ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Facility Operator Field(s) Month/Year of Disposition
GATHERING CENTER 3 BP EXPLORATION ALASKA WESTERN OPERATING AREA-PB Dec-96
Disposition
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour 19,719
4. Flared or vented greater than 1 hour
(Supplemental report required--See 20 AAC 25.235) 14,344
5. Pilot and Purge 14,736
6. Used for lease operations 715,653
7.Other 0
TOTAL items 1- 7 764,452
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 26,485,868
Remarks:
I hereby certify that th foreQOinQ is true and correct to the best of my knowledge.
Signature: ~ ~?,~,.~.~c.--, Title: SUPERVISOR
~
-"
Form 10-422
(R
evised 4/95)
~ ~ ~ ~~
*Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100
Note: All volumes must be corrected to
pressure of 14.65 psia and to a temperature of
60 degrees F. Report due by the 20th of the
month following the month of disposition.
Authority 20 AAC 25.235.
•
•
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT-GC-3
GAS FLARING INCIDENT REPORT
DECEMBER, 1996
LUnplanned Events less than or equal to 1 hour ~
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO"ELIMINATE CAUSE
12/1/96 0054-0139 563 Not required for unplanned events which Not required for unplanned events which
12/1/96 0450-0514 133 are less than or equal to 1 hour are less than or equal to 1 hour
12/1 /96 2140-2227 359
12/2/96 1659-1729 208
12/3/96 1900-1943 4,479
12/7/96 1957-2016 158
12/14/96 2121-2220 4,097
12/17/96 1105-1154 222
12/17/96 1652-1710 388
12/18/96 1537-1559 229
12/22/96 0058-0105 49
12/30/96 1241-1334 773
12/30/96 1518-1607 715
12/31 /96 0027-0105 1,135
12/31/96 0105-0156 5,667
12/31 /96 0427-0456 544
TOTAL 19,719
Unplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN 70 ELIMINATE CAUSE
12/14/96 0831-0939 52 See Attachments See Attachments
12/17/96 0818-0953 542 See Attachments See Attachments
12/30/96 2140-2330 13,750 See Attachments See Attachments
TOTAL 14,344
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf ~
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ' ACTION TAKEN TO ELIMINATE GAUSE
TOTAL 0
Planned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE A "hF~TE CAUSE
TOTAL 0 ~ ~
~ ~: 1997
~~~~ AiB ~ Gas C~n~. ~ar~~mi~si~n
Arlch~rag~
Page 1
BP EXPLORATION (ALASKA) INC. Page 2
PRUDHOE BAY UNIT - GC-3
GAS FLARING INCIDENT REPORT
DECEMBER, 1996
TOTAL
Unplanned Events < 1 Hour 19, 719
Unplanned Events > 1 Hour 14,344
Planned Events < 1 hour & not
exceeding 5,000 MCF
Planned Events > 1 hour and
exceeding 5,000 MCF
• Pilot Purge 14.736
TOTAL FLARED VOLUME 48,799
U
• •
REPORT NO: 96-S6O~
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 14 DeC 96 TOTAL VOLUME: 4,149 MSCF
Intermittent Black
TIME OF F LARING: DURATION: Yes No Smoke? Planned? VOLUME
1. FROM: 0$:31 To: 09:39 1 Hrs. 8 Mins. X^ ^ ^ ^ 52 MSCF
2. FROM: 21:21 TO: 22:20 0 Hrs. 59 Mins. ^ Q ^ ^ 4,097 MSCF
3. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
4. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
5. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:
First Determination of Cause:
1. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
4°F.
2. Asset Area TEG regeneration system shut down because of control/intrumentation failure associated with Skid 20 low
gas alarm (lost fuel gas)
3.
4.
5.
Action Taken to Stop Flaring:
1. BPX reduced production rates and shut-in 1 wells equaling 21 mmcfd. ARCO reduced production rates and shut-in 4
wells equaling 93 mmcfd. Wells were shut-in or choked back starting at 0844 hours.
2. BPX reduced production rates and shut-in 6 wells equaling 100 mmcfd. Wells were shut-in or choked back starting at
21:27 hours.
3.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No: _
AOGCC Representative: Date: BPX Representative: Date:
• •
REPORT NO: 9G-3614
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-$ DATE: 17 DeC 96 TOTAL VOLUME: 1,152 MSCF
Intermittent Black
TIME OF F LARING: DURATION: Yes No Smoke? Planned? VOLUME
1. FROM: 08:18 To: 09:53 1 Hrs. 35 Mins. Q ^ ^ ^ 542 MSCF
2. FROM: 11:05 TO: 11:54 0 Hrs. 49 Mins. Q ^ ^ ^ 222 MSCF
3. FROM: 16:52 TO: 17:10 0 Hrs. 18 Mins. ^ Q ^ ^ 388 MSCF
4. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
5. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
9°F.
2. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
2°F.
3. High gas transit line pressure caused by CGF compressor problems due to tandem #4 SD on high discharge pressure.
4.
5.
Action Taken to Stop Flaring:
1. ARCO reduced production rates and shut-in 4 wells equaling 100 mmcfd. Wells were shut-in or choked back starting at
0856 hours.
2. Arco reduced production rates and shut-in 2 wells equaling 80 mmcfd. Wells were shut-in or choked back starting at
1104 hours.
3. BPX reduced production rates and shut-in 5 wells equaling 150 mmcfd. ARCO reduced production rates and shut-in
10wells equaling 300 mmcfd. Wells were shut-in or choked back starting at 1653 hours.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No: _
AOGCC Representative: Date: BPX Representative: Date:
• • b
REPORT NO: 96-$627
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 30 Dec 96 TOTAL VOLUME: 15,28$ MSCF
Intermittent Black
TIME OF F LARING: DURA TION: Yes No Smoke? Planned? VOLUME
1. FROM: 12:41 TO: 13:34 0 Hrs. 53 Mins. ^ Q ^ ^ 773 MSCF
2. FROM: 15:1$ TO: 16:07 0 Hrs. 49 Mins. ^ Q ^ ^ 715 MSCF
3. FROM: 21:40 TO: 23:30 1 Hrs. 50 Mins. ^ Q ^ ^ 13,750 MSCF
4. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
5. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. While bringing cycle wells on production, gas rates went up causing high gas transit pressure.
2, While bringing cycle wells on production, gas rates went up causing high gas transit pressure.
3. Asset Area TEG regeneration system shut down because of control/intrumentation failure associated high gas alarm.
4.
5.
Action Taken to Stop Flaring:
1. BPX reduced production rates equaling 35 mmcfd. ARCO reduced production rates equaling 50 mmcfd. Wells were
shut-in or choked back starting at 12:50 hours.
2. BPX reduced production rates equaling 58 mmcfd. ARCO reduced production rates equaling 60 mmcfd. Wells were
shut-in or choked back starting at 15:28 hours.
3. BPX reduced production rates and shut-in 11 wells equaling 310 mmcfd. Wells were shut-in or choked back starting at
2140 hours. Fire alarm technition reset alarms.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No: -
AOGCC Representative: Date: BPX Representative: Date:
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Facility Operator Field(s) Month/Year of Disposition
GATIiERING CF:NTI;R 3 BP r,XPI.ORATION ALASKA WFSITR.N ()PERA.TING ARIiA-PB Nav-96
Disposition
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour x,232
4. Flared or vented greater than 1 hour
(Su plemental re ort required--See 20 AAC 25.235) 4,227
5. Pilot and Purge 13,276
6. Used for lease operations 688,368
7.Other 0
TOTAL items 1- 7 715,103
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 25,698,401
Remarks:
I hereby certif~~ that the resoins is true and correct to the best of my knowledge.
Signature: ~:.1r1 Title: SUPERVISOR
f,
Form 10-422 (Revised 4/95)
*Indicate contribution of each pool to total.
Pool Name Code Percent
PRiJDIiOE Cr~0I50 1.00
Official Use Onl --Flarin Authorization > 1 hr.
1. Safety MCF
2. Lease Use MCF
3. Conserv. Purposes MCF
Commissioner Date
Note: All volumes must be corrected to
pressure of 14.65 psia and to a temperature of
60 degrees F. Report due by the 20th of the
month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-3
GAS FLARING INCIDENT REPORT
NOVEMBER, 1996
Unplanned Events less than or equal to 1 hour ~
~_~.~,
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
11/6/96 0400-0415 677 Not required for unplanned events which Not required for unplanned events which
11/7/96 2054-2107 90 are less than or equal to 1 hour are less than or equal to 1 hour
11 /8/96 1014-1040 451
11 /11 /96 1032-1123 531
11 /14/96 0425-0438 90
11 /15/96 1634-1646 250
11 /15/96 2104-2200 739
11 /16/96 0106-0141 304
11 /16/96 0515-0603 600
11/17/96 0950-1004 243
11 /17/96 1311-1352 712
11 /17/96 2103-2109 821
11 /22/96 0641-0700 198
11 /23/96 0119-0153 63
11 /25/96 1318-1349 2,497
11 /26/96 1631-1654 351
11 /26/96 1932-2013 188
11 /27/96 0211-0216 52
11 /30/96 0711-0738 375
TOTAL 9,232
Unplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT &
11/15/96 0849-1037 2,250 See Attachments
• 11/15/96 1756-2005 1,068 See Attachments
11/16/96 1749-1855 871 See Attachments
11/22/96 2046-2219 38 See Attachments
TOTAL
4,227
ACTION TAKEN TO
See Attachments
See Attachments
See Attachments
See Attachments
ELIMINATE CAUSE
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
TOTAL 0
Planned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
TOTAL 0
Page 1
TOTAL
Unplanned Events < 1 Hour 9,232
Unplanned Events > 1 Hour 4,227
Planned Events < 1 hour & not 0
exceeding 5,000 MCF
Planned Events > 1 hour and 0
exceeding 5,000 MCF
Pilot Purge 13.276
TOTAL FLARED VOLUME 26, 735
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-3
GAS FLARING INCIDENT REPORT
NOVEMBER, 1996
Page 2
REPORT NO: 96-3559.
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 15 NOV 96
TIME OF FLARING:
1. FROM: 08:49 To: 10:37
2. FROM: 16:34 To: 16:46
3. FROM: 17:56 To: 20:05
4. FROM: 21:04 To: 22:00
5. FROM: TO:
DURATION:
1 Hrs. 48 Mins.
0 Hrs. 12 Mins.
2 Hrs. 9 Mins.
0 Hrs. 56 Mins.
Hrs. Mins.
Intermittent
Yes No
^ X^
^ 0
a^
^ ^
TOTAL VOLUME:
Black
Smoke? Planned?
^ ^
^ ^
^ ^
^ ^
^ ^
4,307 MscF
VOLUME
2,250 MscF
250 MSCF
1,068 MSCF
739 MSCF
MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. High gas transit line pressure caused by CCP compressor #1876 Tandem shutdown due to an inverter problem.
2. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
6°F.
3. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
7°F.
4. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
8°F.
5.
Action Taken to Stop Flaring:
1. Arco reduced production rates and shut-in wells equaling 220mmcfd. Wells were shut-in or choked back starting at
08:50 hours.
2. BPX reduced production rates wells were choked back equaling 60 mmcfd. ARCO reduced production rates 2 wells
equaling 80 mmcfd. Wells were shut-in or choked back starting at15:10 hours.
3. BPX reduced production rates and shut-in 3 wells equaling 46 mmcfd. ARCO reduced production rates and shut-in 9
wells equaling 130 mmcfd. Wells were shut-in or choked back starting at 1800 hours.
4. BPX reduced production rates and shut-in 2 wells equaling 80 mmcfd. ARCO reduced production rates and shut-in 4
wells equaling 90 mmcfd. Wells were shut-in or choked back starting at 2208 hours.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
! !
REPORT NO: 9G-3561
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 16 Nov 96
TOTAL VOLUME: 1 ,775 MSCF
Intermittent Black
TIME OF F LARING: DURATION: Yes No Smoke? Planned? VOLUME
1. FROM: 01:06 TO: 01:41 0 Hrs. 35 Mins. ^ Q ^ ^ 304 MSCF
2. FROM: 05:15 TO: 06:03 0 Hrs. 48 Mins. ^ Q ^ ^ 600 MSCF
3. FROM: 17:49 TO: 1$:55 1 Hrs. 6 Mins. ^ Q ^ ^ 871 MSCF
4. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
5. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
6°F.
2. High gas transit line pressure caused by CGF putting LTS #3 unit on line and switching gas loads from the two otherLTS
units.
3. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
7°F.
4.
5.
Action Taken to Stop Flaring:
1. BPX reduced production rates and shut-in 1 wells equaling 37 mmcfd. ARCO reduced production rates and shut-in 2
wells equaling 90 mmcfd. Wells were shut-in or choked back starting at 0115 hours.
2. Arco reduced production rates and shut-in 2 wells equaling 60 mmcfd. Wells were shut-in or choked back starting at
0545 hours.
3. BPX reduced production rates and shut-in 3 wells equaling 49 mmcfd. ARCO reduced production rates and shut-in 6
wells equaling 100 mmcfd. Wells were shut-in or choked back starting at 1745 hours.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
REPORT NO: 96-3577
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 22 Nov 96
TIME OF FLARING:
1. FROM: 06:41 To: 07:00
2. FROM: 20:46 To: 22:19
3. FROM: TO:
4. FROM: TO:
5. FROM: TO:
DURATION:
O Hrs. 19 Mins
1 Hrs. 33 Mins
Hrs. Mins
Hrs. Mins
Hrs. Mins
TOTAL VOLUME: 236 MSCF
Intermittent Black
Yes No Smoke? Planned? VOLUME
^ Q ^ ^ 198 MSCF
0 ^ ^ ^ 38 MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
3°F.
2. LPS compressor K-7001 shut down for maintenance repairs
3.
4.
5.
Action Taken to Stop Flaring:
1. Arco reduced production rates and shut-in 4 wells equaling 130 mmcfd. Wells were shut-in or choked back starting at
06:25 hours.
2. BPX reduced production rates using 1 well equaling 36 mmcfd. Wells were shut-in or choked back starting at
22:00hours.
3.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: No: _
AOGCC Representative: Date: BPX Representative: Date:
n
•
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Facility Operator Field(s) Month/Year of Disposition
GATHERING CENTER 3 BP EXPLORATION ALASKA WESTERN OPERATING AREA-PB Oct-96
Disposition *Indicate contribution of each pool to total.
1. Sold 0 Pool Name Code Percent
2. Reinjected 0 PRUDHOE 640150 100
3. Flared or vented less than 1 hour 2,710
4. Flared or vented greater than 1 hour 3,369
(Sup lemental report required--See 20 AAC 25.235)
5. Pilot and Purge 17,635
6. Used for lease operations 611,492
11. Transferred to: CCP 24,875,974
7.Other 0
TOTAL items 1 - 7 635,206
8. NGL Qas equivalent produced 0
9. Purchased Qas 0
10. Transferred from: 0
Note: All volumes must be corrected to
pressure of 14.65 psis and to a temperature of
60 degrees F. Report due by the 20th of the
month following the month of disposition.
Authority 20 AAC 25.235.
Form 10-422 (Revised 4 95)
Remarks:
I hereby certify a eeoing is true and correct to the best of my knowledse.
Signature: itle: SUPERVISOR
,~
planned Events less than or
DATE TIME
10/12/96 1223-1310
10/13/96 0611-0659
10/17/96 1755-1813
10/18/96 1251-1322
10/21 /96 1003-1037
10/26/96 0105-0155
10/28/96 1632-1702
_
TOTAL
2,710
DATE TIME VOLUME DESCRIPTION 4F INCIDENT & CAUSE
10/13/96 1638-1756 278 See Attachments
10/18/96 1951-2103 413 See Attachments
10/22/96 0445-1946 2,678 See Attachments
TOTAL 3,369
c Page 1
D E
_
W m
m
m
.--
t%f
~~
-- - 1`rJ p '4
~~
ACTION TAKEN TO ELIMINATE CAUSE ~ 6
Not required for unplanned events v~i o
are less than or equal to 1 hour ~
Z ~
-
o_
a
ACTION TAKEN TO ELiM#NATE CAUSE
See Attachments
See Attachments
See Attachments
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf ~
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-3
GAS FLARING INCIDENT REPORT
OCTOBER, 1996
equal to 1 hour
VOLUME DESCRfPT#ON OF INCIDENT & CAUSE
375 Not required for unplanned events which
385 are less than or equal to 1 hour
142
431
472
655
250
TOTAL
0
Planned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
TOTAL 0
TOTAL
Unplanned Events < 1 Hour 2,710
Unplanned Events > 1 Hour 3,369
Planned Events < 1 hour & not 0
exceeding 5,000 MCF
Planned Events > 1 hour and 0
exceeding 5,000 MCF
Pilot Purge 17.635
TOTAL FLARED VOLUME 23,714
•
REPORT NO: 9G-3520
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-$ DATE: 13 OCt 96
TIME OF FLARING:
1. FROM: 06:11 To: 06:59
2. FROM: 16:38 To: 17:56
3. FROM: TO:
4. FROM: TO:
5. FROM: TO:
DURATION:
0 Hrs. 48 Mins.
1 Hrs. 18 Mins.
Hrs. Mins.
Hrs. Mins.
Hrs. Mins.
TOTAL VOLUME: 663 MSCF
Intermittent Black
Yes No Smoke? Planned? VOLUME
D ^ ^ ^ 385 MSCF
X^ ^ ^ ^ 278 MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
6°F.
2. During pigging operations gas rates fluxuated causing the LPS compresors to reach maximum gas capacity .
3.
4.
5.
Action Taken to Stop Flaring:
1. BPX reduced production rates and shut-in 1 wells equaling 42 mmcfd. ARCO reduced production rates and shut-in 3
wells equaling 50 mmcfd. Wells were shut-in or choked back starting at 06:40hours.
2. BPX stopped bringing production rates up until wells unloaded and flaring was ceased.
3.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: , No: _
AOGCC Representative: Date: BPX Representative: Date:
REPORT NO: 96-3526
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 18 Oct 96
TOTAL VOLUME: 84.4 MSCF
Intermittent Black
TIME OF FLARING: DURATION: Yes No Smoke? Planned? VOLUME
1. FROM: 12:51 To: 13:22 0 Hrs. 31 Mins. ^ X^ ^ ^ 431 MSCF
2. FROM: 19:51 TO: 21:03 1 Hrs. 12 Mins. Q ^ ^ ^ 413 MSCF
3. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
4. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
5. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
7 °F.
2. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
4°F.
3.
4.
5.
Action Taken to Stop Flaring:
1. BPX reduced production rates and shut-in 2 wells equaling 30 mmcfd. ARCO reduced production rates and shut-in 5
wells equaling130 mmcfd. Wells were shut-in or choked back starting at 13:00 hours.
2. BPX reduced production rates and shut-iniwell equaling 36 mmcfd. ARCO reduced production rates and shut-in 2
wells equaling 60 mmcfd. Wells were shut-in or choked back starting at 2010 hours.
3.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: No:
AOGCC Representative: Date: BPX Representative: Date:
REPORT NO: 96-3533
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 22 Oct 96
TIME OF FLARING: DURATION:
1. FROM: 04:45 TO: 19:46 15 Hrs. 1 Mins.
2. FROM: TO: Hrs. Mins.
3. FROM: TO: Hrs. Mins.
4. FROM: TO: Hrs. Mins.
5. FROM: TO: Hrs. Mins.
TOTAL VOLUME: 2,67$ MSCF
Intermittent Black
Yes No Smoke? Planned? VOLUME
Q ^ ^ ^ 2,67$ MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE:_ RUPTURE DISK:_ CONTROLLED SLOWDOWN: X OTHER:
First Determination of Cause:
1. Flaring occured intermittently to depressure plant during shutdown to repair various equipment.
2.
3.
4.
5.
Action Taken to Stop Flaring:
1. None as this was necessary to provide a safe working enviroment for operating personnel.
2.
3.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
u
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Facility Operator Field(s) Month/Year of Disposition
GATIiERING CENTf:R 3 BP EXPLORATION AI.,ASKA WESTERN OPERATING AREA-PB Se -96
Disposition *Indieate contribution of each pool to total.
1. Sold 0 Pool Name Code Percent
2. Reinjected 0 PRTJDEIOE Cr~01.50 100
3. Flared or vented less than 1 hour 3,107
4. Flared or vented greater than 1 hour 2,335
(Su lemental re rt aired--See 20 AAC 25.235)
5. Pilot and Purge 29,754
6. Used for lease operations 507,263
Official Use Onl --Flarin Authorization > 1 hr.
1. Safety MCF
2. Lease Use MCF
3. Conserv. Purposes MCF
Commissioner Date
11. Transferred to: CCP 22,837,526
7.Other 0
TOTAL items 1 - 7 542,459
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
Note: All volumes must be corrected to
pressure of 14.65 psia and to a temperature of
60 degrees F. Report due by the 20th of the
month following the month of disposition.
Authority 20 AAC 25.235.
Form 10-422 (Re d 4/95)
Remarks:
I hereby certify that th regoins is true and correct to the best of my knowledee.
Signature: Title: SUPERVISOR
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-3
GAS FLARING INCIDENT REPORT
SEPTEMBER, 1996
Page i
Unplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
9/3/96 1658-1733 100 Not required for unplanned events which Not required for unplanned events which
9/4/96 2148-2210 2,399 are less than or equal to 1 hour are less than or equal to 1 hour
9/6/96 1545-1605 185
9/10/96 1334-1408 104
9/28/96 0857-0920 319
TOTAL 3,107
Unplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
9/10/96 0921-1025 2,335 See Attachments See Attachments
TOTAL 2,335
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf ~
_~
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION'TAKEN TO ELIMINATE CAUSE
TOTAL 0
Planned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
TOTAL 0
•
TOTAL
Unplanned Events < 1 Hour 3,107 '~~~~~
~~
Unplanned Events > 1 Hour 2,335 ~->,,:
~..
Planned Events < 1 hour & not 0 ~,,.v>
,.__
'
exceeding 5,000 MCF t,_A•,.
`-
~:~,,
Planned Events > 1 hour and 0 ~.._' .._
exceeding 5,000 MCF
Pilot Purge 29.754 ~-
~? TOTAL FLARED VOLUME 35,196
".
REPORT NO: 9G-3483
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 10 Sep 96 TOTAL VOLUME: 2,439 MSCF
Intermittent Black
TIME OF F LARING: DURA TION: Yes No Smoke? Planned? VOLUME
1. FROM: 09:21 TO: 10:25 1 Hrs. 4 Mins. Q ^ ^ ^ 2,335 MSCF
2. FROM: 13:34 TO: 14:08 0 Hrs. 34 Mins. Q ^ ^ ^ 104 MSCF
3. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
4. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
5. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:
First Determination of Cause:
1. LPS compressor K-7001 was shut down due to a problem associated with high delta pressure across their hydraulic oil
filters.
2. While bringing production rates up following K7001 LPS compressor filter change out, LPS compressors exceeded
maximum gas capacity and discharged to flare.
3.
4.
5.
Action Taken to Stop Flaring:
1. BP started reducing LPS rates at 0825 hours, in order to shut down K7001 (to change out the filters) and close the flare
valves.
2. No response taken as this was deemed to be of short duration.
3.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: - No: _
AOGCC Representative: Date: BPX Representative: Date:
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
r~
L_I
•
(Facility (Operator (Field(s) ~Month/Year of Disposition
GATHERING CENTER 3 BP EXPLORATION ALASKA WESTERN OPERATING AREA-PB Aug-96
Disposition
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour 5,750
4. Flared or vented greater than 1 hour
(Supplemental report required--See 20 AAC 25.235) 0
5. Pilot and Purge 31,694
6. Used for lease operations 545,655
7.Other 0
TOTAL items 1 - 7 583,099
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 24,445,374
Remarks:
I hereby certify that the foresoine is true and correct to the best of my knowled¢e.
Signature: Title: SUPERVISOR
f~~ ~~~t'~--~ A Z`f
Form 10-422 (lYevised 4/95)
*Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100
Ofticial Use Onl --Flarin Authorization> 1 hr.
1. Safety MCF
2. Lease Use MCF
3. Conserv. Purposes MCF
Commissioner Date
Note: All volumes must be corrected to
pressure of 14.65 psia and to a temperature of
60 degrees F. Report due by the 20th of the
month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC. Page 1
PRUDHOE BAY UNIT - GC-3
GAS FLARING INCIDENT REPORT
AUGUST, 1996
Unplanned Events less than or equal to 1 hour ~
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
8/12/96 2207-2231 2,875 Not required for unplanned events which Not required for unplanned events which
8/29/96 0744-0806 115 are less than or equal to 1 hour are less than or equal to 1 hour
8/30/96 1142-1227 2,500
8/30/96 1417-1443 260
TOTAL 5,750
Unplanned Events greater than 1 hour
•
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
TOTAL 0
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
TOTAL 0
Planned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
TOTAL 0
TOTAL
Unplanned Events < 1 Hour 5,750
Unplanned Events > 1 Hour 0
Planned Events < 1 hour & not 0
exceeding 5,000 MCF
Planned Events > 1 hour and 0
exceeding 5,000 MCF
Pilot Purge 31.694
TOTAL FLARED VOLUME 37,444
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Facility Operator Field(s) Month/Year of Disposition
GATHERING CENTER 3 BP EXPLORATION ALASKA WESTERN OPERATING AREA-PB Jul-96
•
u
Disposition
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour 15,113
4. Flared or vented greater than 1 hour
(Supplemental report required--See 20 AAC 25.235) 0
5. Pilot and Purge 32,035
6. Used for lease operations 528,549
7.Other 0
TOTAL items 1 - 7 575,697
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 22,981,456
Remarks:
I hereby certify that the fore¢oins is true and correct to the best of my knowledge.
Signature: ~C~~ ~c~ ~~ ~~~"'`''~ Title: SUPERVISOR
Form 10-422 (Revised 4/95)
*Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100
Official Use On1 =-Flaring Authorization > 1 hr.
1. Safety MCF
2. Lease Use MCF
3. Conserv. Purposes MCF
Commissioner Date
Note: All volumes must be corrected to
pressure of 14.65 psia and to a temperature of
60 degrees F. Report due by the 20th of the
month following the month of disposition.
Authority 20 AAC 25.235.
•
u
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-3
GAS FLARING INCIDENT REPORT
JULY, 1996
Page 1
~Unpl_ned Events less than or equal to 1 hour ._. ~ ~
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
7/3/96 1456-1503 68 Not required for unplanned events which Not required for unplanned events which
7/6/96 2018-2037 330 are less than or equal to 1 hour are less than or equal to 1 hour
7/15/96 1113-1129 2,311
7/17/96 1613-1615 182
7/23/96 2133-2225 9,389
7/24/96 0518-0542 2,833
TOTAL 15,113
Unplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
TOTAL
0
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf ~
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
TOTAL 0
Planned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
TOTAL 0
TOTAL
Unplanned Events < 1 Hour 15,113
Unplanned Events > 1 Hour 0
Planned Events < 1 hour & not 0
exceeding 5,000 MCF
Planned Events > 1 hour and 0
exceeding 5,000 MCF
Pilot Purge 32.035
TOTAL FLARED VOLUME 47,148
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Facility Operator Field(s) Month/Year of Disposition
GATIiERING CI;NTF.,R 3 BP I3XPLORA'CION AI.A:SKA wES'I'FRN OPT;RAT'ING ARFA-PBI. Jun-96
C~
J
U
Disposition
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour 8;246
4. Flared or vented greater than 1 hour
(Supplemental report required--See 20 AAC 25.235) 0
5. Pilot and Purge 31.,144
6. Used for lease operations 518,353
7.Other 0
TOTAL items 1 - 7 557,743
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 20,389,154
Remarks:
I hereby certify th a foregoin¢ is true and wrrect to the best of my knowledse.
Signature: _ Title: SUPERVISOR
Form 1022 (Revised 4/95)
*Indicate contribution of each pool to total.
Pool Name Code Percent
PRTJI)IIOE 040150 100
:Official. Use Onl --Flarin Authorization > 1_hr.
1. Safety MCF
2. Lease Use MCF
3. Conserv. Proposes MCF
Commissioner Date
must be corrected to
pressure of 14.65 psia and to a temperature of
60 degrees F. Report due by the 20th of the
month following the monW of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GCS
GAS FLARING INCIDENT REPORT
JUNE, 1996
Page 1
Unplanned Events less than or equal to 1 hour ~
DATE TIME VOLUME DESCRIPTION OF INCIDENT,& CAUSE ACTION TAKEN TO ELIMINATE CAUSE
6/16/96 1339-1416 7,708 Not required for unplanned events which Not required for unplanned events which
6/22/96 0758-0855 538 are less than or equal to 1 hour are less than or equal to 1 hour
TOTAL 8,246
Unplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
• See Attachments See Attachments
TOTAL 0
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf ~
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
TOTAL 0
Planned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION 4F INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
TOTAL 0
TOTAL
• Unplanned Events < 1 Hour 8,246
Unplanned Events > 1 Hour 0
.Planned Events < 1 hour & not 0
exceeding 5,000 MCF
Planned Events > 1 hour and 0
exceeding 5,000 MCF
Pilot Purge 31.144
TOTAL FLARED VOLUME 39,390
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Facility Operator Field(s) Month/Year of Disposition
r~
~ J
~ GATIiFRING CENTER 3 ABP EXPLC)RATION ALASKA ~ WESTERN C)
Disposition
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour 1,514
4. Flared or vented Qreater than 1 hour
(Sup lemental report required--See 20 AAC 25.235) 3,176
5. Pilot and Purge 27,991
6. Used for lease operations 529,173
7.Other 0
TOTAL items 1- 7 561,854
8. NGL gas equivalent produced 0
9. Purchased >;as 0
10. Transferred from: 0
11. Transferred to: CCP 23,180,979
Remarks:
I hereby certify that the fore¢oins is true .and correct to the best of my 1rnowledQe.
Signature: ~C~ Lc...-r~.. ~ Title: SUPERVISOR
Form 10-422 (Revised 4/95)
*Indicate contribution of each pool to total.
Pool Name Code Percent
PRI.JDIiOE 640150 100
Official Use Onl --Flarin Authorization > 1 hr.
1. Safety MCF
2. Lease Use MCF
3. Conserv. Purposes MCF
Commissioner Date
Note: All volumes must be corrected to
pressure of 14.65 psia and to a temperature of
60 degrees F. Report due by the 20th of the
month following the month of disposition.
Authority 20 AAC 25.235.
i
C~
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-3
GAS FLARING INCIDENT REPORT
MAY, 1996
Page 1
Unplanned Events less than or equal to 1 hour ~
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN"TO ELIMINATE CAUSE
5/6/96 0508-0542 567 Not required for unplanned events which Not required for unplanned events which
5/8/96 0333-0428 76 are less than or equal to 1 hour are less than or equal to 1 hour
5/8/96 1734-1749 104
5/11 /96 0640-0655 156
5/23/96 0441-0459 500
5/25/96 0950-0958 111
TOTAL 1,514
Unplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
5/7/96 1930-2359 3,176 See Attachments See Attachments
TOTAL 3,176
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
TOTAL 0
Planned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
TOTAL 0
f":
:
..
~
TOTAL ~ r- ,~
Unplanned Events < 1 Hour 1, 514
t~
~.. a i?
~ ,,~
Unplanned Events > 1 Hour 3,176
~
~ oif
o
Planned Events < 1 hour & not 0
exceeding 5,000 MCF
Planned Events > 1 hour and 0
exceeding 5,000 MCF
Pilot Purge 27.991
TOTAL FLARED VOLUME 32,681
REPORT NO: 96-3313
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: O7 May 96 TOTAL VOLUME: 3,176 MSCF
Intermittent Black
TIME OF FLARING: DURATION: Yes No Smoke? Planned? VOLUME
~. FROM: 19:30 TO: 23:59 4 Hrs. 29 Mins. ^ Q ^ ^ 3,176 MSCF
2. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
3. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
4. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
5. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. GC-3 was s/d due to transit pipeline s/d. Gas was leaking into the flare header which could cause black smoke. Assist
gas was added to prevent black smoke.
2.
3.
4.
5.
Action Taken to Stop Flaring:
1. Operations personnel attempted to find where the gas to the flare header was leaking from.
2.
3.
4.
5.
~~~~~~~d
Jlli~~ 1 7 ~~~6
Alaska Ci! & Gas G~sis. Commission
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
~ ~
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Facility Operator Field(s) Month/Year of Disposition
GATHERING CENTER 3 ARCO ALASKA, INC. WESTERN OPERATING AREA-PB A r-96
u
•
Disposition
1. Sold 0
2. Reinjected 0
3. Flazed or vented less than 1 hour 11,468
4. Flared or vented greater than 1 hour
(Supplemental report required--See 20 AAC 25.235) 17,842
5. Pilot and Purge 11,981
6. Used for lease operations 538,166
7.Other 0
TOTAL items 1 - 7 579,457
8. NGL ~as equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 23,535,761
Remarks:
I hereby certify that the foregoing is true and correct to the best of my knowledge.
Signatttre:~~~~ _ _ Title: SUPERVISOR
Form 10-422 (Revised 4/95)
*Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100
RECEIV
MA 1 6 19 6
Oil & s Cons.
Note: All volumes must be corrected to
pressttre of 14.65 psia and to a temperature of
60 degrees F. Report due by the 20th of the
month following the month of disposition.
Authority 20 AAC 25.235.
•
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-3
GAS FLARING INCIDENT REPORT
APRIL, 1996
Page 1
Unplanned Events less than or equal to 1 hour ~
DATE
TIME .. ~~~.
VOLUME DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
4/2/96 2301-2400 5,448 Not required for unplanned events which Not required for unplanned events which
4/3/96 2232-2300 259 are less than or equal to 1 hour are less than or equal to 1 hour
4/9/96 0535-0551 189
4/9/96 1708-1742 224
4/10/96 1605-1621 167
4/11/96 1802-1833 603 ~V ~p
4/17/96 1357-1440 111 ~~E
4/18/96 1337-1352 156
4/19/96 0057-0142 375 ~Q~ ~ ~ 19~~
4/20/96 1226-1234 28
~~
4/21 /96 2022-2050 58 ~ & ~, fwpt+~~ ~~
~
4/23/96 1308-1350 496 '~
p-
4/23/96 1506-1534 467
4/23/96 2123-2204 1,794
4/24/96 0047-0142 229
4/24/96 0325-0354 363
4/24/96 0455-0505 42
4/24/96 1030-1045 250
4/29/96 0206-0215 188
4/30/96 2030-2036 21
TOTAL 11,468
Unplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCID
4/3/96 0000-0124 3,208 See Attachments
4/3/96 0124-0924 3,600 See Attachments
4/4/96 1011-1449 367 See Attachments
4/6/96 1220-1529 567 See Attachments
4/16/96 1824-1942 1,679 See Attachments
4/19/96 0533-0635 288 See Attachments
4/23/96 0528-0900 1,472 See Attachments
4/23/96 1030-1240 2,167 See Attachments
4/24/96 0508-0950 3,525 See Attachments
4/30/96 0246-0419 969 See Attachments
TOTAL 17,842
& CAUSE ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
See Attachments
See Attachments
See Attachments
See Attachments
See Attachments
See Attachments
See Attachments
See Attachments
See Attachments
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf
• BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-3
GAS FLARING INCIDENT REPORT
APRIL, 1996
DATE TIME VOLUME .DESCRIPTION OF INCIDENT & CAUSE
TOTAL 0
Planned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
L J
TOTAL
0
TOTAL
Unplanned Events < 1 Hour 11,468
Unplanned Events > 1 Hour 17,842
Planned Events < 1 hour & not 0
exceeding 5,000 MCF
Planned Events > 1 hour and 0
exceeding 5,000 MCF
Pilot Purge 11.981
TOTAL FLARED VOLUME 41,291
ACTION TAKEN TO ELIM{NATE CAUSE
ACTION tAKEN TO ELIMINATE CAUSE
Page 2
•
•
REPORT NO: 9G-3273
FACILITY: Ci.C-3
BPX FLARE REPORT
PRUDHOE BAY
DATE: 02 Apr 96
TIME OF FLARING:
1. FROM: 23:01 To: 24:00
2. FROM: TO:
3. FROM: TO:
4. FROM: TO:
5. FROM: TO:
DURATION:
0 Hrs. 59 Mins.
Hrs. Mins.
Hrs. Mins.
Hrs. Mins.
Hrs. Mins.
TOTAL VOLUME: 5,448 MSCF
Intermittent Black
Yes No Smoke? Planned? VOLUME
^ Q ^ ^ 5,448 MscF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. A PLC failure caused the LPS turbines to shutdown due to the loss of cooling water and instrument air.
2.
3.
4.
5.
Action Taken to Stop Flaring:
1. At 2330 hrs BPX shut in 14 wells totalling 250 mmscf to reduce to one LPS compressor operation. However, at 2331
hrs the remaining LPS compressor SD. At 2345 hrs BPX shutin the remaining wells aligned to the LPS compressors (39
wells totalling 200 mmscf).
2.
3.
4.
5.
RECE4VED
~~~~~ t
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No: _
AOGCC Representative: Date: BPX Representative: Date:
•
i
REPORT NO: 96-$274
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 03 Apr 96 TOTAL VOLUME: 7,067 MSCF
Intermittent Black
TIME OF F LARING: DURATION: Yes No Smoke? Planned? VOLUME
1. FROM: OO:OO TO: 01:24 1 Hrs. 24 Mins. ^ Q ^ ^ 3,208 MSCF
2. FROM: 01:24 To: 09:24 8 Hrs. 0 Mins. ^ Q ^ ^ 3,600 MSCF
3. FROM: 22:32 TO: 23:00 0 Hrs. 28 Mins. ^ Q ^ ^ 259 MSCF
4. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
5. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:
First Determination of Cause:
1. Continued from 04/02/96 (See Report #96-327
2. Assist gas was used to prevent black smoke. Problems with the LP system continued through the morning.
Investigation of low LP Flare system found that one of the LP flare valves was open 100%. The flare valve display on
DCS indicated both flare valves were 100% closed. -~~~~`""-
3. High gas transit line pressure caused by CGF compressor problems due to booster 1801 SD.
4.
5.
Action Taken to Stop Flaring:
1. Continued from 04/02/96
2. Assist gas was used to mitigate black smoke.
3. BPX reduced production rates and shut-in 3 wells equaling 80 mmcfd. ARCO reduced production rates and started
flaring at the FS1 Annex. ARCO called maintance out after second start failed, and BPX and ARCO continued to reduce
production rates.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: ` No: _
AOGCC Representative: Date: BPX Representative: Date:
• i
REPORT NO: 96-SZ76
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 04 Apr 96
TIME OF FLARING:
1. FROM: 10:11 To: 14:49
2. FROM: TO:
3. FROM: TO:
4. FROM: TO:
5. FROM: TO:
DURATION:
4 Hrs. 38 Mins
Hrs. Mins
Hrs. Mins
Hrs. Mins
Hrs. Mins
TOTAL VOLUME: 367 MSCF
Intermittent Black
Yes No Smoke? Planned? VOLUME
X^ ^ ^ ^ 367 MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
20°F.
2.
3.
4.
5.
Action Taken to Stop Flaring:
1. BPX reduced production rates and shut-in 1 well was shut in and two wells were choked back for a total 25mmcfd. Wells
were shut-in or choked back starting at 10:40 hours.
2.
3.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
•
•
REPORT NO: 96-3279
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: ~aC-3 DATE: O6 Apl' 96
TIME OF FLARING:
1. FROM: 12:20 To: 15:29
2. FROM: TO:
3. FROM: TO:
4. FROM: TO:
5. FROM: TO:
DURATION:
3 Hrs. 9 Mins.
Hrs. Mins.
Hrs. Mins.
Hrs. Mins.
Hrs. Mins.
TOTAL VOLUME: 567 MSCF
Intermittent Black
Yes No Smoke? Planned? VOLUME
Q ^ ^ ^ 567 MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
8°F.
2.
3.
4.
5.
Action Taken to Stop Flaring:
1. BPX reduced production rates and shut-in 3 wells equaling 95 mmcfd. ARCO reduced production rates and shut-in
6wells equaling70 mmcfd. Wells were shut-in or choked back starting at 16:00 hours.
2.
3.
4.
5.
RECEIVED
MAY 1 ~ 199&
Alasicai tlil ~ Gs~ Wis. ~rissia-
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
•
•
REPORT NO: 96-3289 ,
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 16 Apr 96
TIME OF FLARING:
1. FROM: 18:24 To: 19:42
2. FROM: TO:
3. FROM: TO:
4. FROM: TO:
5. FROM: TO:
DURATION:
1 Hrs. 18 Mins.
Hrs. Mins.
Hrs. Mins.
Hrs. Mins.
Hrs. Mins.
TOTAL VOLUME:
Intermittent Black
Yes No Smoke? Planned?
^ X^ ^ ^
^ ^ ^ ^
^ ^ ^ ^
^ ^ ^ ^
^ ^ ^ ^
1,679 MscF
VOLUME
1,679 MSCF
MSCF
MSCF
MSCF
MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. High gas transit line pressure caused by CCP compressor problems due to swapping inverters.
2.
3.
4.
5.
Action Taken to Stop Flaring:
1. Flaring was permitted to continue while CCPoperations personnel attempted to restart the equipment. BPX reduced
production rates and shut-in 9 wells equaling 200 mmcfd. ARCO reduced production rates and shut-in 22wells equaling
400mmcfd. Wells were shut-in or choked back starting at19:30 hours.
2.
3.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
•
REPORT NO: 96-3295
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 19 Apr 96 TOTAL VOLUME: 663 MscF
Intermittent Black
TIME OF F LARING: DURATION: Yes No Smoke? Planned? VOLUME
1. FROM: 00:57 TO: 01:42 0 Hrs. 45 Mins. ^ Q ^ ^ 375 MSCF
2. FROM: 05:33 TO: 06:35 1 Hrs. 2 Mins. Q ^ ^ ^ 288 MSCF
3. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
4. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
5. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. High gas transit line pressure caused by CGF compressor problems due to # 2 Booster Compressor 1802 S/D.
2. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
8°F.
3.
4.
5.
Action Taken to Stop Flaring:
1. BPX reduced production rates and shut-in 4 wells equaling106 mmcfd. Wells were shut-in or choked back starting at
01:26 hours.
2. BPX reduced production rates and shut-in 4 wells equaling 70 mmcfd. Wells were shut-in or choked back starting at
06:10 hours.
3.
4.
5.
RECEIVED
MAY 1 !~ 1~91~
~a~11 ~~. ~m~
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
• ..
REPORT NO: 96-3299 ,
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 23 Apr 96 TOTAL VOLUME: 6,396 MSCF
Intermittent Black
TIME OF F LARING: DURATION: Yes No Smoke? Planned? VOLUME
1. FROM: 05:28 TO: 09:00 3 Hrs. 32 Mins. ^ X^ ^ ^ 1,472 MSCF
2. FROM: 10:30 TO: 12:40 2 Hrs. 10 Mins. ^ Q ^ ^ 2,167 MSCF
3. FROM: 13:08 TO: 13:50 0 Hrs. 42 Mins. ^ X^ ^ ^ 496 MSCF
4. FROM: 15:06 TO: 15:34 0 Hrs. 28 Mins. ^ Q ^ ^ 467 MSCF
5. FROM: 21:23 TO: 22:04 0 Hrs. 41 Mins. ^ Q ^ ^ 1,794 MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. Sk-18 LP compressor shut down due to lack of gas to keep the compressor on line. The LP flare assist gas was opened
to prevent black smoke resulting from the increased pressure on the LP flare header. (NOTE: GC3 is at reduced
production rates due to oppportunity maintenance work as a result of theTAPS slowdown).
2. Sk-18 LP compressor shut down due to lack of gas to keep the compressor on line. The LP flare assist gas was opened
to prevent black smoke resulting from the increased pressure on the LP flare header. (NOTE: GC3 is at reduced
production rates due to oppportunity maintenance work as a result of theTAPS slowdown).
3. Sk-18 LP compressor shut down due to lack of gas to keep the compressor on line. The LP flare assist gas was opened
to prevent black smoke resulting from the increased pressure on the LP flare header. (NOTE: GC3 is at reduced
production rates due to oppportunity maintenance work as a result of theTAPS slowdown).
4. Sk-18 LP compressor shut down due to lack of gas to keep the compressor on line. The LP flare assist gas was opened
to prevent black smoke resulting from the increased pressure on the LP flare header. (NOTE: GC3 is at reduced
production rates due to oppportunity maintenance work as a result of theTAPS slowdown).
5. Asset Area TEG regeneration system shut down because of a problem associated with bringing rate back on following
TAPS slowdown.
Action Taken to Stop Flaring:
1. BPX increased production rates to GC3 following completion of maintenance work and repairs.
2. BPX increased production rates to GC3 following completion of maintenance work and repairs.
3. BPX increased production rates to GC3 following completion of maintenance work and repairs.
4. BPX increased production rates to GC3 following completion of maintenance work and repairs.
5. BPX reduced production rates and shut-in 8 wells equaling 162 mmcfd. Wells were shut-in or choked back starting at
21:25 hours.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No: _
AOGCC Representative: Date: BPX Representative: Date:
•
• .
REPORT NO: 96-3300
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 24 Apr 96
TOTAL VOLUME: 4,409 MSCF
Intermittent Black
TIME OF F LARING: DURATION: Yes No Smoke? Planned? VOLUME
1. FROM: 00:47 TO: 01:42 0 Hrs. 55 Mins. ^ Q ^ ^ 229 MSCF
2. FROM: 03:25 TO: 03:54 0 Hrs. 29 Mins. ^ Q ^ ^ 363 MSCF
3. FROM: 05:08 TO: 09:50 4 Hrs. 42 Mins. ^ Q ^ ^ 3,525 MSCF
4. FROM: 04:55 TO: 05:05 0 Hrs. 10 Mins. ^ Q Q ^ 42 MSCF
5. FROM: 10:30 To: 10:45 0 Hrs. 15 Mins. ^ Q ^ ^ 250 MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:
First Determination of Cause:
1. Sk-18 LP compressor shut down .The LP flare assist gas was opened to prevent black smoke resulting from the
increased pressure on the LP flare header.
2. Sk-18 LP compressor shut down .The LP flare assist gas was opened to prevent black smoke resulting from the
increased pressure on the LP flare header.
3. Sk-18 LP compressor shut down .The LP flare assist gas was opened to prevent black smoke resulting from the
increased pressure on the LP flare header.
4. The LP flare assist gas was opened to prevent black smoke resulting from the increased pressure on the LP flare
header. GC-3 tried cutting back on their LP flare assist gas.
5. Sk-18 LP compressor shut down .The LP flare assist gas was opened to prevent black smoke resulting from the
increased pressure on the LP flare header.
Action Taken to Stop Flaring:
1. K-306 LP Compressor re-started.
2. K-306 LP Compressor re-started.
3. K-306 LP Compressor re-started.
4. GC-3 opened their LP flare assist gas. Black smoke clear up immediately.
5. K-306 LP Compressor re-started.
RECEIVED
MAY 1 6 1996
Alas Oil & Aa
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
•
• ',
REPORT NO: 96-3308 ,
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 30 Apr 96
TIME OF FLARING:
1. FROM: 02:46 To: 04:19
2. FROM: 20:30 TO: 20:36
3. FROM: TO:
4. FROM: TO:
5. FROM: TO:
DURATION:
1 Hrs. 33 Mins.
0 Hrs. 6 Mins.
Hrs. Mins.
Hrs. Mins.
Hrs. Mins.
TOTAL VOLUME: QQO MSCF
Intermittent Black
Yes No Smoke? Planned? VOLUME
^ Q ^ ^ 969 MSCF
^ X^ ^ ^ 21 MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:
First Determination of Cause:
1. Sk-18 LP compressor shut down because of a unknown reason. The incident is being further investigated.
2. Sk-18 LP compressor shut down because of a unknown reason. The incident is being further investigated.
3. ~y.-~LANfti'7'I0N P'
4.
5.
Action Taken to Stop Flaring:
1. Equipment was restarted at 04:06hours.
2. Equipment was restarted at 20:36hours.
3.
4.
5.
RECEIVED
MAY 1 F 199&
Alaska Oil & Gas Cons. Cnmmisston
Anchorage
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Facility Operator Field(s) Mon[h/Year of Disposition
GATHERING CENTER 3 ARCO ALASKA, INC. WESTERN OPERATING AREA-PB Mar-96
•
•
Disposition
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour 1,250
4. Flared or vented greater than 1 hour
(Supplemental report required--See 20 AAC 25.235) 0
5. Pilot and Purge 14,031
6. Used for lease operations 581,902
7.Other 0
TOTAL items 1 - 7 597,183
8. NGL gas equivalent produced 0
T: ~
9. Purchased gas ~~~ ~~ ° ~" ~~
0
10. Transferred from: "~~~`~ ~ ~ ~ ~ 0
(',,g
11. Transferred to: CCP '' ,. .
26,168,866
Remarks:
T herehv certify that. the frtregning is mie and correct to the hest. of my knowledge.
Signature:~~~~'~~~. Title: SUPERVISOR
orm evtse
*Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100
Official Use Onl -=Flarin Authorization ~ 1 hr.
1. Safety MCF
2. Lease Use MCF
3. Conserv. Purposes MCF
Commissioner Date
Note: All volumes must be corrected to
pressure of 14.65 psia and to a temperature of
60 degrees F. Report due by the 20th of the
month following the month of disposition.
Authority 20 AAC 25.235.
~J
r
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-3
GAS FLARING INCIDENT REPORT
MARCH, 1996
Page 1
Unplanned Events less than or equal to 1 hour
- -- - - -------
..... .......................................... ......................................................... 1t1~4':~G#~~#I~.::::::::::::::::::::::::.~:.
3/1/96 0108-0120 92 Not required for unplanned events which Not required for unplanned events which
313/96 1329-1338 100 are less than or equal to 1 hour are less than or equal to 1 hour
3/8/96 0000-0044 581
3/10/96 2141-2155 214
3/23/96 1530-1533 15
3/30/96 1210-1244 215
3/30/96 2030-2046 33
Tr~TAI 1 95(1
Unplanned Events < 1 Hour 1,250
Unplanned Events > 1 Hour 0
Planned Events < 1 hour 8~ not 0
exceeding 5,000 MCF
Planned Events > 1 hour and 0
exceeding 5,000 MCF
Pilot Purge 14.031
TOTAL FLARED VOLUME 15,281
~~
~11u~;s?t~ t~ii ~ C^~ I~~~v. C~:t~~issi;'~,
i~ii~isJn ~;~
See Attachments See Attachments
TOTAL 0
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
u
GATHERING CENTER 3
INC.
Field(s)
WESTERN OPERATING
Disposition
1. Sold 0
2. Reinjected 0
3. Flared or vented less than 1 hour 8,525
4. Flared or vented greater than 1 hour
(Supplemental report required--See 20 AAC 25.235) 2,010
5. Pilot and Purge 15,558
6. Used for lease operations 558,040
7.Other 0
TOTAL items 1 - 7 584,133
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: p
11. Transferred to: CCP 24,523,852
Remarks:
l herehv rertifv that the fr,reQ~ing is trne and canrrect t~ the heel ~f my knnwlP.rige.
Signature: ~ Title: SUPERVISOR
orm evtse
Month/Year of Disposition
Feb-96
*Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100
Note: All volumes must be corrected to
pressure of 14.65 psia and to a temperature of
60 degrees F. Report due by the 20th of the
month following the month of disposition.
Authority 20 AAC 25.235.
•
LJ
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-3
GAS FLARING INCIDENT REPORT
FEBRUARY, 1996
Page 1
Unplanned Events less than or equal to 1 hour
.~.
~
DATE
TIME ..
~~
VOLUME DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
2/1/96 1847-1859 125 Not required for unplanned events which Not required for unplanned events which
2/2/96 0014-0029 156 are less than or equal to 1 hour are less than or equal to 1 hour
2/5/96 0736-0745 63
2/5/96 1010-1041 177
2/7/96 0737-0825 3,333
2/8/96 0919-1003 794
2/8/96 1300-1332 422
2/12/96 0820-0906 375
2/14/96 1228-1232 19
2/15/96 0603-0637 590
2/17/96 1340-1414 708
2/18/96 1231-1320 778
2/21/96 1928-1942 175
2/23/96 0640-0649 25
2/25/96 0801-0844 568
2/25/96 2348-2400 100
2/26/96 1648-1716 117
TOTAL 8,525
Unplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE CAUSE
2/6/96 0745-1058 2,010 See Attachments See Attachments
TOTAL 2,010
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-3
GAS FLARING INCIDENT REPORT
FEBRUARY, 1996
Page 2
Planned Events Less Than or Equal 1 Hour AND Not Exceeding 5000 Mcf ~
--~-~
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE ACTION TAKEN TO ELIMINATE GAUSE
TOTAL
Planned Events Exceed
DATE TIME
TOTAL
Unplanned Events < 1 Hour
Unplanned Events > 1 Hour
Planned Events < 1 hour & not
exceeding 5,000 MCF
Planned Events > 1 hour and
exceeding 5,000 MCF
• Pilot Purge
TOTAL FLARED VOLUME
0
Hour OR Exceeding 5000 Mcf
VOLUME DESCRIPTION OF INCIDENT & CAUSE
ACTION TAKEN TO ELIMINATE CAUSE
0
TOTAL
8,525
2,010
0
0
15.558
26,093
REPORT NO: 96-3218
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 06 Feb 96 TOTAL VOLUME: 2,QiQ MSCF
Intermittent Black
TIME OF FLARING: DURATION: Yes No Smoke? Planned? VOLUME
1. FROM: 07:45 To: 10:58 3 Hrs. 13 Mins. ^ Q ^ ^ 2,010 MSCF
2. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
3. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
4. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
5. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. Following a plant shut-down for electrical breaker repair, the plant was being brought on-line. Sk-18 compressor K-305
was found to have a valve sequencing problems. Production was maintained to prevent freezing and to allow for plant
start-up. The ambient temperature was -26F.
2.
3.
4.
5.
Action Taken to Stop Flaring:
1. Equipment was restarted at 10:55 hours.
2.
3.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
ALASKA OIL AND GAS CONSERVATION COMMISSION
FACILITY REPORT OF PRODUCED GAS DISPOSITION
Facility Operator Field(s) Monti-IYeaz of Disposition
GATHERING CENTER 3 ARCO ALASI{A, INC. WESTERN OPERATING AREA-PB Jan-96
LJ
r~
Disposition
1. Sold 0
2. Reinjected 0
3. Flazed or vented less than 1 hour 12,394
4. Flazed or vented greater than 1 hour
(Sup lemental report required--See 20 AAC 25.235) 2,439
5. Pilot and Purge 16,067
6. Used for lease operations 578,934
7.Other 0
TOTAL items 1 - 7 609,834
8. NGL gas equivalent produced 0
9. Purchased gas 0
10. Transferred from: 0
11. Transferred to: CCP 25,609,790
Remarks:
T herehv certify that the forevr,ing is trne an~i correct to the hest of my kn~wle.~lge.
Signature: ~ Title: SUPERVISOR
otm evtse
*Indicate contribution of each pool to total.
Pool Name Code Percent
PRUDHOE 640150 100
Note: All volumes must be corrected to
pressure of 14.65 psia and to a temperature of
60 degrees F. Report due by the 20th of the
month following the month of disposition.
Authority 20 AAC 25.235.
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-3
GAS FLARING INCIDENT REPORT
JANUARY, 1996
Unplanned Events less than or equal to 1 hour
DATE TIME VOLUME DESCRIPTION OFiNCIDENT & CAUSE
1/1/96 1720-1724 28 Not required for unplanned events which
1/3/96 0158-0212 97 are less than or equal to 1 hour
1 /3/96 0358-0433 222
1/4/96 0036-0055 2,560
1 /4/96. 0209-0239 1,417
1/4/96 0243-0310 3,750
• 1/4/96 0328-0344 2,222
1 /15/96 1527-1545 313
1 /19/96 1649-1711 229
1 /19/96 1957-2011 146
1 /26/96 0629-0659 146
1 /26/96 0707-0806 287
1 /28/96 2115-2205 250
1 /29/96 0435-0525 375
1 /29/96 2124-2200 104
1 /30/96 1122-1135 90
1 /30/96 1532-1539 68
1 /31 /96 0935-0954 90
TOTAL 12,394
Unplanned Events greater than 1 hour
DATE TIME VOLUME DESCRIPTION OFINCIDENT & CAUSE
1/1/96 2016-2128 243 See ~~ttachments
1/2/96 1043-1336 214 See Attachments
1/2/96 2016-2249 222 See Attachments
1/3/96 1247-1500 672 See Attachments
1/3/96 1816-1920 153 See Attachments
1/26/96 0817-0931 103 See Attachments
1/27/96 0913-1123 181 See Attachments
1/27/96 1436-2400 450 See Attachments
1/29/96 1355-1538 201 See Attachments
TOTAL 2,439
ACTION TAKEN TO ELIMINATE`CAUSE
Not required for unplanned events which
are less than or equal to 1 hour
ACTION TAKEN TO ELIMINATE CAUSE
See Attachments
See Attachments
See Attachments
See Attachments
See Attachments
See Attachments
See Attachments
See Attachments
See Attachments
Page 1
•~
Planned Events Less Than or Equal 1 Hour AND Not
DATE TIME VOLUAAE DESCRII
TOTAL ~ 0
BP EXPLORATION (ALASKA) INC.
PRUDHOE BAY UNIT - GC-3
GAS FLARING INCIDENT REPORT
JANUARY, 1996
eding 5000 Mcf
OF {NCIDENT & CAUSE
• Planned Events Exceeding 1 Hour OR Exceeding 5000 Mcf
DATE TIME VOLUME DESCRIPTION OF INCIDENT & CAUSE
TOTAL 0
Unplanned Events < 1 Hour
Unplanned Events > 1 Hour
Planned Events < 1 hour & not
exceeding 5,000 MCF
Planned Events > 1 hour and
exceeding 5,000 MCF
• Pilot Purge
TOTAL FLARED VOLUME
TOTAL.
12,394
2,439
0
0
.16.067
30,900
ACTION TAKEN TO ELIMINATE CAUSE
TAKEN TO ELIMINATE
Page 2
REPORT NO: 96-3171
*Correction
BPX FLARE REPORT
. , occ REP : PRUDHOE BAY
FACILITY: GC-3 D ATE: O1 Jan 96 TOTAL VOLUME: 271 MSCF
Intermittent Black
TIME OF FLARING: DURA TION: Yes No Smoke? Planned? VOLUME
1. FROM: 17:20 TO: 17:24 ~ Hrs. 4 Mins. ^ 0 ^ ^ 28 MSCF
2. FROM: 20:16 TO: 21:28 1 Hrs. 12 Mins. Q ^ ^ ^ 243 MSCF
3. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
4. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
5. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. High ambient temperature swings resulted in flaring and required cuts in LP production. Ambient temperature increased
by 10°F.
2. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
7°F.
3.
4.
5.
Action Taken to Stop Flaring:
1. BPX reduced production rates and shut-in 1 well equaling 10 mmcfd. Well was shut-in or choked back starting at 17:24
hours.
2. BPX reduced production rates and shut-in2wells equaling 40 mmcfd. ARCO reduced production rates and shut-in 4
wells equaling 100 mmcfd. Wells were shut-in or choked back starting at 20:00 hours.
3.
4.
5. *Flare report number corrected 01/06/95 from 95 series to 96 series
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
~ ~
REPORT NO: 96-3172
*Correction
BPX FLARE REPORT
OCC REP PRUDHOE BAY
FACILITY: GC-3 D ATE: 02 Jan 96 TOTAL VOLUME: 486 MSCF
Intermittent Black
TIME OF FLARING: DURA TION: Yes No Smoke? Planned? VOLUME
1. FROM: 10:43 TO: 13:36 2 Hrs. 53 Mins. Q ^ ^ ^ 214 MSCF
2. FROM: 20:16 TO: 22:49 2 Hrs. 33 Mins. Q ^ ^ ^ 222 MSCF
3. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
4. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
5. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
4°F.
2. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
6°F. These swings continued from 6deg. to 0 deg. and back up again during this flare period.
3.
4.
5.
Action Taken to Stop Flaring:
1. BPX reduced production rates and shut-in 3 wells equaling 55 mmcfd. Wells were shut-in or choked back starting at
12:03 hours.
2. BPX reduced production rates and shut-in 1 wells equaling 24 mmcfd. Wells were shut-in or choked back starting at
20:20 hours.
3.
4.
5, "Flare report number corrected 01/06/95 from 95 series to 96 series
„~.
..~» t;
vim;. A ~.
3 r} ~ IJ~~
t' t_ 1/ r
1~~: S~~SF2i`
,. ~ d„E#~` ~ ~
s~ ..
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No: _
AOGCC Representative: Date: BPX Representative: Date:
~ ~
~ OCC REP
FACILITY: ~aC-3
BPX FLARE REPORT
PRUDHOE BAY
DATE: 03 Jan 96
TIME OF FLARING:
i . FROM: 01:58 To: 02:12
2. FROM: 03:58 To: 04:33
3. FROM: 12:47 TO: 15:00
4. FROM: 1$:16 To: 19:20
5. FROM: TO:
DURATION:
0 Hrs. 14 Mins.
0 Hrs. 35 Mins.
2 Hrs. 13 Mins.
1 Hrs. 4 Mins.
Hrs. Mins.
Intermittent
Yes No
^ X^
^ X^
0 ^
^ ^
REPORT NO: 9G-3175
TOTAL VOLUME:
Black
Smoke? Planned?
^ ^
^ ^
^ ^
^ ^
^ ^
*Correction
1,144 MscF
VOLUME
97 MSCF
222 MSCF
672 MSCF
153 MscF
MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
6°F.
2. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
10°F. These swings continued from 6deg. to 0 deg. and back up again during this flare period.
3. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
8°F.
4. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
4°F.
5.
Action Taken to Stop Flaring:
1. BPX reduced production rates and shut-in 3 wells equaling 65 mmcfd. Wells were shut-in or choked back starting at
02:00 hours.
2. BPX reduced production rates and shut-in 3 wells equaling 60 mmcfd. Wells were shut-in or choked back starting at
04:10 hours.
3. BPX reduced production rates and shut-in 2 wells equaling 20 mmcfd. Wells were shut-in or choked back starting at
13:04 hours.
4. BPX reduced production rates and shut-in 2 wells equaling 30 mmcfd. Wells were shut-in or choked back starting at
18:40 hours.
5. *Flare report number corrected 01/06/95 from 95 series to 96 series
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
~ ~
REPORT NO: 96-3197
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: CaC-3 DATE: 26 fan 96
TOTAL VOLUME: 586 MSCF
Intermittent Black
TIME OF F LARING: DURATION: Yes No Smoke? Planned? VOLUME
1. FROM: 06:29 TO: 06:59 0 Hrs. 30 Mins. ^ Q ^ ^ 146 MSCF
2. FROM: 07:07 TO: 08:06 0 Hrs. 59 Mins. ^ Q ^ ^ 287 MSCF
3. FROM: 08:17 TO: 09:3 1 Hrs. 14 Mins. ^ X^ ^ ^ 103 MSCF
4. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
5. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. Sk-18 IP/LP compressors shut down because of a problem associated with low gas rates due to Pipeline slowdown.
2. Sk-18 IP/LP compressors shut down because of a problem associated with low gas rates due to Pipeline slowdown.
3. Sk-18 LP compressor K-306 shut down because of a problem associated with high vibrations (low gas rate due to Pipe-
line slowdown).
4.
5.
Action Taken to Stop Flaring:
1. Equipment was restarted at 06:59 hours.
2. Equipment was restarted at08:06 hours.
3. Equipment was restarted at 09:31 hours.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
~ ~
REPORT NO: 96-3201
BPX FLARE REPORT
PRUDHOE BAY
FACILITY: GC-3 DATE: 27 Jan 96
TOTAL VOLUME: 631 MSCF
Intermittent Black
TIME OF FLARING: DURATION: Yes No Smoke? Planned? VOLUME
1. FROM: 09:1.3 TO: 11:23 2 Hrs. 10 Mins. ^ Q Q ^ 181 MSCF
2. FROM: 14:36 TO: 24:00 9 Hrs. 24 Mins. ^ Q ^ ^ 450 MSCF
3. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
4. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
5. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:
First Determination of Cause:
1. Sk-18 LP compressor shut down because of a problem associated with high vibrations due to low LP gas rates.
2. Sk-18 LP compressor shut down because of a problem associated with high vibrations due to low LP gas rates.
3.
4.
5.
Action Taken to Stop Flaring:
1. Equipment was restarted at 11:23 hours.
2. Equipment was restarted at2400 hours.
3.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
~ ~
REPORT NO: 96-3206
BPX FLARE REPORT
PRUDHOE BAY
FACILITY:~.~C-3 DATE: 29 fan 96
TOTAL VOLUME: 680 MSCF
Intermittent Black
TIM E OF F LARING: DURATION: Yes No Smoke? Planned? VOLUME
1. FROM: 04:35 TO: 05:25 0 Hrs. 50 Mins. Q ^ ^ ^ 375 MSCF
2. FROM: 13:55 TO: 15:38 1 Hrs. 43 Mins. Q ^ ^ ^ 201 MSCF
3. FROM: 21:24 TO: 22:00 0 Hrs. 36 Mins. Q ^ ^ ^ 104 MSCF
4. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
5. FROM: TO: Hrs. Mins. ^ ^ ^ ^ MSCF
CHECK ONE: FLARE/RELIEF VALVE: X RUPTURE DISK:_ CONTROLLED BLOWDOWN:_ OTHER:_
First Determination of Cause:
1. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
20°F.
2. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
20°F.
3. High ambient temperature swings resulted in flaring and required cuts in production. Ambient temperature increased by
4°F.
4.
5.
Action Taken to Stop Flaring:
1. BPX reduced production rates and shut-in3 wells equaling50 mmcfd. Wells were shut-in or choked back starting at
04:30 hours.
2. BPX reduced production rates and shut-in 2 wells equaling30 mmcfd. Wells were shut-in or choked back starting at
14:00 hours.
3. BPX reduced production rates and shut-in1 wells equalin20 mmcfd. Wells were shut-in or choked back starting at 21:35
hours.
4.
5.
If >11 HRS., the PCC will notify AOGCC (907) 279-1433. STATE TELEPHONE REPORT? Yes: _ No:
AOGCC Representative: Date: BPX Representative: Date:
~ ~