeding 5000 Mct
TOTAL
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
See attachments
See attachments
o
o
o
o
o
34,789
2/6/2004
10:42 AM
Facility
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA EASTERN OPERATING AREA-PBU 02/2004
FLOW STATION 1
Disposition Volume MCF*
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 214
4. Flared or vented greater than 1 hour 0
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 24,281
6. Used for lease operations Fuel 752,229
Assist 8,376
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 785,100
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: CGF 292,243
11. Transferred to: CCP 79,214,482
Remarks:
I hereby certð, that thÆ foreg01 is true and correct to the best of my knowledge.
Signature: (1. .A ~../\ Þ Title: SUPERVISOR
Form 10-422 (Revised 4/95)
'Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
MCF
2. Lease Use
MCF
3. Conserv. Purposes
MCF
Commissioner
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
SP EXPLORATION (ALASKA) INC.
PRUDHOE SAY UNIT - FS-1
GAS FLARING INCIDENT REPORT
February 2004
Page 1
lunplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
2/9/2004 1446-1504 169 Not required for unplanned events which
2/12/2004 2340-2343 29 are less than or equal to 1 hour
2/28/2004 0207-0213 5
2/28/2004 2236-2237 8
TOTAL
211
lunplanned Events greater than 1 hour
DATE TIME VOLUME
DESCRIPTION OF INCIDENT & CAUSE
See attachments
TOTAL
o
~Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
2/9/2004 0330-0335 3 See attachments
TOTAL
3
~Planned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
211
o
3
o
TOTAL FLARED VOLUME
32,871
ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
3/5/2004
2:07 PM
FACILITY: FS1
SYSTEM
1. Controlled Blowdow
2. FlarelRelief Valve
REPORT NO: 04-0042
BPXA FLARE REPORT
PRUDHOE BAY
DATE: 09 Feb 2004
TIME OF FLARING
Start Stop Duration
03:30 03:35 0 Hrs
Black
Intermittent Smoke
5Mins 0 0
Planned
~
o
14:46 15:04 0 Hrs 18Mins ~ ~
TOTAL VOLUME
First Determination of Cause:
1. Normal stop on 1801 TIC.
2. While swapping STV/IP Compressors 1801 to 1802, 1802 TIC wouldn't stay loaded.
Action Taken to Stop Flaring:
1. 1801 TIC depressUl:ed,after.RO(maJstop.,{':U~02T/Coo .Iine)
2. Finally got 1802 TIC to take the load.
Monday, February 23, 2004
VOLUME
3 MSCF
""'1'69"MSef
172 MSCF
Page 1 of 1
Facility
FLOW STATION 1
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA EASTERN OPERATING AREA-PBU 03/2004
Disposition Volume MCF*
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour. 25
4. Flared or vented greater than 1 hour 0
(Supplemental report required - See 20 AAC 25.235)
5. Pilot and Purge 26,305
6. Used for lease operations Fuel 810,094
Assist 7,252
7. Other Lift Gas, Off Field 0
TOTAL items 1 - 7 843,676
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: CGF 310,402
11. Transferred to: CCP 82,704,582
Remarks:
I hereby ce72. that tt foregoiö :s true and correct to the best of my knowledge.
Signature: . Q. .J A..A .J' Title: SUPERVISOR
Form 10-422 (Revised 4/95)
*Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100.00%
1. Safety
MCF
2. Lease Use
MCF
3. Conserv. Purposes
MCF
Commissioner
Date
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
SP EXPLORATION (ALASKA) INC.
PRUDHOE SAY UNIT - FS-1
GAS FLARING INCIDENT REPORT
March 2004
lunplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
3/31/2004 0323-0325 17 Not required for unplanned events which
are less than or equal to 1 hour
Page 1
TOTAL
17
~unplanned Events greater than 1 hour
DATE TIME VOLUME
DESCRIPTION OF INCIDENT & CAUSE
See attachments
TOTAL
o
Iplanned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
3/18/2004 1501-1501 1 See attachments
3/19/2004 1354-1359 7
TOTAL
8
Jplanned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
17
o
8
o
TOTAL FLARED VOLUME
33,582
ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
4/8/2004
3:08 PM
REPORT NO: 04-0082
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 18 Mar 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 15:01 15:01 OHrs OMins 0 0 ~~,LMSCF
TOTAL VOLUME
1 MSCF
First Determination of Cause:
1. Depressured CHD system to STV flare to repair leak.
Action Taken to Stop Flaring:
1. System depressured.
Tuesday, March 30, 2004
Page 1 of 1
REPORT NO: 04-0087
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 19 Mar 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief,Valwe" 1.3:54,,, 1.3:59.,. "QJ¡J(-S .,,5,Mins 0 0 M ,;Z"MSCF
TOTAL VOLUME
7 MSCF
First Determination of Cause:
1. Four aborted starts of TIC 1801 between 10:37 and 11 :20 (4 mscf). One normal stop of TIC 1801 at
13:54 (3 mscf).
Action Taken to Stop Flaring:
1. Trouble shooting vibration problem with TIC 1801. Shut down to serve as standby machine.
Tuesday, March 30, 2004
Page 1 of 1
Facility
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Operator Field(s) Month/Year of Disposition
BP EXPLORATION, ALASKA EASTERN OPERATING AREA-PBU 04/2004
FLOW STATION 1
Disposition
Volume MCF*
1. Sold
2. Reinjected
3. Flared or vented less than 1 hour.
959
4. Flared or vented greater than 1 hour
(Supplemental report required - See 20 AAC 25.235)
33,154
5. Pilot and Purge
25,177
6. Used for lease operations
Fuel
Assist
743,883
28,863
7. Other
Lift Gas, Off Field
TOTAL items 1 - 7
832,036
8. NGL gas equivalent produced
9. Purchased gas
10. Transferred from: CGF
290,714
11. Transferred to: CCP
72,474,831
Remarks:
Signature:
Form 10-422 (Revised 4/95)
Title: SUPERVISOR
o
o
o
o
o
*Indicate contribution of each pool to total.
Pool Name
Code
Percent
PRUDHOE
640150
100,00%
1, Safety
33 1'54 MCF ,:re-
I
2. Lease Use
MCF
MCF
Note: All volumes must be corrected to pressure of 14.65
psia and to a temperature of 60 degrees F. Report due by
the 20th of the month following the month of disposition.
Authority 20 AAC 25.235.
Page 1
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-1
GAS FLARING INCIDENT REPORT
April 2004
lunplanned Events less than or equal to 1 hour ,., +~
;WHWWiJW!i?:i?i§¡¥WHHv;;;;;HiJW¡giJ&§!!!r1§mHi;nHLn;;D;Lnsi~~.!fiJgtM§mm¡¡m!i?§~ç;B!I1t1!1!~"9¡31I,ªil!!lç;I¡!i?§æ¡~¡~~!it[§l;fm¡Dç;n{;;;;;;iç;;iJnD;§¡mm~º¡I1'~!!I¡;'f~~§!!In1'!;~n§!iit!!r1I!!1~'!'1§;;º~j1¡~§E;¡nii'
4/21/2004 2210-2215 3 Not required for unplanned events which Not required for unplanned events which
4/27/2004 0745-0746 20 are less than or equal to 1 hour are less than or equal to 1 hour
4/27/2004 0845-0847 30
4/27/2004 0915-0916 20
4/27/2004 1549-1624 525
TOTAL
598
lunp,anned Events greater than 1 hour
" '[)ATE" ' "TIME' ,', ' " VOI;;UME;Pt:~cRIPTI~NoF'INCII;)eNT&CAU~E'
4/11/2004 0415-0640 32,200 See attachments
4/17/2004 1930-2100 750
, 'ACTI()NTAKENTO'ELlMINATECAUSE
See attachments
, , , , ,., "I
TOTAL
32,950
~Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf
;¡¡¡mm¡¡,ª~'!'1§mM¡;¡¡¡;¡ii¡;¡¡¡¡¡¡n¡¡'ŒLtl1!M§¡¡;¡¡¡¡mLŒ¡¡¡¡¡¡;¡¡¡i¡;¡~~!£!!!¡M§@¡¡Œ¡¡;¡¡!i?§iºB',f?:¡nI!;!!Im~,ªi¡'!!IiÇ;',ª¡§!!I'f;m~¡~~j1i§ç,;;;';Y""i"'V"""L~Ç;'!'1liON¡]A~§!!Ii'f~E§I+IMJ!!IA'feicAuSE"
4/8/2004 1330-1333 3 See attachments See attachments
4/10/2004 0315-0320 60
4/10/2004 0346-0434 267
4/1 0/2004 0445-0450 1 0
4/12/2004 0400-0405 3
4/18/2004 1050-1055 3
4/24/2004 1415-1420 3
4/25/2004 0930-0935 3
4/30/2004 1040-1045 3
4/30/2004 1120-1155 3
4/30/2004 1200-1205 3
TOTAL
361
5/11/2004
1 :29 PM
Page 2
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT· FS-1
GAS FLARING INCIDENT REPORT
April 2004
Iplanned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
, pATE: " ·::tIME · .'·V.o¡;;U:ME:ºE~ÇFUPT,I,ØN.Ø,F(rljçlt>,E;~r&;çAI,J:~E
4/17/2004 0850-1100 204 See attachments
, 'APTI()NTA'KErIj:T:OELlMINATECAI,JSE: '
See attachments
I
TOTAL
204
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
598
32,950
361
204
TOTAL FLARED VOLUME
88,153
5/11/2004
1 :29 PM
REPORT NO: 04-01 05
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 08Apr 2004
TIME OF FLARING Black
SYSTEM StartStop· 'Durátion 1nterrriittent'-Smoke Planned VOLUME
1. Flare/Relief Valve 13:30 13:33 OHrs 3Mins n 0 ~ 3 MSCF
TOTAL VOLUME
3 MSCF
First Determination of Cause:
1. Normal stopped TIC 1802.
Action Taken to Stop Flaring:
1. Completed flaring after normal stop.
Sunday, April 25, 2004
Page 1 of 1
REPORT NO: 04-01 09
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 10 Apr 2004
TIME OF FLARING
SYSTEM ""Start 'Stop "DurâtÎon '1 h"termittent
1. FlarelRelief Valve 0.3:1.5 0.3:20 OHrs 5.Mins. ,n
2. Flare/Relief Valve
3. Flare/Relief Valve
03:46 04:34 0 Hrs 48 Mins
04:45D4:5o. O'Hrs BNlins
o
o
Black
Smoke Planned VOLUME
0 ~ ,60 MSCF
0 ~ 267 MSCF
0 ~ 10. 'MSCF
TOTAL VOLUME 337 MSCF
First Determination of Cause:
1. Emergency stop test on 1803 TC.
2. Cranked Turbine to cool down the case for water wash and inspection. (1803).
3. Flared to test check valve above 1803 compressor 'case.
Action Taken to Stop Flaring:
1. Emergency test completed. Not a BESD.
2. completed cool down of 1803 turbine
3. completed check valve test and blocked manual valve to flare.
Sunday, April 25, 2004
Page 1 of 1
REPORT NO: 04-0111
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 11 Apr 2004
TIME OF FLARING Black
SYSTEM Start "Stop Duration Intermittent Smoke Planned ., VOLUME
1. Flare/Relief Valve 04: 15 06:40 2 Hrs 25 Mins 0 0 0 32,200 MSCF
TOTAL VOLUME 32,200 MSCF
First Determination of Cause:
1. While E.S.D. Testing TIC 1804, TIC 1803 also SID. Leaving both L.P.S. Turbines SID.
Action Taken to Stop Flaring:
1. TIC 1803 1 st Start - No go due to Starting Clutch Disengaged.
TIC 1803 2nd Start - No go due to High Vibration SID.
TIC 1803 3rd Start - No go due to Failure to Fire.
TIC 1803 4th Start - No go due to High Vibration SID.
TIC 1804 Started and loaded .
Shut in the listed wells: 5-5,5-9,2-37,2-11,18-24,2-30,12-13,12-36,12-15,
12-3.
Reduced choke on 12-29 to min..
Sunday, April 25, 2004
Page 1 of 1
REPORT NO: 04-0114
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 12 Apr 2004
TIME OF FLARING Black
SYSTEM StartStop'Durätìon Intermittént Smoke Planned VOLUME
1. Flare/Relief Valve 04:.00 04:05., OHrs5Mins ,n 0 ø .3..MSGF
TOTAL VOLUME
3 MSCF
First Determination of Cause:
1. Normal stop 1801 TC.
Action Taken to Stop Flaring:
1. 1801 Compressor case depressuring completed.
Sunday, April 25, 2004
Page 1 of 1
REPORT NO: 04-0121
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 17 Apr 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 08:50 11 :00 2 Hrs 10 Mins D D ~ 204 MSCF
2. Flare/Relief Valve 19:30 21 :00 1 Hrs 30 Mins ~ D 0 750 MSCF
TOTAL VOLUME
"954 MSCF
First Determination of Cause:
1. Oepressured commonlines 20/5E, 58 and 50 for maintenance work at Orillsite 5.
2. 1802 STV case unload several times.
Action Taken to Stop Flaring:
1. Oepressuring completed.
2. Idle and reloaded 1802 each tinme.
Sunday, April 25, 2004
Page 1 of 1
REPORT NO: 04-0123
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 18 Apr 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/ReliefValve 10:50 10:55 OHrs" 5Mins 0 0 ~ ..3MS.GF
TOTAL VOLUME
3 MSCF
First Determination of Cause:
1. Shut down TIC 1802 for maintenance work.
Action Taken to Stop Flaring:
1., Compresso.rcase ,depressured.
Sunday, April 25, 2004
Page 1 of 1
REPORT NO: 04-0135
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 24 Apr 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 14:15 14:20 0 Hrs 5 Mins 0 0 ~ ..3 MSCF
TOTAL VOLUME
3 MSCF
First Determination of Cause:
1. ESD/OSD testing for TIC 1801
Action Taken to Stop Flaring:
1. Completed ESD/OSD testing
Sunday, April 25, 2004
Page 1 of 1
REPORT NO: 04-0137
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 25 Apr 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOL.UME
1. Flare/Relief Valve 09:30 09:35 0 Hrs 5 Mins 0 0 ~ 3 MSCF
TOTAL VOLUME
3 MSCF
First Determination of Cause:
1. TIC 1801 OSD/ESD testing
Action Taken to Stop Flaring:
1. completed testing
Monday, May 03, 2004
Page 1 of 1
REPORT NO: 04-0150
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 30 Apr 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 10:40 10:45 0 Hrs 5 Mins 0 0 ~3,MSCF
2. Flare/Relief Valve 11 :20 11 :55 0 Hrs 35 Mins ~ 0 ~ 3 MSCF
3. Flare/Relief Valve 12:00 12:05 0 Hrs 5 Mins 0 0 ~ ·'3MSCF
TOTAL VOLUME
9 MSCF
First Determination of Cause:
1. 1801 TIC started, idled and shut down for maintenance work.
2. Three aborted starts pn 1801 TIC
3. Normal stop for 1801 TIC.
Action Taken to Stop'Flaring:
1. 1801T/C depressured at shut down.
2. 1801 T/C started on idle.
3. 1801T/Cdepressured atshut'down.
Monday, May 03, 2004
Page 1 of 1
FW: GPB Flaring Incident
-----Original Message-----
From:
Sent:
To:
Cc:
Advisor
Subject:
GPB, Prod Opt TL
Monday, April 12, 2004 5:59 PM
'steve mcmains@adrnin.state.ak.us"
FIedler ~--ÄÏÏne--M;BerÚ¡on;--Gary-jí:; Pfeiffer, Jim A;
West; GPB, Environ TL; GPB, Environ Advisor East;
FW: GPB Flaring Incident
GPB, Environ
GPB, FSl TL
To:
Steve McMains, AOGCC
steve mcmains@admin.state.ak.us
907-793-1241, fax 907-276-7542
From:
Hal Tucker, GPB Prod Optim Team Leader,
907-659-4472
An extended flare event occurred on April 11,
2004. Both FSl LPS compressors (15-1803/1804) shut down unexpectedly
during ESD testing (only 1804 was supposed to shut down). Four
attempts were made to restart 15-1803, with no success. Finally
15-1804 was restarted and loaded up. Total volume flared was 32,200
MSCF, over a 2 hour and 25 minute duration. A total of 12 wells were
shut-in and 1 well was choked to minimum, cutting the FSl gas rate by
176 MMSCFD.
If you require additional information, please
don't hesitate to call me.
Hal Tucker
GPB production Optimization TL
659-4472
1 of 1
4/13/20047:08 AM
....~
STATE OF ALASKA
ALASKA Oil AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000028
2. Facility Name
PBU FS 1
Disposition
3. Field
PBU - EOA
Volume MCF
4. Operator 5. Month/Year of Disposition
BP Ma -2004
20. For production from multiple pools. list contribution of each pool as a percent of
Total Volume.
6. Sold
o
Pool Name
PRUDHOE
Pool Code
640150
Percent
7. Reinjected
o
100.00%
8. Flared or vented 1 hour or less
452
9. Flared or vented more than 1 hour (see instr.)
9,000
10. Pilot and Purge
25,916
11. Used for lease operations (specify in Remarks)
782,121
12. Other (see instructions)
o
Authorization> 1 hr:
Safety
q Doo
S£P--
13. TOTAL VOLUME (ITEMS 6-12)
817,489
Lease Use
MCF
14. NGL Gas Equivalent
o
Conservation
MCF
15. Purchased gas
o
Waste:
MCF
16. Transferred from: CGF
279,545
Dat7/2.I/
17. Transferred to: (Express as a negative #) CCP
-73,239,517
18. Remarks: Block II: Fuel Gas = 760,915 mscf and Assist Gas = 21.206 mscf
I hereby certify that the foregoing is ue and correct to the best of my knowledge.
Signature Q~ .
Printed Name
Title
Note: All volumes must be
corrected to pressure of 14.65 psia
and to a temperature of 600 F.
Authorit 20 MC25.235.
Phone (907)564-5028
Form 10-422 Rev. 1/2004
Submit in Duplicate
Page 1
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-1
GAS FLARING INCIDENT REPORT
May 2004
Unplanned Events less than or equal to 1 hour
5/12/2004
5/13/2004
5/17/2004
5/21/2004
5/23/2004
0915-0930
2100-2105
0405-0408
0513-0519
1645-1700
0217-0220
4 Not required for unplanned events which
3 are less than or equal to 1 hour
3
271
130
26
Not required for unplanned events which
are less than or equal to 1 hour
TOTAL
437
Iunplanned Events greater than 1 hour
'. '. DATE ',TIME> ' , . 'VOLUME · DESCRIPTION OF INCIDENT & CAUSE, """'.., ACTION TAKEN TO ELIMINATE CAUSE
5/17/2004 1425-1537 9,000 See attachments See attachments
TOTAL
9,000
~Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mct
, ,DATE < TIME · ' , , , , . . VOLUME DESCRIPTION OF INCIDENT & CAUSE
5/4/2004 0915-0920 3 See attachments
5/6/2004 11 00-11 05 3
5/30/2004 1720-1725 3
5/31/2004 0956-1001 3
5/31/2004 1505-1510 3
.' ...... ACTION TAKEN TO ELIMINATE CAUSE,
See attachments
TOTAL
15
Iplanned Events Exceeding 1 Hour OR Exceeding 5000 Mct
.,. DATE TIME ".. VOLUMEDESCRIPTIONOl=INCIDENT & ,CAUSE ,
See attachments
ACTION TAKEN TO ELIMINATE CAt)$E . . .. '
See attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
9,000
15
o
TOTAL FLARED VOLUME
56,574
6/11/2004
2:31 PM
REPORT NO: 04-0164
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 04 May 2004
TIME OF FLARING Black
SYSTEM Stsrt',Stop "Duration' 'intermittent Smoke Planned VOLUME
1. Controlled Blowdow 09:15 09:20 OHrs 5Mins 0 0 ~ 3 MSCF
TOTAL VOLUME
3 MSCF
First Determination of Cause:
1. 1801 TIC started, idled and shut down for maintenance work.
Action Taken to Stop Flaring:
1. 1801 TIC depressured at shut down.
Tuesday, May 25,2004
Page 1 of 1
bp
REPORT NO: 04-0167
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 06 May 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Controlled Blowdow 11 :00 11 :05 0 Hrs 5Mins 0 0 ~ 3 MSCF
TOTAL VOLUME
3 MSCF
First Determination of Cause:
1. 1801 TIC started, idled and shut down after maintenance work.
Action Taken to Stop Flaring:
1. 1801 TIC depressured at shut down.
Tuesday, May 25, 2004
Page 1 of 1
REPORT NO: 04-0176
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 17 May 2004
SYSTEM
1. FlarelRelief Valve
2. Flare/Relief Valve
TIME OF FLARING Black
Start Stop "'oOuration 'intermittent Smoke
05:13 05:19 OHrs 6Mins 0 0
14:25 15:37 1 Hrs 12Mins 0 0
Planned' VOL1JME
o 271 MSCF
o 9,000 MSCF
TOTAL VOLUME 9,271 MSCf
First Determination of Cause:
1. Pressure control valve P-1 O-A V on 'C' slugcatcher came open for no apparent reason.
2. Flared off the Annex for CGF; they lost 1883 Tandem.
Action Taken to Stop Flaring:
1. Operator put P-1 O-A V in manual and closed the valve.'Swapped controller back to auto and the
valve stayed shut.
2. Shut in wells 18-18, 5-38, and 15-48. CGF got 1883 Tandem back on line.
Tuesday, May 25, 2004
Page 1 of 1
FACILITY: FS1
SYSTEM
1. Flare/Relief Valve
BPXA FLARE REPORT
PRUDHOE BAY
DATE: 30 May 2004
TIME OF FLARING Black
Start Stop ,Duration Intermittent Smoke
17:20 17:25 0 Hrs 5 Mins 0 0
REPORT NO: 04-0197
Planned "VOLUME
~ 3 MSCF
TOTAL VOLUME
First Determination of Cause:
1. 1801 I started, idled and shut down for maintenance work.
Action Taken to Stop Flaring:
1. 1801 TIC depressured at shut down.
Tuesday, June 01, 2004
..
3 MSCF
Page 1 of 1
FACILITY: FS1
SYSTEM
1. Flare/Relief Valve
2. Flare/Relief Valve
REPORT NO: 04-0202
BPXA FLARE REPORT
PRUDHOE BAY
DATE: 31 May 2004
TIME OF FLARING
Start Stop DUfatiGn
09:56 10:01 0 Hrs
15:05 15:10 0 Hrs
Black
'~fttermi.tteRt ,Smoke
5Mins 0 0
5Mins 0 0
Planned
~
~
·:¡'Q:¡'ALVOLUM E
First Determination of Cause:
1. 1801 TIC started, idled and shutdown for maintenance work.
2. Shutdown 1802 TIC
Action Taken to Stop Flaring:
1. 1801 TIC completed depressure at shutdown.
2. 1802 TIC completed depressure at shutdown.
Tuesday, June 01, 2004
..
~ .
V-oLUME
3 MSCF
3 MSCF
6 MSCF
Page 1 of 1
GPB Flaring Incident
To: Steve McMains, AOGCC
steve _mcmains@admin.state.ak.us
907-793-1241, fax 907-276-7542
From: Michael Bolkovatz, GPB Prod Optim Team Leader, 907-659-5566
An extended flare event occurred beginning at 14:25 on May 17, 2004 at FS1. CGF Tandem 1883
shutdown on a false fire & gas BESD (blowdown) switch resulting in a high pressure on the gas
transit header. Per normal upset response, we flared at FS 1 to maintain the gas transit header
pressure. FS1 flaring lasted for 1 hr, 12 mins until the CGF tandem was restarted. FS1 shutin a total
of 170 MMSCFPD during the flaring to reduce the pressure on the header. Total gas flared was
9,000 MSCF.
If you require additional information, please do not hesitate to call me.
Michael Bolkovatz
GPB Production Optimization TL
,
1 of 1
5/18/20041:47 PM
STATE OF ALASKA
ALASKA Oil AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000028
2. Facility Name
PBU FS 1
Disposition
3. Field
PBU - EOA
Volume MCF
4. Operator 5. MonthlYear of Disposition
BP June-2004
20. For production from multiple pools. list contribution of each pool as a percent of
Total Volume.
6. Sold
o
Pool Name
PRUDHOE
Pool Code
640150
7. Reinjected
o
8. Flared or vented 1 hour or less
188
9. Flared or vented more than 1 hour (see instr.)
20,653
10. Pilot and Purge
25,144
11. Used for lease operations (specify in Remarks)
713,013
12. Other (see instructions)
o
13. TOTAL VOLUME (ITEMS 6-12)
758,998
14. NGL Gas Equivalent
o
15. Purchased gas
o
16. Transferred from: CGF
255,277
17. Transferred to: (Express as a negative #) CCP
-60,712,842
18. Remarks: Block 11: Fuel Gas = 698,586 mscf and Assist Gas = 14,427 mscf
I hereby certify that the foregoing'
Signature Q. G.
Percent
100.00%
~R-
Title
Note: All volumes must be
corrected to pressure of 14.65 psia
and to a temperature of 600 F.
Authorit 2 AAC25.235.
Printed Name
Robert A. Re nolds
Phone (907)564-5028
Date 1
Submit in Duplicate
Form 10-422 Rev. 1/2004
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-1
GAS FLARING INCIDENT REPORT
June 2004
lunplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
6/28/2004 2125-2136 76 Not required for unplanned events which
6/28/2004 2148-2157 63 are less than or equal to 1 hour
6/28/2004 2252-2259 49
Page 1
TOTAL
188
lunPlanned Events greater than 1 hour
DATE" TIME VOLUME' DESCRIPTION OF INCIDENT & CAUSE
6/2/2004 1542-1649 10,794 See attachments
6/17/2004 1000-2400 6,445
6/18/2004 0000-0245 2,046
TOTAL
19,285
Iplanned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf
'DATE TIME ' VOLUME 'DESCRIPTION ,OF INCIDENT & CAUSE
See attachments
TOTAL
o
Iplanned Events Exceedin~ 1 Hour OR Exceedin2 5000 Mcf
DATE TIME 'VOLUME DESCRIPTION OF INCIDENT & CAUSE
6/20/2004 1430-1600 1 ,355 See attachments
6/29/2004 0011-0325 13
TOTAL 1,368
Unplanned Events < 1 Hour 188
Unplanned Events> 1 Hour 19,285
Planned Events < 1 hour and not 0
exceeding 5,000 MCF
Planned Events> 1 hour or 1,368
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME 60,412
ACTION TAKEN TO ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
7/8/2004
10:03 AM
REPORT NO: 04-0205
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 02 Jun 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 15:42 16:49 1 Hrs 7Mins ~ 0 0 10,794 MSCF
TOTAL VOLUME 10,794 MSCF
First Determination of Cause:
1. When Drill Site 12 shutdown on ESD, caused 1804 TIC to shutdown.
Action Taken to Stop Flaring:
1. Pinched back on wells 2-27,2-14 and 5-12. Restarted 1804 TIC
Friday, June 18, 2004
Page 1 of 1
REPORT NO: 04-0229
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 17 Jun 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 10:00 24:00 14 Hrs 0 Mins 0 0 0 6,445 MSCF
TOTAL VOLUME 6,445 MSCF
First Determination of Cause:
1. 1801 STV case unloaded due to hot weather.
Action Taken to Stop Flaring:
1. 1801 will not load. Started 1802 in an attempt to pickup load.
Friday, June 18, 2004
Page 1 of 1
REPORT NO: 04-0235
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 18 Jun 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Refief Valve 00:00 02:45 2 Hrs 45 Mins 0 0 0 2,046 MSCF
TOTAL VOLUME 2,046 MSCF
First Determination of Cause:
1. 1801 Compressor STV Case unloaded due to woarm weather.
Action Taken to Stop Flaring:
1. After repeated raising and lowing the speed on 1801 and attemping to
manually load the IP compressor case.
The ambient temperature fell and the IP case loaded and the STV Case
Loaded in auto.
Thursday, July 01, 2004
Page 1 of 1
REPORT NO: 04-0239
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 20 Jun 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Controlled Blowdow 14:30 16:00 1 Hrs 30 Mins 0 0 ~ 1,355 MSCF
TOTAL VOLUME 1,355 MSCF
First Determination of Cause:
1. Oepressured Drill site 2 to flare. Drill site had a tubing leak that required depressuring for safety,
investagation and repair.
Action Taken to Stop Flaring:
1. completed the depressure of the common lines and Drill site 2 Manifold piping to FS1 's flare.
2-b cml depreessured from 700# to 0#
2-D cml 700# to 0#
2-C cml 165# to 0#
2-E cml 700# to 0#
Thursday, July 01, 2004
Page 1 of 1
REPORT NO: 04-0262
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 29 Jun 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 00:11 03:25 3Hrs 14Mins 0 0 ~ 13 MSCF
TOTAL VOLUME
13 MSCF
First Determination of Cause:
1. Depressurization of A Hp oil train due to corrosion problems found.
Action Taken to Stop Flaring:
1. Finished depressurization, blocked in.
Thursday, July 01, 2004
Page 1 of 1
GPB Flaring Incidents
To:
Steve McMains, AOGCC
steve mcmains@admin.state.ak.us
907-793-1241, fax 907-276-7542
From:
Hal Tucker, GPB Prod Optim Team Leader,
907-659-4472
Several extended flare events occurred in the past few
weeks at GPB. This is a note giving you a courtesy "heads up" on the
greater than one hour flare events you will be seeing in the monthly gas
disposition reports prepared by the Anchorage Volume Accounting Team_
* GC3 experienced three flare events on June 24, 25 and 26 due to
K5500 shutting down on high lube oil temperature. Temperature probes,
RTD's and switches were changed out during the three days in attempts to
eliminate that root cause of the shut downs. K5500 procedures were
followed to minimize flaring. Total volume for the three events was
1,261 MSCF, total duration for the three events was 7 hours and 17
minutes.
* ~experienced one extended flare event beginning at 10:00 June
17 and ~g at 02:45 June 18 when the 1801 STV/IP compressor shut down
due to high ambients. Several attempts were made to restart and reload
the machine. Total flare volume for the event was 8,491 MSCF over 16
hours and 45 minutes.
* GC2 experienced two flare events on May 30 and 31 due to PLC
malfunction in the produced water section of the plant. The production
cuts resulting from the water section upset caused the skid 18, IP and
LP compressors to surge intermittently due to the low GC oil rate. The
compressors loaded up as GC2 oil rates returned to normal. Total volume
for the two events was 920 MSCF, total duration was 5 hours and 31
minutes.
* CGF experienced two flare events on June 17 and 18. The first
event occurred when the 1884 tandem shut down 3 times due to high
ambient temperatures over a 2 hour period. Each shut down resulted in 15
minutes of flaring. This event should have been captured as three
separate flaring events and should not be considered as a greater than
one hour event. The second event occurred when the 1805 MI compressor
shut down a recycle trip while loading the boosters. Flaring stopped
when 1805 was restarted. Total duration for the 1805 event was 1 hour
and 14 minutes, total volume was 8,677 MSCF.
* LPC experienced one flare event on June 17 when the 1808 gas
reinjection turbine shut down. Flaring stopped when 1808 was restarted.
lof2
6/28/20047:02 AM
GPB Flaring Incidents
"Gas was cut during the event to reduce flare volume. Total duration for
the event was 1 hour and 16 minutes, total volume was 5,804 MSCF.
* FS3 experienced two flare events on June 17 and June 20. The
first event occurred when the 1801 STV/IP compressor shut down due to
high ambients and plant upsets. After three failed restart attempts, the
spare machine (1802) was started, ending the flare event. Total duration
for this event was 1 hour and 10 minutes, total volume was 466 MSCF. The
second event occurred when the 1806 gas lift machine shut down due to
instrumentation problems. 1806 was secured and depressured, ending the
flare event. Total duration of the event was 6 hours of intermittent
flaring totaling 685 MSCF.
If you require additional information, please do not
hesitate to call me.
Hal Tucker
GPB production Optimization TL
20f2
6/28/20047:02 AM
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000028
2. Facility Name
PBU FS 1
Disposition
3. Field
PBU - EOA
Volume MCF
6. Sold
o
7. Reinjected
o
8. Flared or vented 1 hour or less
833
9. Flared or vented more than 1 hour (see instr.)
14,041
10. Pilot and Purge
26,015
11. Used for lease operations (specify in Remarks)
697,374
12. Other (see instructions)
o
13. TOTAL VOLUME (ITEMS 6-12)
738,263
14. NGL Gas Equivalent
o
15. Purchased gas
o
16. Transferred from: CGF
248,907
17. Transferred to: (Express as a negative #) CCP
-65,415,570
18. Remarks: Block 11: Fuel Gas = 685,853 mscf and Assist Gas = 11,521 mscf
I hereby certify that the foregoing is true and correct to the best of my knowledge.
S;,o,,"re Q.O. ~.A ^~ h
Printed Name Robert A. Re nolds
Title
Phone (907)564-5028
Form 10-422 Rev. 1/2004
4. Operator
5. Month/Year of Disposition
BP Jul -2004
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
Pool Name
PRUDHOE
Pool Code
640150
Percent
100.00%
0£J!-
Note: All volumes must be
corrected to pressure of 14.65 psia
and to a temperature of 600 F.
Authorit 20 MC25.235.
Date
Submit in Duplicate
Page 1
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-1
GAS FLARING INCIDENT REPORT
July 2004
7/2/2004
7/2/2004
7/31/2004
0755-0803
0850-0853
1505-1600
56 Not required for unplanned events which
21 are less than or equal to 1 hour
753
Not required for unplanned events which
are less than or equal to 1 hour
TOTAL
830
Unplanned Events reater than 1 hour
7/2/2004
7/2/2004
7/30/2004
1249-1455
1510-2130
2005-2145
875 See attachments
2,639
2,389
See attachments
TOTAL
5,903
7/12/2004
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf
1 000-1 005
3 See attachments
See attachments
TOTAL
3
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
7/2/2004
7131/2004
1305-1630
0652-1430
See attachments
1,532 See attachments
6,606
TOTAL
8,138
5,903
3
8,138
52,410
8/9/2004
9:54 AM
REPORT NO: 04-0270
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1 DATE: 02 Jul 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 07:55 08:03 OHrs 8Mins ~ 0 0 56 MSCF
2. Flare/Relief Valve 08:50 08:53 OHrs 3Mins ~ 0 0 21 MSCF
3. FlarelRelief Valve 12:49 14:55 2Hrs 6Mins ~ 0 0 875 MSCF
4. FlarelRelief Valve 15:10 21:30 6Hrs 20 Mins ~ 0 0 2,639 MSCF
TOTAL VOLUME 3,591 MSCF
First Determination of Cause:
1. Lost forward flow on 1801 TIC.
2. Lost forward trow on 1801 TIC.
''.¡ 3. Lost forward flow on 1801 TIC because of low gas rates..
'-.,; 4. 1801 TIC shutdown because of low gas rates..
Action Taken to Stop Flaring:
1. Reestablished forward flow on 1801 TIC.
2. Reestablished forward flow on 1801 TIC.
3. Reestablished forward flow on 1801 TIC.
4. Restarted 1801 TIC after maintenace made repairs.
Wednesday, July 28,2004
Page 1 of 1
REPORT NO: 04-0269
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 02 Jul 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. FlarelRelief Valve 13:05 16:30 3 Hrs 25 Mins 0 0 ~ 1,532 MSCF
TOTAL VOLUME 1,532 MSCF
First Determination of Cause:
1. Depressured "B" and "C" HP Trains, 1 B, and 10 commonlines to repair leak on nipple on HP
commonline.
Action Taken to Stop Flaring:
1. Completed depressuring.
Wednesday, July 28,2004
Page 1 of 1
REPORT NO: 04-0288
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 12 Jul 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. FlarelRelief Valve 10:00 10:05 0 Hrs 5 Mins 0 0 ~ 3 MSCF
TOTAL VOLUME
3 MSCF
First Determination of Cause:
1. Normal stop of 1802 T /C
Action Taken to Stop Flaring:
1. Flare stopped when compressor case depressured.
Wednesday, July 28, 2004
Page 1 of 1
REPORT NO: 04-0317
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 30 Jul 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 20:05 21 :45 1 Hrs 40 Mins ~ 0 0 2,389 MSCF
TOTAL VOLUME 2,389 MSCF
First Determination of Cause:
1. TIC 1801 SID due to "Valves Out of Position" alarm.
Action Taken to Stop Flaring:
1. Instr called out to help in restart of TIC 1801. Unit BOL.
VVednesday,August04,2004
Page 1 of 1
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 31 Jul 2004
REPORT NO: 04-0318
SYSTEM
1. Flare/Relief Valve
2. Flare/Relief Valve
TIME OF FLARING Black
Start Stop Duration Intermittent Smoke Planned VOLUME
06:52 14:30 7Hrs 38 Mins 0 0 ~ 6,606 MSCF
15:05 16:00 OHrs 55 Mins ~ 0 0 753 MSCF
TOTAL VOLUME 7,359 MSCF
First Determination of Cause:
1. Shut down 1801 TIC for isolation and maintenance on 1802 TIC
2. 1801 TIC shut down for unknown reasons.
Action Taken to Stop Flaring:
1. Completed blinding 1802 TIC and restarted 1801.
2. Restarted 1801 TIC.
VVednesday,August04,2004
Page 1 of 1
GPB Flaring Incident
'" .'
To: Steve McMains, AOGCC
steve _ mcmains@admin.state.ak.us
907-793-1241, fax 907-276-7542
From: Michael Bolkovatz, GPB Prod Optim Team Leader,
907-659-5566
A planned extended flare event occurred on July 31, 2004. The
1802 STV/IP compressor was shutdown in order to perform a
planned major overhaul on the machine and upgrade the system
controls. Operations personnel were unable to safely isolate this
machine from the plant without also shutting down the other STV/IP
compressor 1801. Both STV/IP compressors were shutdown in
order to blind off 1802. Once the blinding was completed on 1802,
TIC 1801 was restarted and the flaring event ended. TIC 1801
shutdown for unknown reasons 35 minutes after it was started. It
was down an additional 55 minutes. Total volume flared was 7,359
MSCF over an 8 hour and 33 minute duration.
If you require additional information, please don't hesitate to call
me.
Michael Bolkovatz
GPB Production Optimization TL
659-4472
1 of 1
8/2/2004 6:25 AM
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000028
2. Facility Name
PBU FS 1
Disposition
3. Field
PBU - EOA
Volume MCF
6. Sold
o
7. Reinjected
o
8. Flared or vented 1 hour or less
572
9. Flared or vented more than 1 hour (see instr.)
23,225
10. Pilot and Purge
26,172
11. Used for lease operations (specify in Remarks)
683,249
12. Other (see instructions)
o
13. TOTAL VOLUME (ITEMS 6-12)
733,218
14. NGL Gas Equivalent
o
15, Purchased gas
o
16. Transferred from: CGF
247,459
17. Transferred to: (Express as a negative #) CCP
-66,749,404
18. Remarks: Block 11: Fuel Gas = 659,828 mscf and Assist Gas = 23,421 mscf
I hereby certify that the foregoing is true and correct to the best of my knowledge.
Signature Q. Q. ~
Title
Printed Name
Robert A. Re nolds
Phone (907)564-5028
Form 10-422 Rev. 1/2004
4. Operator 5. Month/Year of Disposition
BP Au ust-2004
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
Pool Name
PRUDHOE
Pool Code
640150
Percent
100.00%
J~
Note: All volumes must be
corrected to pressure of 14.65 psia
and to a temperature of 600 F.
Authorit 20 AAC25.235.
Date
Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-1
GAS FLARING INCIDENT REPORT
August 2004
~Unplanned Events less than or equal to 1 hour
·DATE.> . TIME. .. . VOLUME DESCRIPTloNOFINCIDENT&CAUSE'
8/6/2004 1512-1516 30 Not required for unplanned events which
8/6/2004 1553-1558 38 are less than or equal to 1 hour
Page 1
TOTAL
68
IUnplanned Events greater than 1 hour
. DATE .' . .. TIME . . VOLUME · £)ESCRIPTION OF INCIDENT & CAUSE
8/6/2004 1752-1900 1,653 See attachments
8/7/2004 1045-1250 3,038
8/7/2004 1734-2030 5,011
TOTAL
9,702
Iplanned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mct
PATE'TIME<; . ...."". ·····'·VOLUME> . '£)¡¡;~~~I~TIºN!()I'fINÇ!£)ENT8!CA"SEr
8/12/2004 0330-0340 60 See attachments
8/13/2004 0330-0340 60
8/16/2004 0427-0433 204
8/16/2004 0900-0910 60
8/16/2004 1030-1040 60
8/16/2004 1515-1525 60
TOTAL
504
I
~Planned Events Exceeding 1 Hour OR Exceeding 5000 Mct
DATE .... TIME> VOLUME DESCRIPTION OF INCIDENT & CAUSE .....
8/16/2004 1155-1340 2,187 See attachments
8/20/2004 0825-1930 11,336
TOTAL
13,523
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
9,702
504
13,523
TOTAL FLARED VOLUME
73,390
ACTIONTAKEHTO.ELIMINATE CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
.. ACTION TAKEN TO ELIMINATE CAUSE .'
See attachments
·.ACTION TAKEN TO ELIMINATE CAUSE .
See attachments
. . . ACTION TAKEN TO ELIMINATE CAUSE' . . .
See attachments
9/10/2004
1:21 PM
FACILITY: FS1
SYSTEM
1. Flare/Relief Valve
2. Flare/Relief Valve
3. Flare/Relief Valve
REPORT NO: 04-0324
BPXA FLARE REPORT
PRUDHOE BAY
DATE: 06 Aug 2004
TIME OF FLARING Black
Start Stop Duration Intermittent Smoke Planned VOLUME
15:12 15:16 OHrs 4Mins ~ 0 0 30 MSCF
15:53 15:58 OHrs 5 Mins ~ 0 0 38 MSCF
17:52 19:00 1 Hrs 8Mins ~ 0 0 1,653 MSCF
TOTAL VOLUME 1,721 MSCF
First Determination of Cause:
1. 1801 T /C lost load.
2. 1801 TIC lost load.
3. 1801 TIC Shut down (tripped)
Action Taken to Stop Flaring:
1. 1801 T /C took load again.
2. 1801 T/C took load again.
3. Instrumentation restarted 1801 TIC back again and on line.
VVednesday, August 25, 2004
Page 1 of 1
REPORT NO: 04-0325
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 07 Aug 2004
TIME OF FLARING
SYSTEM Start Stop Duration Intermittent
1. FlarelRelief Valve 10:45 12:50 2 Hrs 5Mins 0
2. Flare/Relief Valve
17:34 20:30 2 Hrs 56 Mins ~
Black
Smoke Planned VOLUME
0 0 3,038 MSCF
0 0 5,011 MSCF
TOTAL VOLUME 8,049 MSCF
First Determination of Cause:
1. 1801 TIC shutdown due to high ambient temperature.
2. 1801 TIC TRIPPED.
GOVERNOR HYDRAULIC PUMP MOTOR OVERHEATED.
DUE TO HI AMBIENT TEMP.
Action Taken to Stop Flaring:
1. Restarted 1801 TIC
2. COOLED DOWN MODULE AND PUT COOLING FAN ON HYDRAULIC PUMP AND MOTOR.
VVednesday,August25,2004
Page 1 of 1
REPORT NO: 04-0346
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 12 Aug 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 03:30 03:40 0 Hrs 10 Mins 0 0 ~ 60 MSCF
TOTAL VOLUME
60 MSCF
First Determination of Cause:
1. normal stop on TIC 1804 for fin fan cleaning.
Action Taken to Stop Flaring:
1. Compressor completed normal blowdown volume.
VVednesday, August25,2004
Page 1 of 1
bp
REPORT NO: 04-0347
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 13 Aug 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 03:30 03:40 0 Hrs 10 Mins D 0 ~ 60 MSCF
TOTAL VOLUME
60 MSCF
First Determination of Cause:
1. Normal stop 1803 for fin fan foam water wash.
Action Taken to Stop Flaring:
1. Foam wash of coolers completed. 1803 return to service.
VVednesday, August 25, 2004
Page 1 of 1
REPORT NO: 04-0361
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 16 Aug 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 11 :55 13:40 1 Hrs 45 Mins D 0 ~ 2,187 MSCF
TOTAL VOLUME 2,187 MSCF
First Determination of Cause:
1. 1803 turbine cool down. Assist gas.
Action Taken to Stop Flaring:
1. 1803 turbine cool down completed.
VVednesday, August25,2004
Page 1 of 1
REPORT NO: 04-0354
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1 DATE: 16 Aug 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Controlled Slowdow 04:27 04:33 OHrs 6 Mins 0 0 ~ 204 MSCF
2. Flare/Relief Valve 09:00 09:10 OHrs 10 Mins 0 0 ~ 60 MSCF
3. Flare/Relief Valve 10:30 10:40 OHrs 10 Mins 0 0 ~ 60 MSCF
4. Flare/Relief Valve 15:15 15:25 OHrs 10 Mins 0 0 ~ 60 MSCF
TOTAL VOLUME 384 MSCF
First Determination of Cause:
1. Depressured B Train Slugcatcher for corroded spool replacemrnt.
2. Normal stopped 1803 Compressor to repair hydraulic system problem.
3. Normal stopped 1803 compressor repair hydraulic system problems.
4. Normal stopped 1803 Compressor to repair hydraulic system problem.
Action Taken to Stop Flaring:
1. Completed depressuring STrain Slugcatcher.
2. Completed flaring after Turbine shutdown.
3. Flaring completed after 1803 normal shutdown.
4. Completed flaring after Turbine shutdown.
VVednesday,August25,2004
Page 1 of 1
REPORT NO: 04-0388
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 20 Aug 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 08:25 19:30 11 Hrs 5 Mins 0 0 ~ 11,336 MSCF
TOTAL VOLUME 11,336 MSCF
First Determination of Cause:
1. Shutdown 1801 TIC to pull the blinds on 1802 TIC.
Action Taken to Stop Flaring:
1. Started 1801 T /C after blinds were pulled.
VVednesday, August 25, 2004
Page 1 of 1
GPB Flaring Incident
To: Steve McMains, AOGCC
steve_mcmains@admin.state.ak.us
907-793-1241, fax 907-276-7542
From: Michael Bolkovatz, GPB Prod Optim Team Leader,
907-659-5566
An extended unplanned flare event occurred on August 6 & 7
at FS1. The 1802 STV/IP compressor was blinded off on
July 31 for a system controls upgrade. The remaining
STV/IP compressor 1801 shutdown on August 6 & 7 due to
high ambient temperatures which caused the compressor to
unload. On August 6, the flare lasted 1 hr, 17 mins (3 events)
and total flared was 1,721 MSCF. On August 7, the flare
lasted 5 hrs, 1 min (2 events) and total flared was 8,049
MSCF.
If you require additional information, please don't hesitate to
call me.
Michael Bolkovatz
GPB Production Optimization TL
659-5566
I of I
8/l0/2004 7:36 AM
~ .
Re)..J l se.-':~ \ 2. - w ,- oi.{
STATE OF ALASKA
ALASKA Oil AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000028
2. Facility Name
PBU FS 1
Disposition
3. Field
PBU - EOA
Volume MCF
6. Sold
o
7. Reinjected
o
8. Flared or vented 1 hour or less
5,872
9. Flared or vented more than 1 hour (see instr.)
5,383
10. Pilot and Purge
25,349
11. Used for lease operations (specify in Remarks)
689,291
12. Other (see instructions)
o
13. TOTAL VOLUME (ITEMS 6-12)
725,895
14. NGL Gas Equivalent
o
15. Purchased gas
o
16. Transferred from: CGF
244,305
17. Transferred to: (Express as a negative #) CCP
-72,123,470
18. Remarks: Block II: Fuel Gas = 667,422 mscf and Assist Gas = 21,869 mscf
4. Operator 5. MonthlYear of Disposition
BP Se tember-2004
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
Pool Name
PRUDHOE
Pool Code
640150
Percent
100.00%
ft-
MCF
MCF
MCF
/-//-oS
Date
Signature,4
Title
\J t> (~ I\C:L,"~fo,ti-
Date ~2. 7..Ð cll
Note: All volumes must be
corrected to pressure of 14.65 psia
and to a temperature of 600 F.
Authorit AAC25.235.
Printed Name
Þe .1.5('">'\
Phone (907)564-5028
Form 10-422 Rev. 1/2004
Submit in Duplicate
Page 1
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT· FS-1
GAS FLARING INCIDENT REPORT
September 2004
REVISED 12-20-2004
Un lanned Events less than or e ual to 1 hour
9/8/2004
9/11/2004
9/16/2004
9/16/2004
9/16/2004
9/18/2004
9/18/2004
9/16/2004
1726-1820
1844-1845
0416-0446
2130-2151
2213-2255
1700-1730
2300-2335
2320-0003
TOTAL
Not required for unplanned events which
are less than or equal to 1 hour
491 Not required for unplanned events which
18 are less than or equal to 1 hour
729
510
1,020
112
1,944
1,045
5,869
Iunplanned Events greater than 1 hour
... . . .D~TE . . . . . · · . . TIME. · . · · . . · '. VOI..UME· ... i:)ESCRIPTION OF INCIDENT & CAUSE ..
9/18/2004 1700-2000 4,375 See attachments
9/18/2004 2200-2345 200
·.··ACTI()N TAKEN TO ELIMINATE CAUSE' . .. .
See attachments
J
TOTAL
4,575
9/8/2004
Planned Events Less Than or E ual1 Hour AND Not Exceedin 5000 Mcf
See attachments
1635-1640
TOTAL
3 See attachments
3
Iplanned Events Exceedin~ 1 Hour OR Exceedin9 5000 Mcf
. ... . . DATE. . . . ... ..... TIME < . . · · · . .V()LUM.E . DESCRIPTION OF INCIDENT & CAUSE · . . . . . · · · · . . . . ACTION TAKEN TO ELIMINATE CAUSE . . .
9/6/2004 0100-0400 808 See attachments See attachments
TOTAL 808
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour 4,575
Planned Events < 1 hour and not 3
exceeding 5,000 MCF
Planned Events> 1 hour or 808
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME 58,473
12/20/2004
2:02 PM
1. Facility Number
0290000028
6. Sold
7. Reinjected
8. Flared or vented 1 hour or less
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
2. Facility Name
PBU FS 1
Disposition
3. Field
PBU - EOA
Volume MCF
o
o
4,827
6,428
10. Pilot and Purge
9. Flared or vented more than 1 hour (see instr.)
25,349
689,291
11. Used for lease operations (specify in Remarks)
12. Other (see instructions)
13. TOTAL VOLUME (ITEMS 6-12)
14. NGL Gas Equivalent
15. Purchased gas
16. Transferred from: CGF
o
725,895
o
o
244,305
17. Transferred to: (Express as a negative #) CCP
-72,123,470
18. Remarks: Block 11: Fuel Gas = 667,422 mscf and Assist Gas = 21,869 mscf
I hereby certify that the foregoing is true and correct to the best of my knowledge.
Signature ß}r~___ ,~
4. Operator 5. Month/Year of Disposition
BP Se tember-2004
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
Pool Name
PRUDHOE
Pool Code
640150
Percent
100.00%
Printed Name
Robert A. Re nolds
Phone (907)564-5028
Title Mana er, State Taxes and Ro aft
Date tc..- ( 8' -6'
Note: All volumes must be
corrected to pressure of 14.65 psia
and to a temperature of 600 F.
Authorit 20 AAC25.235.
Form 10-422 Rev. 1/2004
Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-1
GAS FLARING INCIDENT REPORT
September 2004
lunplanned Events less than or equal to 1 hour
.. . DATE · .. . TIME . . VOLUME . DESCRIPTION Ot=INCIDENT & CAUSE ."
9/8/2004 1726-1820 491 Not required for unplanned events which
9/11/2004 1844-1845 18 are less than or equal to 1 hour
9/16/2004 0416-0446 729
9/16/2004 2130-2151 510
9/16/2004 2213-2255 1,020
9/18/2004 1700-1730 112
9/18/2004 2300-2335 1,944
TOTAL
4,824
~Unplanned Events greater than 1 hour
. . DATE. . . . . . TIME' · . . . VOLUME . DESCRIPTION OF INCIDENT & CAUSE.
9/16/2004 2320-0003 1,045 See attachments
9/18/2004 1700-2000 4,375
9/18/2004 2200-2345 200
TOTAL
5,620
Iplanned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mct
. .'. PATE·.··.·..... . TIME .. . VOLUME··.. DESCRIPTION OF INCIDENT & CAUSE
9/8/2004 1635-1640 3 See attachments
TOTAL
3
Iplanned Events Exceedin~ 1 Hour OR Exceedin~ 5000 Mct
. DATE . . TIME ...... VOLUM.EDESCRIPTIONOFINCIDENT&C~USE
9/6/2004 0100-0400 808 See attachments
TOTAL
808
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
5,620
3
808
TOTAL FLARED VOLUME
58,473
. . . . ACTION .TAKEN TOEI:;IMINATECAUSE. . .
Not required for unplanned events which
are less than or equal to 1 hour
. ACTION TAKEN TO ELIMINATE CAUSE .
See attachments
. .. ACTION TAKEN TO ELIMINATE CAUSE
See attachments
.. .... . ACTION TAKEN TO ELIMINATE CAUSE
See attachments
Page 1
E~
L . '~:'1
;'.-'-~,,") <,C.
1 0/6/2004
10:54 AM
REPORT NO: 04-0408
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 06 Sep 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 01 :00 04:00 3 Hrs 0 Mins 0 0 ~ 808 MSCF
TOTAL VOLUME
808 MSCF
First Determination of Cause:
1. Depressured 12-8 and 12-C commonlines for maintenance.
Action Taken to Stop Flaring:
1. Stopped flaring when depressured.
Monday, September 27,2004
Page 1 of 1
REPORT NO: 04-0414
BPXA FLARE REPORT
PRUDHOE BAY'
FACILITY: FS1 DATE: 08 Sep 2004
TIME OF FLARING
SYSTEM Start Stop Duration Intermittent
1. FlarelRelief Valve 16:35 16:40 0 Hrs 5 Mins 0
2. Flare/Relief Valve 17:26 18:20 0 Hrs 54 Mins ~
Black
Smoke Planned VOLUME
0 ~ 3 MSCF
0 0 491 MSCF
TOTAL VOLUME 494 MSCF
First Determination of Cause:
1. 1801 SHUTDOWN FOR BOROSCOPE. NORMAL SID FLARE TO DEPRESSURE CASES.
2. 1802 STV CASE WOULDN'T HOLD THE LOAD. DISCHARGE PRESSURE HI.
Action Taken to Stop Flaring:
1. CASE DEPRESSURING COMPLETED.
2. INSTR. ADJUSTED THE lIP SUCTION PRESSURE AND STV REMAINED LOADED.
Monday, September 27,2004
Page 1 of 1
REPORT NO: 04-0447
BPXA FLARE REPORT
PRUDHOE SAY
FACILITY: FS1 DATE: 16 Sep 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 04:16 04:46 OHrs 30 Mins 0 0 0 729 MSCF
2. Flare/Relief Valve 21:30 21:51 OHrs 21 Mins 0 0 0 510 MSCF
3. Flare/Relief Valve 22:13 22:55 OHrs 42 Mins 0 0 0 1,020 MSCF
4. FlarelRelief Valve 23:20 00:03 ~01 Hrs 43 Mins 0 0 0 1,045 MSCF
TOTAL VOLUME 3,304 MSCF
First Determination of Cause:
1. 1802 TIC unloaded.
2. 1802 TIC unloaded.
3. 1802 TIC unloaded.
4. 1802 TIC unloaded.
Action Taken to Stop Flaring:
1. 1802 TIC took the load, off flare.
2. 1802 TIC took the load, off flare.
3. 1802 TIC took the load, off flare.
4. Started and loaded 1801 TIC.
Monday, September 27,2004
Page 1 of 1
REPORT NO: 04-0451
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1 DATE: 18 Sep 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 17:00 20:00 3Hrs OMins 0 0 0 4,375 MSCF
2. Flare/Relief Valve 17:00 17:30 OHrs 30 Mins 0 0 0 112 MSCF
3. Flare/Relief Valve 22:00 23:45 1 Hrs 45 Mins ~ 0 0 200 MSCF
4. Flare/Relief Valve 23:00 23:35 OHrs 35 Mins 0 0 0 1,944 MSCF
TOTAL VOLUME 6,631 MSCF
First Determination of Cause:
1. Power failure caused 1801 TIC to shutdown.
2. Power failure caused 1803 & 1804 TICs to shutdown, flared gas off slugcatchers.
3. Five aborted starts on 1804 TIC.
4. Flared off slugcatchers: more rate than 1803 TIC could handle.
Action Taken to Stop Flaring:
1. Restarted TIC.
2. LPS commonlines also OSD'd, shutting in LPS production.
3. 1804 TIC started on the 6th try.
4. Shut in wells 1-6 & 1-10 for rate cut.
Monday, September 27, 2004
Page 1 of 1
Gas Disposition
Gary,
Last month I email you about some additional data for some facility high volumes.
I haven't heard from you on these GC-3 and 2 request about GPMA.
Sept 2004, I found 1 event at FS-t on Sept 16 that I think is an error, it is only
43 minutes.
Steve
R 'i--\ll\ S ~ at
1= (J~m
S~n(
J ofl
10/28/2004 1 :28 PM
STATE OF ALASKA
ALASKA Oil AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000028
2. Facility Name
PBU FS 1
Disposition
3. Field
PBU - EOA
Volume MCF
4. Operator 5. Month/Year of Disposition
BP October-2004
20. For production from multiple pools, list contribution of each pool as a percent of
Total Volume.
6. Sold
o
Pool Name
PRUDHOE
Pool Code
640150
Percent
100.00%
7. Reinjected
o
8. Flared or vented 1 hour or less
1,421
9. Flared or vented more than 1 hour (see instr.)
3,894
10. Pilot and Purge
26,268
11. Used for lease operations (specify in Remarks)
743,367
14. NGL Gas Equivalent
o
12. Other (see instructions)
o
13. TOTAL VOLUME (ITEMS 6-12)
774,950
15. Purchased gas
o
16. Transferred from: CGF
277,969
17. Transferred to: (Express as a negative #) CGF
-73,137,705
18. Remarks: Block 11: Fuel Gas = 728,485 mscf and Assist Gas = 14,882 mscf
I hereby certify that the foregoing is true and correct to the best of my knowledge.
Signature ,~~ +w-
Printed Name ~'n
Title Mana er, Production Taxes and Ro alt
Note: All volumes must be
corrected to pressure of 14.65 psia
and to a temperature of 600 F.
Authorit 20 AAC25.235.
Phone (907)564-5028
Form 10-422 Rev. 1/2004
Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-1
GAS FLARING INCIDENT REPORT
October 2004
¡unplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
10/4/2004 0950-0951 4 Not required for unplanned events which
10/4/2004 0953-0955 7 are less than or equal to 1 hour
10/4/2004 1451-1501 28
10/14/2004 0927-0929 18
10/14/2004 0932-0937 45
Page 1
TOTAL
102
~Unplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
See attachments
TOTAL
o
¡Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Met
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
10/4/2004 1030-1035 3 See attachments
10/18/2004 1840-1930 521
10/18/2004 2230-2235 40
10/18/2004 0030-0035 60
10/18/2004 0420-0520 107
10/18/2004 1032-1115 448
10/18/2004 1214-1219 40
10/18/2004 1303-1308 40
10/18/2004 1400-1405 60
TOTAL
1,319
¡Planned Events Exceeding 1 Hour OR Exceedin9 5000 Met
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
10/18/2004 2100-2230 143 See attachments
10/18/2004 0200-0530 2,188
10/18/2004 1438-1708 1 ,563
TOTAL 3,894
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
o
1,319
3,894
46,465
ACTION TAKEN TO ELIMINATE CAuse
Not required for unplanned events which
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSe
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
11/9/2004
10:58 AM
bp
REPORT NO: 04-0482
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1 DATE: 04 Oct 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Flare/Relief Valve 09:50 09:51 OHrs 1 Mins 0 0 0 4 MSCF
2. FlarelRelief Valve 09:53 09:55 OHrs 2 Mins D D 0 7 MSCF
3. Flare/Relief Valve 10:30 10:35 OHrs 5Mins D 0 ~ 3 MSCF
4. FlarelRelief Valve 14:51 15:01 OHrs 10 Mins ~ 0 0 28 MSCF
TOTAL VOLUME 42 MSCF
First Determination of Cause:
1. Loading 1802 T/C, adjusting speed and recycle controller to get machine to take the load; flaring of
STV sucton scrubber.
2. Loading 1802 T/C, adjusting speed and recycle controller to get machine to take the load; flaring of
STY sucton scrubber.
3. 1801 TIC normal stop.
4. 1802 T /C lost load.
Action Taken to Stop Flaring:
1. 1802 TIC took load.
2. 1802 TIC took load.
3. 1801 depressured after normal stop.
4. Adjusted speed; 1802 TIC took load.
Friday, October 22, 2004
Page 1 of 1
REPORT NO: 04-0510
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 18 Oct 2004
SYSTEM
1. Other
2. Controlled Blowdow
3. Controlled Blowdow
TIME OF FLARING Black
Start Stop Duration Intermittent Smoke Planned VOLUME
18:40 19:30 OHrs 50 Mins 0 0 ~ 521 MSCF
21:00 22:30 1 Hrs 30 Mins 0 0 ~ 143 MSCF
22:30 22:35 OHrs 5Mins 0 0 ~ 40 MSCF
TOTAL VOLUME 704 MSCF
First Determination of Cause:
1. 1803 TIC spin for water wash.
2. Depressure 1 C Commonline for maintenance.
3. Normal start of 1803 TIC, purge volume.
Action Taken to Stop Flaring:
1. 1803 T /C spin for water wash completed.
2. Completed depressure of 1 C commonline.
3. 1803 TIC online.
Friday, October 22, 2004
Page 1 of 1
bp
REPORT NO: 04-0506
BPXA FLARE REPORT
PRUDHOE BA V
FACILITY: FS1 DATE: 18 Oct 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. Controlled Blowdow 00:30 00:35 OHrs 5Mins 0 0 ~ 60 MSCF
2. Other 02:00 05:30 3Hrs 30 Mins 0 0 ~ 2,188 MSCF
3. Controlled Blowdow 04:20 05:20 1 Hrs OMins 0 0 ~ 107 MSCF
4. Other 10:32 11 :15 OHrs 43 Mins 0 0 ~ 448 MSCF
5. Controlled Blowdow 12:14 12:19 OHrs 5Mins 0 0 ~ 40 MSCF
6. Controlled Blowdow 13:03 13:08 OHrs 5Mins 0 0 ~ 40 MSCF
7. Flare/Relief Valve 14:00 14:05 OHrs 5Mins 0 D ~ 60 MSCF
8. Other 14:38 17:08 2Hrs 30 Mins D 0 ~ 1 ,563 MSCF
TOTAL VOLUME 4,506 MSCF
First Determination of Cause:
1. Normal stop Slowdown on 1804 TIC
2. 1804 TIC spin cool down for Water Wash.
3. Depessure 2C Commonline for Maintenance.
4. 1804 TIC spin for Water Wash.
5. Attemted start of 1804 TIC, purge volume.
6. Start of 1804 TIC, purge volume.
7. Normal stop of 1803 TIC.
8. 1803 TIC spin cool down for Water Wash.
Action Taken to Stop Flaring:
1. Completed normal stop Slowdown on 1804 TIC.
2. Completed Spin Cool Down.
Friday, October 22, 2004
Page 1 of 2
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 18 Oct 2004
3 _% Completed Depressure of 2C Common line
f y 1804 TIC spin for Water Wash completed.
{' JZ" Aborted start of 1804 TIC.
b ).8':" 1804 TIC started, purge completed.
7 11C Normal stop of 1803 TIC completed.
<jJ .:J« Completed Spin Cool Down.
Friday, October 22,2004
REPORT NO: 04-0506
Page 2 of 2
· ~
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000028
2. Facility Name
PBU FS 1
Disposition
3. Field
PBU - EOA
Volume MCF
6. Sold
o
7. Reinjected
o
8. Flared or vented 1 hour or less
9,387
9. Flared or vented more than 1 hour (see instr.)
8,749
10. Pilot and Purge
25,612
11. Used for lease operations (specify in Remarks)
780,417
12. Other (see instructions)
o
13. TOTAL VOLUME (ITEMS 6-12)
824,165
14. NGL Gas Equivalent
o
15. Purchased gas
o
16. Transferred from: CGF
278,572
17. Transferred to: (Express as a negative #) CGF
-77 ,243,153
18. Remarks: Block 11: Fuel Gas = 767,236 mscf and Assist Gas = 13,181 mscf
I 000::: .,~ ::",=7;Z;' 00" ro ~ kMMOO~
Printed Name ~ernard W. Ha'n7
4. Operator 5. Month/Year of Disposition
BP November-2004
20. For production from multiple pools. list contribution of each pool as a percent of
Total Volume.
Pool Name
PRUDHOE
Pool Code
640150
Percent
100.00%
5u-
MCF
MCF
MCF
/-//-ð6
Date
Phone (907)564-5028
Title Mana er, Production Taxes and Ro alt
Date
Note: All volumes must be
corrected to pressure of 14.65 psia
and to a temperature of 600 F.
Authorit 20 AAC25.235.
Form 10-422 Rev. 1/2004
--âY
Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - FS-1
GAS FLARING INCIDENT REPORT
November 2004
Page 1
11/3/2004
11/3/2004
11/3/2004
0415-0500
0714-0716
0838-0840
9,375 Not required for unplanned events which
6 are less than or equal to 1 hour
6
Not required for unplanned events which
are less than or equal to 1 hour
TOTAL
9,387
See attachments
See attachments
TOTAL
o
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf
See attachments
See attachments
TOTAL
o
Iplanned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
11/7/2004 1210-1313 8,749 See attachments
ACTION TAKEN TO ELIMINATE CAUSE
See attachments
TOTAL
8,749
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
o
o
8,749
56,929
12/6/2004
4:07 PM
bp
REPORT NO: 04-0530
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 07 Nav 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration Intermittent Smoke Planned VOLUME
1. FlarelRelief Valve 12:10 13:13 1 Hrs 3Mins 0 0 ~ 8,749 MSCF
TOTAL VOLUME 8,749 MSCF
First Determination of Cause:
1. Reguested to flare from the the Annex per E.O.C. due to a TIC trip at C.G.F..
Action Taken to Stop Flaring:
1. Tandem Compressor at C.G.F returned to service. S/I flare from Annex.
Monday, November 22, 2004
Page 1 of 1
"
STATE OF ALASKA
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
1. Facility Number
0290000028
2. Facility Name
PBU FS 1
Disposition
6. Sold
7. Reinjected
8. Flared or vented 1 hour or less
9. Flared or vented more than 1 hour (see instr.)
10. Pilot and Purge
11. Used for lease operations (specify in Remarks)
12. Other (see instructions)
13. TOTAL VOLUME (ITEMS 6-12)
14. NGL Gas Equivalent
15. Purchased gas
16. Transferred from: CGF
17. Transferred to: (Express as a negative #) CGF
18. Remarks: Block 11: Fuel Gas = 828,752 mscf and Assist Gas = 9,905 mscf
Signature
Printed Name
Form 10-422 Rev. 1/2004
3. Field
PBU-EOA
Volume MCF
o
o
293
1,978
26,434
838,657
o
867,362
o
o
301,093
-81,759,413
4. Operator 5. MonthlYear of Disposition
BP December-2004
20. For production from multiple pools. list contribution of each pool as a percent of
Total Volume.
Pool Name
PRUDHOE
Pool Code
640150
Percent
100.00%
~
Phone (907)564-5028
Title Mana er, Production Taxes and Ro alt
Date
- //- (',') \'
7' -<"
Note: All volumes must be
corrected to pressure of 14.65 psia
and to a temperature of 600 F.
Authorit 20 MC25.235.
Submit in Duplicate
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - F8-1
GAS FLARING INCIDENT REPORT
December 2004
Page 1
12/18/2004
12/1812004
12/20/2004
1816-1821
2205-2210
1401-1429
3 Not required for unplanned events which
3 are less than or equal to 1 hour
272
Not required for unplanned events which
are less than or equal to 1 hour
TOTAL
278
Unplanned Events greater than 1 hour
12/16/2004
1540-1730
1 ,978 See attachments
See attachments
TOTAL
1,978
Planned Events Less Than or Equal 1 Hour AND Not Exceedin
12/17/2004 0830-0835 3 See attachments See attachments
12/17/2004 1400-1405 3
12/17/2004 1630-1635 3
12/19/2004 1205-1210 3
12/19/2004 1810-1815 3
TOTAL 15
See attachments
See attachments
TOTAL
o
Unplanned Events < 1 Hour
Unplanned Events> 1 Hour
Planned Events < 1 hour and not
exceeding 5,000 MCF
Planned Events> 1 hour or
exceeding 5,000 MCF
Pilot Purge
Assist
TOTAL FLARED VOLUME
1,978
15
o
38,610
1/10/2005
3:27 PM
GPB Flaring Incident
To: Steve McMains, AOGCC
steve _mcmains@admin.state.ak.us
907-793-1241, fax 907-276-7542
From: Michael Bolkovatz, GPB Prod Optim Team Leader, 907-659-5566
An extended flaring event occurred 12/16 at FS-1. Turbine Compressor 1801 quit
running due to a main lube oil pressure problem. The backup compressor, 1802 was
started as quickly as possible. No attempts were made to reduce flaring (ie; SI
production) since weather conditions were -10 deg and Phase II visibility. Flaring
occurred over 1 hr, 50 mins and a total volume of 1978 MSCF was flared.
If you require additional information, please don't hesitate to call me.
Michael Bolkovatz
GPB Production Optimization TL
659-5566
I of 1
12/17/20049:04 AM
bp
FACILITY: FS1
SYSTEM
1. Flare/Relief Valve
BPXA FLARE REPORT
PRUDHOE BAY
DATE: 16 Dec 2004
TIME OF FLARING Black
Start Stop Duration Intermittent Smoke
15:40 17:30 1 Hrs 50Mins ~ 0
REPORT NO: 04-0557
Planned VOLUME
o 1,978 MSCF
TOTAL VOLUME 1,978 MSCF
First Determination of Cause:
1. Turbine 1801 dropped off line due to a main lube oil pressure problem.
Action Taken to Stop Flaring:
1. Turbine I Compressor 1802 started and loaded.
Tuesday, December 21,2004
Page 1 of 1
REPORT NO: 04-0558
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1 DATE: 17 Dee 2004
TIME OF FLARING Black
SYSTEM Start Stop Duration I nterm ittent Smoke Planned VOLUME
1. Flare/Relief Valve 08:30 08:35 OHrs 5Mins 0 0 ~ 3 MSCF
2. Flare/Relief Valve 14:00 14:05 OHrs 5Mins 0 0 ~ 3 MSCF
3. Flare/Relief Valve 16:30 16:35 OHrs 5Mins 0 0 ~ 3 MSCF
TOTAL VOLUME 9 MSCF
First Determination of Cause:
1. shut down TIC 1802 to load TIC 1801
2. Shut Down TIC 1801 to load TIC 1802
3. Shut down TIC 1802 to load TIC 1801
Action Taken to Stop Flaring:
1. Loaded TIC 1801
2. Loaded TIC 1802
3. Loaded IC 1801
Tuesday. December 21. 2004
Page 1 of 1
bp
REPORT NO: 04-0564
BPXA FLARE REPORT
PRUDHOE BAY
FACILITY: FS1
DATE: 19 Dee 2004
SYSTEM
1. Flare/Relief Valve
2. Flare/Relief Valve
TIME OF FLARING Black
Start Stop Duration Intermittent Smoke Planned VOLUME
12:05 12:10 OHrs 5Mins 0 0 ~ 3 MSCF
18:10 18:15 OHrs 5Mins 0 0 ~ 3 MSCF
TOTAL VOLUME 6 MSCF
First Determination of Cause:
1. TIC 1802 Shut down for maintenance
2. TIC 1801 Shut down to bring TIC 1802 on-line.
Action Taken to Stop Flaring:
1. Start TIC 1801
2. Start TIC 1802